PAS · Energy registers, water and gas
Energy registers: quantities, capacity and meter models
Start with what an electrical energy register measures, then distinguish native totals, programmable billing registers, tariffs and pulse counters.
Written course for development review; live pulse commissioning and recording pending.
Before you start
- Identify the exact model, firmware and fitted input modules. A PAS source list does not prove that every input exists on the meter.
- Read and save the current setups and required logs before changing sources, multipliers, tariffs or counters. Use an authorised training setup for programming exercises.
Power tells you the rate; energy tells you the accumulated amount
kW is active power. kWh is active energy accumulated over time. A cumulative reading is a running total; consumption for a period normally comes from the difference between matched start and finish readings, after checking for resets, rollover or scaling changes.
Worked example: a constant 12 kW load for 30 minutes uses 12 × 0.5 = 6 kWh. A single 12 kW snapshot does not prove that the load remained constant for that half-hour. kvarh records reactive energy; kVAh records apparent energy. Keep these quantities separate and do not add them to kWh.
Read the direction and quantity before reading the number
For a correctly installed supply meter, import normally means energy entering the monitored installation and export means energy leaving it. Confirm the wiring orientation and the model’s convention before assigning those meanings to a particular record. Import and export totals allow simultaneous generation and consumption to be examined without hiding either direction.
Quadrant reactive-energy readings describe different operating conditions; they are not four extra loads. Do not infer a model’s quadrant sign convention from the word import alone. Use its vector/quadrant definition when interpreting Q1–Q4.
| Reading | Unit | Interpretation |
|---|---|---|
| Active import / export | kWh | Keep two directional totals; subtract only when the analysis calls for net exchange. |
| Reactive import / export or quadrants | kvarh | Use the required reactive definition; do not combine overlapping totals. |
| Apparent energy | kVAh | A different quantity from kWh; a cumulative power-factor calculation needs matched definitions and periods. |
| Per-phase and whole-meter readings | Model dependent | Do not add phase readings to the aggregate reading: that would count the same measurement twice. |
The word register can mean several different things
A native energy total is a built-in measured quantity. A programmable summary or billing register accumulates an assigned source. TOU registers divide a source into tariff periods. A general pulse/event counter counts input or setpoint events. The physical digital input is the terminal receiving a signal; it is not the counter itself.
A Modbus register is also a transport word. A 32-bit value can occupy two 16-bit addresses but still represents one accumulated quantity. A long protocol address list is not a count of independently usable energy channels.
Match capacity to the exact meter
The table compares programmable accumulation systems, not the number of electrical reading names. Capacities are documented capabilities; installed modules, firmware and PAS support determine what is usable on an individual device.
| Model | Billing / TOU capacity | General counters | Physical inputs |
|---|---|---|---|
| EM133 base family | Operation-manual procedure describes 4 billing registers and up to 8 tariffs. | 4 general pulse/event counters. | 2 standard inputs; supported expansion options add 4, 8 or 12. Confirm the fitted option. |
| EM133-XM | Datasheet describes 8 totalisation/tariff groups × 8 tariffs. The XM protocol maps 12 billing setup/summary slots; see the qualification below. | 4 general pulse/event counters; keep these distinct from billing slots. | 2 built-in pulse inputs; up to 14 with a supported expansion option. |
| EM235 / PM335 PRO | 16 summary accumulators and 16 TOU sets, up to 16 tariffs per set. | 32 logical pulse/event counters. | Up to 26 DI with the specified optional built-in inputs, modules and supply arrangement. |
| PM180 | 16 summary accumulators and 16 TOU sets, up to 16 tariffs per set. | 32 logical pulse/event counters. | Up to 48 DI using three 16-DI modules; other module choices use the same available slots. |
Source 5 · Source 1 · Source 6 · Source 4 · Source 7 · Source 2 · Source 8 · Source 3
Why the XM count needs a check
The XM datasheet’s eight groups and the protocol’s twelve mapped Billing/TOU setup and summary slots describe conflicting published limits. The generic family manual’s four-register procedure must not be used as a universal XM limit. The protocol target-range text is also inconsistent. These documents alone do not establish how many groups your firmware and PAS combination can configure.
Record the model, firmware and PAS version, open the current meter’s Energy/TOU setup and list the usable register rows and source assignments. Preserve that readback with the setup backup. If the intended slot is missing or cannot be read back, resolve the version-specific limit with SATEC before relying on it. Do not experiment with raw register writes to discover capacity.
Limits and checks
- Worked values are teaching examples, not readings or settings from the demonstration meter. No live programming or pulse test is represented by this written lesson.
Check your understanding
Does 16 TOU sets with 16 tariffs mean 256 separate physical meters?
Sources
- Source 1. EM133 / EM133-XM Modbus Reference — energy and Billing/TOU (opens in a new tab)
BG0640 Rev. A1, PDF/printed pages 32–38, 65–66 and 77–80. Page 66 contains an inconsistent target-range label; it is not a programming instruction.
- Source 2. PRO EM235/PM335 Modbus Reference (opens in a new tab)
BG0613 Rev. A8, September 2025. PDF/printed pages 60, 72–73 and 85–87: counters, total/summary energy and TOU.
- Source 3. PM180 Modbus Reference (opens in a new tab)
BG0527 Rev. A11, September 2024. PDF/printed pages 55, 63–64 and 74–75: counters, total/summary energy and TOU.
- Source 4. EM13x Installation and Operation Manual — digital inputs and counters (opens in a new tab)
Printed pages 100–101 and 105–106 / PDF pages 103–104 and 108–109.
- Source 5. EM13x Installation and Operation Manual — Billing/TOU (opens in a new tab)
Printed pages 114–118 / PDF pages 117–121. Base-family procedure; XM capacity and units require the XM reference.
- Source 6. EM133-XM 5 A CT input datasheet — TOU and pulse inputs (opens in a new tab)
TBV1.1, PDF pages 1–2: eight totalisation/tariff groups, eight tariffs and up to fourteen digital pulse inputs. Compare with the exact installed version.
- Source 7. PRO Series Installation and Operation Manual (opens in a new tab)
BG0612 Rev. A8, December 2024. PDF/printed pages 10–12 (modules), 64, 80, 118 and 138–139. Some appendix/target tables differ; use the current protocol alongside the main chapters.
- Source 8. PM180 Operation Manual (opens in a new tab)
BG0525 Rev. A7, April 2019. Printed pages 9, 22, 75 and 117–118 / PDF pages 10, 23, 76 and 118–119.
Revision and review details
| Revision | Change and reason | Review / supersedes |
|---|---|---|
| 20261108-energy-v1 8 November 2026 | Added electricity-first energy and water/gas pulse-register lessons. Explain model-specific capacity, correct units, PAS setup and consumption checks. | Primary-source and configured Product Master consultation completed; independent artifact review follows. None |