PAS · Energy registers, water and gas
Compare energy readings and calculate consumption
Use matched readings to calculate consumption and average power, while separating resets, scaling and overlapping totals.
Written course for development review; live pulse commissioning and recording pending.
Before you start
- Identify the exact model, firmware and fitted input modules. A PAS source list does not prove that every input exists on the meter.
- Read and save the current setups and required logs before changing sources, multipliers, tariffs or counters. Use an authorised training setup for programming exercises.
Capture a matched start and finish
Record meter identity, register/source name, unit, timestamp, timezone and scaling at both ends of the period. Use the same register definition and a consistent clock basis. A change to source assignment, multiplier, CT/PT configuration or reset history can break the comparison.
Consumption = finish cumulative reading − start cumulative reading, provided the register remained continuous. A negative difference is a reason to investigate: it is not automatically exported energy. Check the direction-specific register, reset/replacement history and documented rollover before calculating a correction.
Worked electricity example
The following readings are illustrative and refer to the same half-hour. No reset, rollover or scaling change occurred.
| Quantity | Start / calculation | Finish | Result |
|---|---|---|---|
| Import kWh | 12,450.20 | 12,456.70 | 6.50 kWh imported |
| Export kWh | 340.10 | 341.60 | 1.50 kWh exported |
| Calculated net exchange | 6.50 − 1.50 | — | 5.00 kWh net import |
| Calculated average imported power | 6.50 ÷ 0.5 h | — | 13.00 kW over the half-hour |
Keep the calculation’s meaning
Net exchange is a calculated balance of the two directional increments in this example. It does not replace the separate import and export records, and it does not establish a bill. Tariff rates, contractual rules and the selected meter’s own net-energy definition are separate matters.
Average power equals interval energy divided by elapsed hours. Use the actual elapsed interval, not an assumed one if records are missing or timestamps changed. Do not add the 5.00 kWh net result to the 6.50 kWh import result; those quantities overlap.
Use a practical comparison sequence
For a read-only check, select the intended energy quantities in PAS monitoring, note their units and capture the readings. Retrieve the matching historical records through Logs > Upload Logs, then open the saved archive and inspect its fields and timestamps.
Compare register increments with the corresponding interval records only after confirming whether those records contain cumulative totals, interval increments or a different quantity. Sum interval increments; take differences of cumulative totals. Summing cumulative readings greatly overstates consumption.
Check tariff increments against the summary increment only where the source, coverage period, calendar and reset history are aligned. Allow for displayed resolution and documented rounding. Investigate discrepancies rather than forcing totals to agree by clearing a register.
Pro Tip: preserve the evidence around a change
Keep the before and after readings, setup files, source description and change time together. File dates and sizes help locate versions; they do not prove identical live totals. Readback confirms the current setting, and an uploaded record confirms retained history. Neither can reconstruct pulses or energy that were never recorded.
Limits and checks
- Worked values are teaching examples, not readings or settings from the demonstration meter. No live programming or pulse test is represented by this written lesson.
Check your understanding
A cumulative kWh reading fell. Should you call the negative difference export?
Sources
- Source 1. EM133 / EM133-XM Modbus Reference — energy and Billing/TOU (opens in a new tab)
BG0640 Rev. A1, PDF/printed pages 32–38, 65–66 and 77–80. Page 66 contains an inconsistent target-range label; it is not a programming instruction.
- Source 2. PRO EM235/PM335 Modbus Reference (opens in a new tab)
BG0613 Rev. A8, September 2025. PDF/printed pages 60, 72–73 and 85–87: counters, total/summary energy and TOU.
- Source 3. PM180 Modbus Reference (opens in a new tab)
BG0527 Rev. A11, September 2024. PDF/printed pages 55, 63–64 and 74–75: counters, total/summary energy and TOU.
- Source 4. EM13x Installation and Operation Manual — logging and resets (opens in a new tab)
Printed pages 119–124 and 130–131 / PDF pages 122–127 and 133–134. Check the installed model before changing or clearing records.
- Source 5. PAS Getting Started — save setups and retrieve logs (opens in a new tab)
BG0337 Rev. A2, pages 10, 21–22 and 25. Upload Setups and Upload Logs are separate operations.
- Source 6. EM13x Installation and Operation Manual — Billing/TOU (opens in a new tab)
Printed pages 114–118 / PDF pages 117–121. Base-family procedure; XM capacity and units require the XM reference.
Revision and review details
| Revision | Change and reason | Review / supersedes |
|---|---|---|
| 20261108-energy-v1 8 November 2026 | Added electricity-first energy and water/gas pulse-register lessons. Explain model-specific capacity, correct units, PAS setup and consumption checks. | Primary-source and configured Product Master consultation completed; independent artifact review follows. None |