PAS · New site, backup and online/offline editing

Change a CT primary online and compare the offline file

Written lesson · recording pending

The meter and the Site Config database are separate stores. Send programs the meter. Save As stores a setup locally. The exercise deliberately leaves the local file unchanged after an accepted meter change, compares both views, then brings the working file up to date.

Written draft; edited recording and full CT comparison pending.

Before you start

Keep track of the two values

This table describes the intended exercise, not the outcome of the incomplete practice run. The CT write was rejected during that run, so it has not yet demonstrated the differing online and offline values.

StageMeterWorking Site Config file
After upload and DuplicateOriginal CT primaryOriginal CT primary
After an accepted Send; local Save declinedNew CT primaryOriginal CT primary
After reading back and saving locallyNew CT primaryNew CT primary

Source 3 · Source 5

Make one controlled online change

A save-changes prompt is not proof that Send succeeded. PAS also displayed “Setup has changed. Do you want to save the changes?” after the rejected write in the practice run. Check the write result and fresh meter readback separately.

  1. Read the baseline

    Select the working copy and enable Monitor > On line. Open MeterSetup > General Setup > Basic Setup. Use Receive and confirm retrieval to refresh the displayed setup from the meter. Record the original CT primary.

    Source 3 · Source 4

  2. Enter the training value

    Use only the agreed training value for the actual input variant. Change CT Primary Current, A and inspect the entire field before sending. Leave the secondary, wiring mode, PT ratio and other settings unchanged.

    Source 4

  3. Send and check the result

    Select Send and read the device-programming confirmation. Use the authorised meter password if requested. Continue only after the meter accepts the write; an access-denied or communication error is not a successful change.

    Source 3 · Source 5

  4. Decline the local save for this exercise

    When closing the setup dialog, read the save-changes prompt and deliberately select No for the local file. Do not confuse this with declining the earlier device-programming confirmation. Declining a local save does not undo an already accepted meter change.

    Source 3 · Source 5

Source 3 · Source 4 · Source 5

Compare online readback and the offline file

  1. Check the meter

    While online, reopen Basic Setup and use Receive to retrieve the current CT primary. It must show the value accepted by the meter. Close without saving locally yet.

    Source 3

  2. Check the local file

    Turn Monitor > On line off, then reopen Basic Setup for the same working site. Compare the stored CT primary with the online readback. Confirm the mode and site name before explaining either value.

    Source 3

  3. Explain the difference

    The offline file is a saved configuration, not a continuous mirror of the meter. If both views match unexpectedly, stop the demonstration and check whether a local save or Upload Setups updated the file. Do not manufacture a mismatch.

    Source 3

Source 3

Save the accepted setup and check again

  1. Retrieve the final meter value

    Return online and Receive Basic Setup again. Confirm the intended CT primary before saving.

    Source 3

  2. Save into the working site

    Select Save As and confirm the working site database as the destination. Preserve the separate backup. Saving locally does not send another programming command to the meter.

    Source 3

  3. Reopen offline

    Return offline, reopen Basic Setup and confirm the working file now contains the same CT primary as the final meter readback. Record the final value and whether the training value was retained or restored.

    Source 3

Source 3

Recording status

The current practice run read a CT primary of 5 A and prepared a 100 A example. The meter rejected the write at authorisation. The setup dialog was closed with No selected at the save prompt. No successful CT change or online/offline mismatch is claimed by this lesson.

The completed comparison and final local save will be recorded after authorised programming access is available. Do not use a rejected-write clip as evidence of a successful configuration change.

Source 5

Limits and checks

Check your understanding

Send succeeds, but you decline the local Save. Has the meter change been undone?

Show answer

No. Check the meter with a fresh online Receive. The offline site database can still hold the earlier value.

Source 3

PAS reports Access denied after Send. May the next shot say the meter was changed?

Show answer

No. Resolve authorisation and obtain an accepted write plus fresh readback before making that claim.

Source 5

Is Open the right button for a read-only comparison with another setup file?

Show answer

No. PAS documents Open as copying setup from another database into the present database. Use the selected site and explicit online/offline views for this exercise.

Source 3

A save-changes prompt appears after Send. Does this prove the meter accepted the new value?

Show answer

No. The prompt can appear even after a rejected write. Check the programming result and retrieve the meter setup again before comparing values.

Source 5 · Source 3

Sources

Revision and review details
RevisionChange and reasonReview / supersedes
20261108-site-files-v1
8 November 2026
Added the new-site, setup-backup, Duplicate and online/offline workflow.

Teach the meter and its local Site Config file as separate stores.

Written draft; complete CT comparison recording pending.

Initial site-file course.