RTC means Real Time Clock.

00:00:02.400 --> 00:00:07.380
It is the meter's own date and time, used to timestamp recorded data and events.

00:00:07.380 --> 00:00:11.620
A useful reading needs the right time as well as the right value, especially when you

00:00:11.620 --> 00:00:13.920
compare records from different meters.

00:00:13.920 --> 00:00:17.640
In PAS, select the correct meter site and go online.

00:00:17.640 --> 00:00:20.340
Open Monitor, then RTC.

00:00:20.340 --> 00:00:22.360
Compare the device time with the computer time.

00:00:22.360 --> 00:00:27.100
Check the computer's date, time zone and time source before using it as the reference.

00:00:27.100 --> 00:00:29.000
Set copies the computer time to the meter.

00:00:29.000 --> 00:00:35.020
This recording shows separate before and after views; the authentication step is omitted.

00:00:35.020 --> 00:00:38.800
After setting the clock, select Read again and compare the times.

00:00:38.800 --> 00:00:43.100
Retrieve the Event Log to check the recorded clock change where the meter supports that

00:00:43.100 --> 00:00:44.120
event.

00:00:44.120 --> 00:00:49.360
Here, that event was checked in the saved database; the report is not shown.

00:00:49.360 --> 00:00:53.680
Setting the clock once does not keep it synchronised indefinitely.

00:00:53.680 --> 00:00:58.320
PAS can also update the clock on a schedule, using the Upload Scheduler's RTC

00:00:58.320 --> 00:01:00.800
Synchronization Enable option.

00:01:00.800 --> 00:01:04.560
PAS must remain running and online, with the schedule enabled and communication

00:01:04.560 --> 00:01:06.300
available.

00:01:06.300 --> 00:01:11.000
For ongoing site operation, choose the time-management arrangement during commissioning.

00:01:11.000 --> 00:01:16.620
That may involve PAS, an eXpertPower service, or a supported external time source.

00:01:16.620 --> 00:01:20.860
Confirm how that installation updates the meter, rather than assuming a connection is

00:01:20.860 --> 00:01:21.040
enough.

00:01:21.040 --> 00:01:26.487
Our separate clock-synchronisation explainer introduces SNTP, P

00:01:26.487 --> 00:01:31.660
T P and IRIG-B, and explains why support depends on the meter and its fitted options.
