PAS · New site, backup and online/offline editing

Check Site Config files: dates, size and copies

Written lesson · recording pending

Use file dates and sizes to find the likely backup and flag differences quickly. They are useful clues, but equal sizes or dates do not prove equal settings or a match with the live meter.

Short written lesson. File example checked locally; screen recording pending.

Before you start

Quick check in File Explorer

  1. Show the useful columns

    Open the folder containing the Site Config .mdb files. Select View > Details. Compare Name, Date modified, Type and Size; click Date modified to sort. Keep each meter’s files in its own clearly named folder.

    Source 2 · Source 4

  2. Check the exact file size

    Right-click each file > Properties > General. Compare Size in bytes, not Size on disk or only the rounded Size column. Confirm the full folder location so you do not compare the wrong copy.

    Source 4

  3. Record the result

    Keep the original backup. Note the meter identity, upload date, filename and purpose in your maintenance record. Name later snapshots clearly, for example XM Before.mdb and XM After.mdb; do not rename every file simply to make the dates look consistent.

    Source 1 · Source 4

Source 1 · Source 2 · Source 4

What the comparison tells you

Compare equivalent models and input variants. Two meter files may legitimately differ in identity or connection details even where the intended metering settings are the same.

File checkMeaning
Same sizeSame byte count only. Settings can differ without changing the file size.
Newer Date modifiedA later file write, not proof of a successful upload or newer meter settings.
Different Created datesThe files were created at different times; their contents can still match.
Matching SHA-256 hashesStrong confirmation of identical file content. It does not establish current meter settings.
Different hashesFile content differs. This does not identify which setting changed or prove the meter configurations differ.

Source 2 · Source 3 · Source 1

Example: the Duplicate we made

XM Backup.mdb and XM Work.mdb were each 188,416 bytes. Both showed Date modified of 8 November 2026 at 09:29:37 on the demonstration PC. The working copy was created later, at 09:31:45. A byte-for-byte check confirmed identical content. The matching size alone would not have established that result.

Source 4

When you need to compare meter settings

Select each file separately as the current PAS site through Tools > Configuration > Sites, with Monitor > On line switched off, and inspect the same setup tabs. Compare the required values, such as CT primary, VT settings and logging configuration. Do not use a setup dialog’s Open button as a read-only viewer: it copies settings into the current site.

For a live comparison, identify the intended meter online and use Receive in the relevant setup dialog, then compare its values with the saved offline values. Checking selected fields is not a complete configuration audit. Send and Download Setups write to the meter; neither is needed to inspect or compare. Upload Setups overwrites the selected local file, so preserve the baseline first.

Source 1 · Source 5

eXpertTip: check an exact copy

Optional: with PowerShell open in the folder containing the closed files, run:

Get-FileHash -LiteralPath '.\XM Backup.mdb', '.\XM Work.mdb' -Algorithm SHA256 | Format-List

Compare the complete Hash values for the two paths. Substitute your filenames. This reads the files without changing them. Matching hashes establish an identical copy, not that both files contain the latest configuration from their meters.

Source 3

Check your understanding

Two site files have the same size. Can you conclude their CT settings match?

Show answer

No. Inspect the corresponding saved setup values; read the identified meter when a current online comparison is needed.

Source 1 · Source 3

Sources

Revision and review details
RevisionChange and reasonReview / supersedes
20261108-file-check-v1
8 November 2026
Added a short file-management lesson after Upload and Duplicate.

Use dates and file sizes as screening clues, then distinguish identical copies from matching meter settings.

Source and navigation review for this development revision.

New lesson