PAS · ONLINE METER SHOWCASE

Explore the EM133-XM setup options in PAS

Take a guided tour of the connected meter through the Site Tree. See where measurement setup, inputs and outputs, energy, logging and communications fit together.

Explore the setup options online

Jump to a setup area

About this online recording

This showcase reads the connected demonstration meter and opens its setup views. It does not change settings or test every physical input, output or protocol. Available options depend on the meter model, firmware and fitted modules. A visible menu or empty channel row does not establish that the corresponding hardware is installed.

Australian Michael narration from ElevenLabs. The PAS Site Tree and recorded clock remain visible. Use fullscreen to read smaller fields.

General Setup

Begin with the wiring arrangement and transformer ratios. They establish the measurement values used by alarms, outputs and other functions.

Basic Setup

Match the meter to the wiring arrangement, CT primary rating and PT/VT ratio. Set the demand calculation periods here.

Use the ratings and wiring of the actual installation. A demand period and a data-recording interval are different settings.

Device Options

Review calculation and presentation choices, such as phase-energy calculation and measurement resolution where available.

More displayed digits do not increase measurement accuracy. Energy Test Mode is a separate function and remains unchanged in this tour.

Digital Inputs

Choose how contacts or incoming pulses are interpreted, including polarity and contact-bounce filtering.

Inputs may provide conditions for setpoints or sources for counters and billing registers. Check the fitted input hardware and the applicable debounce behaviour before programming.

Relay Outputs

Choose how a fitted relay behaves, for example as an alarm output or an energy-pulse output.

Operating mode, polarity, pulse width and pulse weight have different purposes. The showcase does not operate a relay.

Analog Inputs

Give a compatible analogue input an engineering quantity and its zero and full-scale values.

The input signal range and engineering units must match the fitted module and sensor. Visible rows are not a count of installed inputs.

Analog Outputs

Select a measurement and scale it for transmission to another system through a compatible analogue output.

Confirm the output type and fitted module before selecting zero and full engineering scales. Blank rows do not demonstrate an operating output.

Pulse/Event Counters

Count incoming pulses or selected events and apply the appropriate multiplier.

The counter is separate from the Event Log. Water or gas measurement requires the correct pulse weight and units from the source device.

Control/Alarm Setpoints

Connect a measured condition or time condition to an action. Review operating and release thresholds, delays and the selected action.

For recording, the setpoint supplies the trigger; the Data Recorder supplies the values. Thresholds use the applicable primary engineering units.

Local Settings

Review date presentation, daylight-saving rules and available clock-synchronisation inputs.

Time settings affect records and tariff schedules. Opening this view does not synchronise the meter clock.

Transformer Correction

Apply transformer ratio and phase-angle correction data when an installation requires it.

These corrections differ from the nominal CT/PT ratios in Basic Setup. Use established correction data; this is not a remedy for incorrect wiring.

Display Setup

Choose the front-display behaviour, including scrolling, return behaviour, backlight and the available measurement pages.

Check the actual front display when confirming a later change. This showcase shows the configuration options only.

Energy/TOU Setup

Energy sources feed the billing registers. Daily profiles set tariff change times, and the calendar selects the daily schedule to use.

Billing/TOU Registers

Select energy or external pulse sources and decide which total, tariff and demand values belong in the daily profile.

Internal energy sources and external pulses have different scaling requirements. Confirm the register and profile options for the installed meter.

TOU Daily Profiles

Set when the active tariff changes within a day.

A tariff change point is not a data-recording interval. The schedule should match the intended tariff arrangement.

TOU Calendar

Choose which daily tariff schedule applies to weekdays, weekends, seasons and exceptions.

The order of calendar entries matters. The example already in this meter is not a tariff recommendation for another site.

Memory/Log

A useful recording needs space, a choice of values and a trigger. These settings work together; the memory table alone does not tell you how often a record is created.

Log Memory

Inspect how memory is allocated to the Event Log and data files. Compare allocated bytes, record size, available capacity and records already stored.

Wrap-around recording reuses the oldest records first, often called FIFO. Capacity is not the stored count. Upload the required log history before a later clearing or repartitioning operation; uploading setups alone does not back up that history.

Data Recorder

Choose the values saved in a data file and give the file a useful name. Connect this view back to memory allocation and its recording trigger.

Daily Data Log 16 is a billing profile, so its setup differs from an ordinary interval file. Establish the billing-register/profile choices before allocating that profile's memory.

Communication Setup

These views configure communication at the meter. They are separate from the PC's PAS site connection settings.

