PAS · New site, backup and online/offline editing
Create a blank site and check the connected meter
Narrated tour
Download MP4 · SRT captions · Use the video controls for captions and fullscreen; Escape returns to this lesson.
About this recording
EM235 New local file, Internet connection at 192.168.1.203, two firmware read requests and online Properties.
Screen recording of this EM235 demonstration. Follow the steps below using your own meter details.
Chapters
Create a blank local site, check that the meter replies, then read its details in Properties. The walkthrough uses an EM235; choose the correct model and connection for your own meter.
EM235 walkthrough with written steps below.
Before you start
- PAS installed, with a writable folder for Site Config files.
- The intended meter’s model, network address and Modbus device address, and permission to read it.
Have the meter details ready
Use the model, network address and Modbus address assigned to your meter. In this demonstration the EM235 uses IP address 192.168.1.203, device address 1 and host port 502. These are this demonstration’s settings.
If you are checking the PC network first, open Command Prompt and run ipconfig. Then use ping with the meter’s IP address. A reply shows that the address is reachable; it does not identify the meter or prove that Modbus communication works.
Create the blank Site Config file
Open the site list
Select Tools > Configuration > Sites. Choose the folder for the new local database.
Create the file
Enter a short name, such as EM235 New, and select New. Select the new file and confirm OK. Keep existing site files intact.
Choose the meter
Select EM235 and Internet Site, then enter device address 1 for this demonstration. Use the model and address assigned to your own meter.
Set the connection
On Connection, enter 192.168.1.203, host port 502 and Modbus RTU/TCP for this demonstration. Confirm OK. Port 502 is the usual direct Modbus TCP port; use a different port only when your network setup requires it. These fields tell PAS where to connect; they do not upload the meter’s settings.
Test communication before reading measurements
Open Communication Test
Leave Monitor > On line switched off. In this PAS demonstration, Communication Test is available in that state. Select Monitor > Communication Test.
Prepare a read request
Select Edit Request. For this EM235, use device address 1, function 03 (read holding registers), raw Start Register 46100 and Word Count 2. Start Register is where PAS starts reading. Word Count 2 requests two register values. Confirm the request. Use the applicable meter’s register map when working with a different model.
Send and repeat
Select Send, then send the same request again. The demonstration returns 4005 and 9 on both reads. The final counters show OK 2, with N/R, NAK and Check Error all at zero. Check the counters and returned words on your own test.
Understand the result
Firmware is the software inside the meter. This test reads the firmware version and build fields. The same values should return on each read unless the firmware changes. Use Properties next to check the meter’s identity.
Read the meter details in Properties
Go online
Close Communication Test. Check that the new site is selected, then select Monitor > On line.
Open Properties
Right-click the selected site and choose Properties. Read the reported model, online status, serial number and firmware. Scroll through the available information.
Match the intended meter
Compare the serial number in Properties with the meter’s label or your installation record.
Next: upload a configuration backup
A new site is not yet a backup. Next, follow Upload the setups, then duplicate the backup to save the meter’s current settings and make a working copy.
Pro Tips after the menu workflow
If OK is outside the visible area, check the active dialog and focused control, then press Enter to activate its default action. Read any confirmation that follows.
Keep site names short. Expand the + beside a site to see its programming menus, and widen the Site Tree enough to read their full names.
Use the menu workflow first. Practise keyboard shortcuts after you know which dialog and setting you need. You can pause or rewind the video whenever you want.
Limits and checks
- For another meter model, use its own register map.
Check your understanding
Does a successful firmware read identify the physical meter?
Sources
- Source 1. PAS Getting Started — creating a site (opens in a new tab)
BG0337 Rev. A2, printed/PDF page 6, creating a site
New creates a local site database. Select the actual model and instrument options.
- Source 2. PAS Getting Started — Ethernet connection (opens in a new tab)
BG0337 Rev. A2, printed/PDF page 9, Ethernet communication
Connection settings identify how PAS reaches the meter; they do not retrieve its configuration.
- Source 3. PAS Getting Started — local files and meter setups (opens in a new tab)
BG0337 Rev. A2, printed/PDF page 10, sections 3.2–3.3
Save As stores settings in the site database; Send programs the displayed setup; Upload Setups retrieves configuration from the meter.
- Source 4. EM235 / PM335 Modbus Communications — Device Identification (opens in a new tab)
BG0613 Rev. A8 (September 2025), PDF page 145, table 3.7; addressing convention on PDF page 6
Raw register 46100 is the firmware version word; 46101 is the firmware build word. This request is specific to the documented EM235 register map.
- Source 5. PAS demonstration — EM235 New site and communication check
PAS recording, 8 November 2026, EM235 New
Shows local site creation, repeated firmware reads and online Properties.
Revision and review details
| Revision | Change and reason | Review / supersedes |
|---|---|---|
| 20261108-site-files-v1 8 November 2026 | Added the new-site, setup-backup, Duplicate and online/offline workflow. Teach the meter and its local Site Config file as separate stores. | Written draft; complete CT comparison recording pending. Initial site-file course. |
| 20261108-em235-new-site-v1 8 November 2026 | Added the EM235 blank-site, read-only communication and Properties workflow. Show the complete first connection before the backup lesson. | Companion instructions for the reviewed EM235 walkthrough. General create-and-identify instructions; other lessons unchanged. |