PAS · EM133-XM memory and interval logging
Choose a logging interval and understand the NEM context
Choose the interval for the intended record, then check the quantity and timestamps. A PAS logging timer alone does not establish NEM compliance.
Source-reviewed draft; human review pending.
Before you start
- Identify whether the record is for site analysis, a tariff comparison or regulated metering. For regulated metering, obtain the applicable configuration from the responsible Metering Coordinator or Metering Data Provider.
- Use the accompanying EM133 memory and setpoint lessons for model-specific controls. This lesson explains the data requirements; it does not change the connected meter.
Settlement and logging are different decisions
The NEM began five-minute settlement on 1 October 2021.
Current procedures still describe fifteen- and thirty-minute interval data and its conditional profiling. Do not treat every existing installation as requiring the same change, or describe all longer-interval data as obsolete. Confirm the installation's requirements before selecting a logging period.
Check the interval boundaries
The specified boundaries use Eastern Standard Time. A repeating timer is not enough unless the resulting records align to the required clock boundaries.
Inspect actual records
After configuration, check consecutive timestamps and the recorded quantity. Include restart and clock-change behaviour in the verification; a timer setting alone does not demonstrate correct alignment.
| Interval | Required boundary pattern in EST |
|---|---|
| 5 minutes | On the hour, then each successive five-minute boundary |
| 15 minutes | On the hour, quarter-hour, half-hour and three-quarter-hour |
| 30 minutes | On the hour and half-hour |
Recognise period-ending records
NEM12 interval records describe periods ending at the stated boundary. A complete day has the counts below; the last period ends at midnight of the following day. This explains the data format and does not claim PAS produces an accepted NEM12 file.
| Interval | First period ends | Values per complete day |
|---|---|---|
| 5 minutes | 00:05 | 288 |
| 15 minutes | 00:15 | 96 |
| 30 minutes | 00:30 | 48 |
Check what each value means
Engineering interpretation: instantaneous kW is power at a moment. Cumulative kWh is an accumulating energy register. Interval kWh is energy accumulated during the specified period. Logging the first or second does not automatically produce the third.
Verify the EM133 recorder's quantity, units, scaling and treatment of energy against its manual. MDFF section 4.4 describes the value for the interval, including applicable multipliers.
Use the intended time reference
NEM time is AEST, UTC+10. It is distinct from a local daylight-saving clock.
Before using PAS to synchronise an intended NEM-time recorder, check the PC time zone, daylight-saving setting and the meter's time handling. Do not copy the local PC display into the meter simply because the times can be made equal. Record the reference and verify the resulting timestamps.
Do not present profiled data as measured data
Part B provides conditional methods for representing eligible longer-interval energy in five-minute periods. These methods do not recover measurements the original meter never recorded. Dividing every thirty-minute value by six is not a universal conversion rule.
Limits and checks
- This lesson makes no claim about the demonstration EM133-XM's NMI pattern approval, settlement eligibility, accuracy class or acceptance by a Metering Data Provider.
- The relevant installation, data collection and validation requirements extend beyond the selected logging interval.
Check your understanding
Does selecting a five-minute timer prove that the EM133-XM is suitable for NEM settlement?
Show answer
No. Check the installation and metering-data requirements separately with the responsible parties.
Can all longer-interval energy simply be divided into equal five-minute values?
Show answer
No. Applicable profiling methods are conditional; converted values must not be represented as finer-resolution measurements.
Is a local daylight-saving PC clock automatically the right reference for a NEM-time recorder?
Show answer
No. Establish the intended time reference before synchronising and then check the stored timestamps.
Sources
- Source 1. AEMO — Five Minute Settlements
Five Minute Settlements overview; HTML page
Settlement commencement. This does not establish the suitability of the demonstration meter.
- Source 2. AEMO Metrology Procedure Part A v8.23
Section 3.9, printed page 10 / PDF page 10; responsibility and components, printed/PDF pages 5–6
Final version effective 1 November 2026. Interval alignment and installation responsibilities; no product approval inferred.
- Source 3. AEMO Metrology Procedure Part B v8.23
Sections 12.4–12.5, printed/PDF pages 37–39
Final version effective 1 November 2026. Profiling rules are conditional and do not establish finer-resolution measurement at the original meter.
- Source 4. AEMO Meter Data File Format Specification NEM12 & NEM13 v3.0
Section 3.3.3, printed/PDF page 8; sections 4.3–4.4, printed/PDF pages 11–12
Final version effective 1 November 2026. Interval lengths, period-ending records and data meaning. No PAS export capability claimed.
- Source 5. AEMO Project EDGE Data Specification Part A
Section 4.2, printed page 24
Used only for the definition of NEM time as AEST, UTC+10; this project specification is not the authority for an EM133 metering installation.
Revision and review details
| Revision | Change and reason | Review / supersedes |
|---|---|---|
| 20261108-draft-v1 8 November 2026 | Added interval selection, energy meaning, period-ending timestamps and NEM context. Support PAS logging lessons without implying that a timer setting establishes settlement compliance. | Primary AEMO source review complete; human review pending. None |