Network Setup

Review the meter's network address, subnet mask, gateway and applicable TCP services.

Changing network settings can interrupt the connection. Keep the working assigned address during a read-only tour.

Serial Ports

Select the meter port and review its device address, baud rate, data format and applicable protocol.

Meter port names and Windows COM-port names refer to different ends of the connection. The displayed protocol choices still require matching firmware and hardware.

WiFi Station Setup

Configure a compatible Wi-Fi module to join an existing wireless network.

Network credentials and identifying wireless names are private. The meter's assigned address is separate from the router's address.

WiFi Access Point Setup

Configure a compatible Wi-Fi module's own access-point/router network.

This has a different purpose from joining an existing network. Use the appropriate module mode and current security requirements for the installation.

GPRS Setup

Review the mobile-network connection settings for a compatible cellular option.

GPRS is the historical PAS label. It does not establish an active cellular module or available network service. Provider credentials remain private.

ExpertPower Client

Configure the meter's client connection to the eXpertPower service, including its destination and session behaviour.

An available setup view does not establish an active service account. Use the service's assigned settings and preserve server-managed timing.

TCP Notification Client

Configure event- or time-triggered notifications to a receiving Modbus/TCP server.

This needs a receiving server and the relevant setpoint action. It is not a native email or SMS function.

Protocol Setup

Protocol views determine how another system reads the meter's data. Check the installed firmware and the corresponding communication guide before relying on an optional protocol.

Modbus Registers

Arrange selected data in a convenient register map and review the relevant data representation options.

This is different from setting the device address. The receiving system must still use the correct data types, scaling and word order.

DNP Options

Review DNP data representations and protocol behaviour for an applicable installation.

Opening this view is not a demonstration that DNP is supported or working on the connected unit. Confirm the exact firmware applicability first.

DNP Class 0 Points

Select the point ranges returned by a DNP Class 0 response on an applicable installation.

Object, variation, starting point and quantity define each range. These are DNP point choices, not Modbus addresses.

Administration Setup

Access control is a separate consideration from the meter's hardware capabilities.

Passwords

Control authorised access to meter settings.

The showcase identifies the Site Tree entry only. Password values and security edits are excluded.

From showcase to setup tutorials

This film shows what each setup area is for. Separate tutorials will work through the fields, valid ranges and a checked configuration example for each main branch. Those detailed tutorials are being developed.

Manuals for this showcase

Download the full EM133-XM showcase · Download captions

Transcript

Let's explore what you can configure in an EM133-XM using PAS. We're connected to the demonstration meter, and we'll use the Site Tree throughout. We'll explain each page without changing settings. Available functions depend on the meter's firmware and fitted options.

Expand General Setup and select Basic. Wiring mode and transformer ratings tell the meter how to interpret the electrical installation. Demand settings control the period over which demand is calculated. These settings come before alarms or analogue outputs. Keep the demand period separate from the interval used to record a data log.

Device Options covers choices such as calculating energy for each phase, the method used to calculate power, and measurement resolution. Resolution affects the detail displayed or reported; more decimal places do not make the meter more accurate. Energy test mode is a service function, which we leave unchanged.

The Digital Inputs page defines how the meter recognises contact changes and incoming pulses. Polarity and pulse mode control what is counted. Debounce time helps prevent a bouncing contact being counted repeatedly. These inputs can monitor a contact or receive pulses from another meter. The available channels depend on the fitted hardware; debounce is shared across inputs.

Relay Outputs defines how a fitted relay responds. It can follow an alarm, remain latched until released, or produce energy pulses. Pulse width is how long the pulse lasts. Pulse weight is how much energy it represents. We can review these choices without operating the relay.

Analog Inputs is used with a compatible input module. Its scaling converts an incoming signal into the quantity you want to measure. The low and high signal levels need matching engineering values. Use the sensor and module specifications for those values. An available setup page does not, by itself, identify fitted hardware.

With the appropriate output module, Analog Outputs sends a meter measurement to another system as a current signal. Choose the measurement, then define what the bottom and top of the signal range represent. When online, PAS receives the output type from the meter, which helps you work with the correct module settings.

Pulse and Event Counters can count incoming pulses or selected events. The source tells the meter what advances the counter. The multiplier tells it how much to add each time. Match that multiplier to the source's pulse weight, and take care to preserve any totals already accumulated.

Control and Alarm Setpoints links a condition to an action. A condition might be a measurement threshold or a time interval. Operate and release settings control when it starts and clears. Here, Setpoint One uses a fifteen-minute interval to trigger Data Log One. Remember that link when we open the recorder and its memory allocation.

