Let's explore what you can configure in an EM133-XM using PAS.

00:00:04.920 --> 00:00:08.970
We're connected to the demonstration meter, and we'll use the Site Tree throughout.

00:00:08.980 --> 00:00:11.690
We'll explain each page without changing settings.

00:00:11.700 --> 00:00:15.910
Available functions depend on the meter's firmware and fitted options.

00:00:15.920 --> 00:00:18.210
Expand General Setup and select Basic.

00:00:18.220 --> 00:00:23.350
Wiring mode and transformer ratings tell the meter how to interpret the electrical installation.

00:00:23.360 --> 00:00:27.110
Demand settings control the period over which demand is calculated.

00:00:27.120 --> 00:00:29.690
These settings come before alarms or analogue outputs.

00:00:29.700 --> 00:00:34.630
Keep the demand period separate from the interval used to record a data log.

00:00:34.640 --> 00:00:39.290
Device Options covers choices such as calculating energy for each phase,

00:00:39.300 --> 00:00:43.050
the method used to calculate power, and measurement resolution.

00:00:43.060 --> 00:00:47.290
Resolution affects the detail displayed or reported; more decimal places

00:00:47.300 --> 00:00:49.770
do not make the meter more accurate.

00:00:49.780 --> 00:00:54.330
Energy test mode is a service function, which we leave unchanged.

00:00:54.340 --> 00:00:58.550
The Digital Inputs page defines how the meter recognises contact changes

00:00:58.560 --> 00:01:00.430
and incoming pulses.

00:01:00.440 --> 00:01:03.590
Polarity and pulse mode control what is counted.

00:01:03.600 --> 00:01:08.210
Debounce time helps prevent a bouncing contact being counted repeatedly.

00:01:08.220 --> 00:01:12.450
These inputs can monitor a contact or receive pulses from another meter.

00:01:12.460 --> 00:01:17.530
The available channels depend on the fitted hardware; debounce is shared across inputs.

00:01:17.540 --> 00:01:21.110
Relay Outputs defines how a fitted relay responds.

00:01:21.120 --> 00:01:26.130
It can follow an alarm, remain latched until released, or produce energy pulses.

00:01:26.140 --> 00:01:29.050
Pulse width is how long the pulse lasts.

00:01:29.060 --> 00:01:31.830
Pulse weight is how much energy it represents.

00:01:31.840 --> 00:01:34.930
We can review these choices without operating the relay.

00:01:34.940 --> 00:01:38.370
Analog Inputs is used with a compatible input module.

00:01:38.380 --> 00:01:42.450
Its scaling converts an incoming signal into the quantity you want to measure.

00:01:42.460 --> 00:01:46.130
The low and high signal levels need matching engineering values.

00:01:46.140 --> 00:01:49.670
Use the sensor and module specifications for those values.

00:01:49.680 --> 00:01:53.830
An available setup page does not, by itself, identify fitted hardware.

00:01:53.840 --> 00:01:57.430
With the appropriate output module, Analog Outputs sends a meter measurement

00:01:57.440 --> 00:02:00.050
to another system as a current signal.

00:02:00.060 --> 00:02:04.850
Choose the measurement, then define what the bottom and top of the signal range represent.

00:02:04.860 --> 00:02:08.750
When online, PAS receives the output type from the meter, which helps you

00:02:08.760 --> 00:02:11.010
work with the correct module settings.

00:02:11.020 --> 00:02:15.510
Pulse and Event Counters can count incoming pulses or selected events.

00:02:15.520 --> 00:02:17.650
The source tells the meter what advances the counter.

00:02:17.660 --> 00:02:21.750
The multiplier tells it how much to add each time.

00:02:21.760 --> 00:02:25.530
Match that multiplier to the source's pulse weight, and take care to preserve

00:02:25.540 --> 00:02:27.950
any totals already accumulated.

00:02:27.960 --> 00:02:31.430
Control and Alarm Setpoints links a condition to an action.

00:02:31.440 --> 00:02:34.790
A condition might be a measurement threshold or a time interval.

00:02:34.800 --> 00:02:38.730
Operate and release settings control when it starts and clears.

00:02:38.740 --> 00:02:43.330
Here, Setpoint One uses a fifteen-minute interval to trigger Data Log One.

00:02:43.340 --> 00:02:46.390
Remember that link when we open the recorder and its memory allocation.

00:02:46.400 --> 00:02:52.240
Local Settings covers date format, daylight-saving rules and clock-synchronisation

00:02:52.250 --> 00:02:54.650
inputs where supported.

00:02:54.660 --> 00:03:00.350
These choices matter when you compare events or use daily profiles and tariff schedules.

