PAS · CLOCK SYNCHRONISATION
Understand and check the meter RTC
See what the Real Time Clock does, how PAS sets it and how regular updates are maintained.
Jump to a topic
About this recording
Earlier EM133-XM online footage, newly narrated. Separate before/after views omit authentication. Extended views are labelled while explained. Scheduled operation is explained, not demonstrated in this recording.
Michael, Australian narration from ElevenLabs. Use captions, rewind or fullscreen whenever helpful.
What the RTC does
RTC means Real Time Clock: the meter’s date and time. It timestamps recorded data and events. Matching the time basis across meters helps you compare records in the right order.
Check, set and read back
Select the intended meter site and go online. Open Monitor > RTC. Compare Device time with PC time. Check the computer’s time, time zone and daylight-saving settings before using it as the reference.
Set writes the computer time to the meter. Use Read afterwards to check the result. Where the meter records clock changes, retrieve the Event Log and check the entry. The recorded example’s RTC set event was checked in the saved database; a PAS Event Log report is not shown.
Keep the clock synchronised
For scheduled PAS updates, use Logs > Upload Scheduler and enable RTC Synchronization for the intended site. The schedule must be enabled, PAS must remain running and online, and the meter must be reachable.
PAS and eXpertPower can update the meter’s model-specific clock registers through Modbus. A working communications link alone does not establish that regular clock updates are configured. Check the update service and verify the resulting time.
Choose a supported time source
Some meters support SNTP, PTP or IRIG-B. Check the exact model, firmware, fitted options and network requirements. The next video explains how these methods differ.
Transcript and manuals
RTC means Real Time Clock. It is the meter's own date and time, used to timestamp recorded data and events. A useful reading needs the right time as well as the right value, especially when you compare records from different meters.
In PAS, select the correct meter site and go online. Open Monitor, then RTC. Compare the device time with the computer time. Check the computer's date, time zone and time source before using it as the reference.
Set copies the computer time to the meter. This recording shows separate before and after views; the authentication step is omitted. After setting the clock, select Read again and compare the times. Retrieve the Event Log to check the recorded clock change where the meter supports that event. Here, that event was checked in the saved database; the report is not shown.
Setting the clock once does not keep it synchronised indefinitely. PAS can also update the clock on a schedule, using the Upload Scheduler's RTC Synchronization Enable option. PAS must remain running and online, with the schedule enabled and communication available.
For ongoing site operation, choose the time-management arrangement during commissioning. That may involve PAS, an eXpertPower service, or a supported external time source. Confirm how that installation updates the meter, rather than assuming a connection is enough. Our separate clock-synchronisation explainer introduces SNTP, PTP and IRIG-B, and explains why support depends on the meter and its fitted options.
Manual references
- PAS Getting Started — Manual RTC update: page 13. Scheduler: pages 22–23.
- PRO installation and operation manual — BG0612 A8: SNTP pages 100–101; clock sources and local time pages 126–128.
- PM180 PMU application note — Time synchronisation and applicable ports: page 8.
- ETC-II installation and operation manual — BG0594 A5: downstream device RTC updates, page 18.