Local Settings covers date format, daylight-saving rules and clock-synchronisation inputs where supported. These choices matter when you compare events or use daily profiles and tariff schedules. Review them against the site's time requirements. Setting the clock itself is a separate task; opening this page does not synchronise it.

Transformer Correction is separate from entering transformer ratings in Basic Setup. It allows ratio and phase-angle corrections for the voltage and current channels. Use established correction data for the actual transformers. This is specialist work: check the wiring and measurement arrangement before considering corrections to an unexpected reading.

Display Setup controls the meter's front display. Review how quickly it scrolls, when it returns to the main view, and how long the backlight stays on. Other choices control which measurement pages appear. These settings help present the information needed by the person reading the meter.

Next, expand Energy and Time of Use. Billing Registers links energy or external pulse sources to the required totals. Profile options choose which energy, tariff and maximum-demand values go into the daily record. Water or gas pulses need the correct pulse weight and units. The available registers depend on the meter version.

Daily Profiles defines when each tariff applies during the day. Select a season and day type, then review the change times and tariff numbers. This schedule allocates energy between tariffs. It is separate from the interval used to record a conventional data log.

The Calendar chooses which daily profile applies across the year. Weekdays, weekends, seasonal periods and exceptions can use different schedules. The registers define what is counted, the daily profiles define tariff change times, and the calendar chooses the day schedule. Check that the complete arrangement matches the site.

Now open Log Memory. In this example, Data Log One is allocated four thousand three hundred and twenty records. That is its capacity, not the number already stored. Record size and parameter count affect the space needed. Wrap-around recording replaces the oldest records, often called first in, first out. Upload and check required history before repartitioning or clearing memory.

Data Recorder shows what goes into each record. For Data Log One, connect these selected values with the fifteen-minute setpoint and the allocated record capacity. Those choices determine what is stored, when, and how much fits. Data Log Sixteen is different: it stores a daily billing profile. Configure its billing and tariff selections before allocating that file.

Under Communication Setup, Network contains the meter's address, subnet mask and gateway. These are separate from the connection settings in the PAS site file on your PC. Direct Modbus TCP communication normally uses port five hundred and two. Changing network settings can interrupt the connection, so we are reviewing the existing values.

Serial Ports contains the address, baud rate, data format and protocol for the selected meter port. The meter's port names are different from the COM-port number assigned by Windows. For a working serial connection, both ends need compatible settings and the correct physical interface.

WiFi Station lets a compatible WiFi module join an existing wireless network. Its network name and security settings must match that network, and the meter needs suitable addressing. With the connection established, PAS can access configuration and recorded data over the wireless link.

WiFi Access Point gives a compatible module a different role: providing its own wireless network. Station mode joins an existing network; access-point mode creates one. Review the mode and network settings for the intended arrangement. Having both pages in PAS does not mean both modes are operating together.

The page labelled GPRS contains mobile-network settings for a compatible cellular option, including the provider's access point name. The modem and available network service determine what can be used today. This is a configuration view; its presence does not show that a cellular connection is active.

The eXpertPower Client page configures the meter's connection to the eXpertPower service. It shows the server, communication port and client state. Use the settings supplied for that installation. To check whether communication is working, you would also check the connection status and the receiving service.

TCP Notification Client lets the meter notify a receiving Modbus TCP server when a configured event or time condition occurs. The destination and setpoint action need to work together. This is a server notification function, rather than a built-in email or text-message service.

Under Protocol Setup, Modbus Registers helps organise data for another system. User-assignable registers can group selected measurements into a convenient map. The receiving software also needs the correct data format and scaling. For detailed integration work, use the register guide that applies to the meter and firmware.

DNP is another communications protocol. The DNP Options page covers settings such as data representation and protocol timing for supported installations. Opening this view does not establish DNP support on this demonstration meter. Check the exact firmware and communication interface before including DNP in a project specification.

On a supported DNP installation, Class Zero Points chooses the information included in a Class Zero response. Each range has an object type, starting point and quantity. The firmware qualification still applies, and these are separate from Modbus register assignments.

Finally, Administration contains password controls for authorised access. We'll identify the entry in the Site Tree without opening it. Access permissions control what an operator can change. They are separate from which hardware and functions the meter supports. Password management belongs in a private, authorised session.

You have now seen the setup areas for this EM133-XM, from measurement, inputs and outputs through energy, logging and communications. Use the chapters to revisit an area. Detailed tutorials will show how to choose settings and check results for an installation.