00:03:00.360 --> 00:03:03.730
Review them against the site's time requirements.

00:03:03.740 --> 00:03:09.810
Setting the clock itself is a separate task; opening this page does not synchronise it.

00:03:09.820 --> 00:03:14.890
Transformer Correction is separate from entering transformer ratings in Basic Setup.

00:03:14.900 --> 00:03:19.930
It allows ratio and phase-angle corrections for the voltage and current channels.

00:03:19.940 --> 00:03:23.710
Use established correction data for the actual transformers.

00:03:23.720 --> 00:03:27.390
This is specialist work: check the wiring and measurement arrangement before

00:03:27.400 --> 00:03:30.550
considering corrections to an unexpected reading.

00:03:30.560 --> 00:03:33.670
Display Setup controls the meter's front display.

00:03:33.680 --> 00:03:37.550
Review how quickly it scrolls, when it returns to the main view, and how

00:03:37.560 --> 00:03:39.490
long the backlight stays on.

00:03:39.500 --> 00:03:42.350
Other choices control which measurement pages appear.

00:03:42.360 --> 00:03:46.190
These settings help present the information needed by the person reading the meter.

00:03:46.664 --> 00:03:49.814
Next, expand Energy and Time of Use.

00:03:49.824 --> 00:03:54.434
Billing Registers links energy or external pulse sources to the required totals.

00:03:54.444 --> 00:03:58.874
Profile options choose which energy, tariff and maximum-demand values go

00:03:58.884 --> 00:04:00.455
into the daily record.

00:04:00.465 --> 00:04:04.014
Water or gas pulses need the correct pulse weight and units.

00:04:04.024 --> 00:04:06.594
The available registers depend on the meter version.

00:04:06.604 --> 00:04:10.474
Daily Profiles defines when each tariff applies during the day.

00:04:10.484 --> 00:04:14.854
Select a season and day type, then review the change times and tariff numbers.

00:04:14.864 --> 00:04:17.595
This schedule allocates energy between tariffs.

00:04:17.605 --> 00:04:21.394
It is separate from the interval used to record a conventional data log.

00:04:21.404 --> 00:04:25.114
The Calendar chooses which daily profile applies across the year.

00:04:25.124 --> 00:04:30.394
Weekdays, weekends, seasonal periods and exceptions can use different schedules.

00:04:30.404 --> 00:04:34.334
The registers define what is counted, the daily profiles define tariff change

00:04:34.344 --> 00:04:37.234
times, and the calendar chooses the day schedule.

00:04:37.244 --> 00:04:39.934
Check that the complete arrangement matches the site.

00:04:39.944 --> 00:04:41.674
Now open Log Memory.

00:04:41.684 --> 00:04:47.194
In this example, Data Log One is allocated four thousand three hundred and twenty records.

00:04:47.204 --> 00:04:50.454
That is its capacity, not the number already stored.

00:04:50.464 --> 00:04:53.855
Record size and parameter count affect the space needed.

00:04:53.864 --> 00:04:59.174
Wrap-around recording replaces the oldest records, often called first in, first out.

00:04:59.184 --> 00:05:03.874
Upload and check required history before repartitioning or clearing memory.

00:05:03.884 --> 00:05:06.674
Data Recorder shows what goes into each record.

00:05:06.684 --> 00:05:10.774
For Data Log One, connect these selected values with the fifteen-minute setpoint

00:05:10.784 --> 00:05:13.454
and the allocated record capacity.

00:05:13.464 --> 00:05:17.894
Those choices determine what is stored, when, and how much fits.

00:05:17.904 --> 00:05:22.215
Data Log Sixteen is different: it stores a daily billing profile.

00:05:22.225 --> 00:05:25.554
Configure its billing and tariff selections before allocating that file.

00:05:26.139 --> 00:05:31.609
Under Communication Setup, Network contains the meter's address, subnet mask and gateway.

00:05:31.619 --> 00:05:36.389
These are separate from the connection settings in the PAS site file on your PC.

00:05:36.399 --> 00:05:41.769
Direct Modbus TCP communication normally uses port five hundred and two.

00:05:41.779 --> 00:05:45.169
Changing network settings can interrupt the connection, so we are reviewing

00:05:45.179 --> 00:05:47.349
the existing values.

00:05:47.359 --> 00:05:51.929
Serial Ports contains the address, baud rate, data format and protocol for

00:05:51.939 --> 00:05:53.989
the selected meter port.

00:05:53.999 --> 00:05:58.249
The meter's port names are different from the COM-port number assigned by Windows.

