PAS · New site, backup and online/offline editing
Change a CT primary online and compare the offline file
The meter and the Site Config database are separate stores. Send programs the meter. Save As stores a setup locally. The exercise deliberately leaves the local file unchanged after an accepted meter change, compares both views, then brings the working file up to date.
Written draft; edited recording and full CT comparison pending.
Before you start
- A checked configuration backup and separate working duplicate.
- An authorised training meter, agreed CT value, known input variant and valid programming access.
Keep track of the two values
This table describes the intended exercise, not the outcome of the incomplete practice run. The CT write was rejected during that run, so it has not yet demonstrated the differing online and offline values.
| Stage | Meter | Working Site Config file |
|---|---|---|
| After upload and Duplicate | Original CT primary | Original CT primary |
| After an accepted Send; local Save declined | New CT primary | Original CT primary |
| After reading back and saving locally | New CT primary | New CT primary |
Make one controlled online change
A save-changes prompt is not proof that Send succeeded. PAS also displayed “Setup has changed. Do you want to save the changes?” after the rejected write in the practice run. Check the write result and fresh meter readback separately.
Read the baseline
Select the working copy and enable Monitor > On line. Open MeterSetup > General Setup > Basic Setup. Use Receive and confirm retrieval to refresh the displayed setup from the meter. Record the original CT primary.
Enter the training value
Use only the agreed training value for the actual input variant. Change CT Primary Current, A and inspect the entire field before sending. Leave the secondary, wiring mode, PT ratio and other settings unchanged.
Send and check the result
Select Send and read the device-programming confirmation. Use the authorised meter password if requested. Continue only after the meter accepts the write; an access-denied or communication error is not a successful change.
Decline the local save for this exercise
When closing the setup dialog, read the save-changes prompt and deliberately select No for the local file. Do not confuse this with declining the earlier device-programming confirmation. Declining a local save does not undo an already accepted meter change.
Compare online readback and the offline file
Check the meter
While online, reopen Basic Setup and use Receive to retrieve the current CT primary. It must show the value accepted by the meter. Close without saving locally yet.
Check the local file
Turn Monitor > On line off, then reopen Basic Setup for the same working site. Compare the stored CT primary with the online readback. Confirm the mode and site name before explaining either value.
Explain the difference
The offline file is a saved configuration, not a continuous mirror of the meter. If both views match unexpectedly, stop the demonstration and check whether a local save or Upload Setups updated the file. Do not manufacture a mismatch.
Save the accepted setup and check again
Retrieve the final meter value
Return online and Receive Basic Setup again. Confirm the intended CT primary before saving.
Save into the working site
Select Save As and confirm the working site database as the destination. Preserve the separate backup. Saving locally does not send another programming command to the meter.
Reopen offline
Return offline, reopen Basic Setup and confirm the working file now contains the same CT primary as the final meter readback. Record the final value and whether the training value was retained or restored.
Recording status
The current practice run read a CT primary of 5 A and prepared a 100 A example. The meter rejected the write at authorisation. The setup dialog was closed with No selected at the save prompt. No successful CT change or online/offline mismatch is claimed by this lesson.
The completed comparison and final local save will be recorded after authorised programming access is available. Do not use a rejected-write clip as evidence of a successful configuration change.
Limits and checks
- Do not apply the example CT value to an operating installation; use the installed CT and meter input ratings.
- The complete CT change, declined-save comparison and final save sequence still require a successful recorded demonstration.
Check your understanding
Send succeeds, but you decline the local Save. Has the meter change been undone?
Show answer
No. Check the meter with a fresh online Receive. The offline site database can still hold the earlier value.
PAS reports Access denied after Send. May the next shot say the meter was changed?
Show answer
No. Resolve authorisation and obtain an accepted write plus fresh readback before making that claim.
Is Open the right button for a read-only comparison with another setup file?
Show answer
No. PAS documents Open as copying setup from another database into the present database. Use the selected site and explicit online/offline views for this exercise.
Sources
- Source 1. PAS Getting Started — creating a site (opens in a new tab)
BG0337 Rev. A2, printed/PDF page 6, creating a site
New creates a local site database. Select the actual model and instrument options.
- Source 2. PAS Getting Started — Ethernet connection (opens in a new tab)
BG0337 Rev. A2, printed/PDF page 9, Ethernet communication
Connection settings identify how PAS reaches the meter; they do not retrieve its configuration.
- Source 3. PAS Getting Started — local files and meter setups (opens in a new tab)
BG0337 Rev. A2, printed/PDF page 10, sections 3.2–3.3
Save As stores settings in the site database; Send programs the displayed setup; Upload Setups retrieves configuration from the meter.
- Source 4. EM13x Installation and Operation Manual — Basic Setup (opens in a new tab)
Printed pages 95–96 / PDF pages 98–99, Basic Setup
Use the actual meter input variant and connected CT rating. The course example is for an unconnected training meter, not a commissioning value.
- Source 5. PAS demonstration — new site, backup and Duplicate
PAS V1.5.8.9, EM133-XM demonstration, 8 November 2026
The practice run created XM Backup, completed Upload Setups and created XM Work using Duplicate. The two database files matched at that point. The attempted CT write was rejected; the online/offline comparison is still awaiting a successful demonstration.
Revision and review details
| Revision | Change and reason | Review / supersedes |
|---|---|---|