PAS · Energy registers, water and gas

Water meters: pulse inputs, litres, kL and m³

Written lesson · recording pending

Follow the water meter’s pulse output through a fitted digital input into a correctly scaled volume register, then verify the result with a known increment.

Written course for development review; live pulse commissioning and recording pending.

Before you start

The external meter measures water; the SATEC meter counts its signal

The chain is: external water meter → compatible pulse output → fitted SATEC digital input → selected counter or billing source → volume total → historical record. Identify each link. A SATEC electrical CT ratio is not the water pulse factor.

Record the water meter identity, pulse constant, output type and pulse-width/rate limits. Match these to the exact SATEC input option and its electrical ratings. A dry contact, transistor/open-collector output and powered signal are not interchangeable wiring instructions. Use the applicable terminal diagrams; do not infer terminals or polarity from the PAS DI number.

Source 1 · Source 2 · Source 3 · Source 4

Use units per pulse, not its reciprocal

1 kL = 1 m³ = 1,000 L. The numeric totals in kL and m³ are therefore equal for the same volume. The unit label still matters because a litre total would be one thousand times larger.

Volume increment = detected pulses × volume per pulse. If the external specification gives pulses per unit, first take its reciprocal for a units-per-pulse field. Read the field definition rather than assuming every screen uses the same convention.

Illustrative output constantVolume per pulseReciprocal descriptionExpected increment
10 L/pulse0.010 kL/pulse = 0.010 m³/pulse100 pulses/kL100 pulses → 1.000 kL
1 L/pulse0.001 kL/pulse = 0.001 m³/pulse1,000 pulses/kL250 pulses → 0.250 kL
100 L/pulse0.100 kL/pulse = 0.100 m³/pulse10 pulses/kL25 pulses → 2.500 kL

Source 5 · Source 6

Choose a raw counter or a volume register deliberately

The EM13x general Pulse/Event Counter uses an integer multiplier, documented as 1–9999. A factor of 1 is useful for checking the number of detected pulses. It cannot express 0.010 kL per pulse directly in that integer field.

The EM13x Billing/TOU source setup instead documents a fractional multiplier of 0.001–100.000 for external pulse sources. This is the relevant path for the example’s 0.010 volume units per pulse. Check the range and precision offered by the exact model/firmware; do not force a smaller pulse quantum into a field that cannot represent it.

XM protocol F15 includes kL. The generic EM133 and the cited PRO/PM180 unit lists include m³ but do not establish a native kL selection. If kL is unavailable, a correctly scaled m³ total has the same numeric value; label any converted report clearly. Selecting a unit does not establish the pulse factor for you.

Source 1 · Source 5 · Source 6 · Source 3 · Source 4

Work through the PAS settings in order

Perform this setup only on an authorised test input. Preserve the baseline totals; a water demonstration does not require a reset.

  1. Inspect Digital Inputs

    Open MeterSetup > General Setup > Digital Inputs. Select the fitted input and compare mode, polarity and debounce with the external output specification. EM13x Pulse mode counts one selected edge; KYZ counts both edges. Its debounce setting is shared by all inputs, so assess other channels before changing it.

    Source 1 · Source 5 · Source 7

  2. Inspect a pulse counter

    For EM13x, open MeterSetup > General Setup > Pulse/Event Counters. PRO and PM180 manuals call this tab Counters. Read an existing suitable counter or allocate an authorised unused counter to the DI with multiplier 1 for a raw-count check. Do not overwrite a counter serving another purpose.

    Source 1 · Source 5 · Source 7

  3. Assign the volume source

    Open MeterSetup > Energy/TOU. Choose an available billing destination and the intended DI source. For the 10 L/pulse teaching example, use 0.010 kL per pulse on a supported XM setup, or 0.010 m³ per pulse where m³ is the available unit. Read back source, destination, factor and unit together.

    Source 1 · Source 5 · Source 7

  4. Keep the baseline and test

    Record start raw count and volume. Have the authorised test arrangement supply a known pulse increment compatible with the input, or compare against the external meter over a known volume. Record the end values; calculate differences without resetting either meter.

    Source 1 · Source 5 · Source 7

  5. Check and save

    For exactly 100 detected pulses at 10 L/pulse, the expected increment is 1.000 kL. Confirm the readback and record the result, then save the working offline configuration separately from the original backup.

    Source 1 · Source 5 · Source 7

Source 1 · Source 5 · Source 7

Compare increments before comparing lifetime totals

A water meter may already have a lifetime total before the SATEC input is connected. Record that commissioning offset rather than resetting a useful counter just to make the displays look alike. Compare increments over the same observation period first.

Worked check: the raw counter rises from 8,000 to 8,137. At 10 L/pulse, 137 × 0.010 = 1.370 kL. The external meter’s displayed increment may differ slightly at the observation boundary because a pulse represents a volume quantum and the display has its own resolution. Investigate pulse timing and resolution before changing a correct factor.

Source 1 · Source 5

Limits and checks

Check your understanding

For 100 pulses/kL, should the units-per-pulse multiplier be 100?

Show answer

No. It is 1 ÷ 100 = 0.010 kL/pulse. Putting 100 into that field reverses the relationship.

Source 5

Does a kL label prove that the volume is scaled correctly?

Show answer

No. Check source, pulse constant, multiplier and a known increment. A label alone does not validate the measurement.

Source 6 · Source 5

Sources

Revision and review details
RevisionChange and reasonReview / supersedes
20261108-energy-v1
8 November 2026
Added electricity-first energy and water/gas pulse-register lessons.

Explain model-specific capacity, correct units, PAS setup and consumption checks.

Primary-source and configured Product Master consultation completed; independent artifact review follows.

None