00:05:58.259 --> 00:06:02.509
For a working serial connection, both ends need compatible settings and the

00:06:02.519 --> 00:06:04.349
correct physical interface.

00:06:04.359 --> 00:06:09.489
WiFi Station lets a compatible WiFi module join an existing wireless network.

00:06:09.499 --> 00:06:13.409
Its network name and security settings must match that network, and the meter

00:06:13.419 --> 00:06:15.369
needs suitable addressing.

00:06:15.379 --> 00:06:19.089
With the connection established, PAS can access configuration and recorded

00:06:19.099 --> 00:06:21.049
data over the wireless link.

00:06:21.059 --> 00:06:25.609
WiFi Access Point gives a compatible module a different role: providing its

00:06:25.619 --> 00:06:27.229
own wireless network.

00:06:27.239 --> 00:06:32.249
Station mode joins an existing network; access-point mode creates one.

00:06:32.259 --> 00:06:35.889
Review the mode and network settings for the intended arrangement.

00:06:35.899 --> 00:06:40.449
Having both pages in PAS does not mean both modes are operating together.

00:06:40.459 --> 00:06:45.009
The page labelled GPRS contains mobile-network settings for a compatible

00:06:45.019 --> 00:06:49.249
cellular option, including the provider's access point name.

00:06:49.259 --> 00:06:53.409
The modem and available network service determine what can be used today.

00:06:53.419 --> 00:06:57.409
This is a configuration view; its presence does not show that a cellular

00:06:57.419 --> 00:06:59.509
connection is active.

00:06:59.519 --> 00:07:04.309
The eXpertPower Client page configures the meter's connection to the eXpertPower service.

00:07:04.319 --> 00:07:07.629
It shows the server, communication port and client state.

00:07:07.639 --> 00:07:10.209
Use the settings supplied for that installation.

00:07:10.219 --> 00:07:13.389
To check whether communication is working, you would also check the connection

00:07:13.399 --> 00:07:15.929
status and the receiving service.

00:07:15.939 --> 00:07:21.329
TCP Notification Client lets the meter notify a receiving Modbus TCP server

00:07:21.339 --> 00:07:24.569
when a configured event or time condition occurs.

00:07:24.579 --> 00:07:27.949
The destination and setpoint action need to work together.

00:07:27.959 --> 00:07:33.489
This is a server notification function, rather than a built-in email or text-message service.

00:07:33.499 --> 00:07:38.469
Under Protocol Setup, Modbus Registers helps organise data for another system.

00:07:38.479 --> 00:07:43.149
User-assignable registers can group selected measurements into a convenient map.

00:07:43.159 --> 00:07:46.229
The receiving software also needs the correct data format and scaling.

00:07:46.239 --> 00:07:50.269
For detailed integration work, use the register guide that applies to the

00:07:50.279 --> 00:07:51.609
meter and firmware.

00:07:51.619 --> 00:07:54.429
DNP is another communications protocol.

00:07:54.439 --> 00:07:58.929
The DNP Options page covers settings such as data representation and protocol

00:07:58.939 --> 00:08:01.389
timing for supported installations.

00:08:01.399 --> 00:08:06.369
Opening this view does not establish DNP support on this demonstration meter.

00:08:06.379 --> 00:08:10.189
Check the exact firmware and communication interface before including DNP

00:08:10.199 --> 00:08:12.269
in a project specification.

00:08:12.279 --> 00:08:16.509
On a supported DNP installation, Class Zero Points chooses the information

00:08:16.519 --> 00:08:19.309
included in a Class Zero response.

00:08:19.319 --> 00:08:23.209
Each range has an object type, starting point and quantity.

00:08:23.219 --> 00:08:28.409
The firmware qualification still applies, and these are separate from Modbus register assignments.

00:08:28.419 --> 00:08:33.289
Finally, Administration contains password controls for authorised access.

00:08:33.299 --> 00:08:36.629
We'll identify the entry in the Site Tree without opening it.

00:08:36.639 --> 00:08:39.709
Access permissions control what an operator can change.

00:08:39.719 --> 00:08:43.289
They are separate from which hardware and functions the meter supports.

00:08:43.299 --> 00:08:46.809
Password management belongs in a private, authorised session.

00:08:46.819 --> 00:08:52.329
You have now seen the setup areas for this EM133-XM, from measurement, inputs

00:08:52.339 --> 00:08:56.289
and outputs through energy, logging and communications.

00:08:56.299 --> 00:08:58.829
Use the chapters to revisit an area.

00:08:58.839 --> 00:09:02.669
Detailed tutorials will show how to choose settings and check results for an installation.