PAS · CLOCK SYNCHRONISATION
Clock synchronisation across SATEC meters
Compare software clock updates, SNTP, PTP, IRIG-B and gateway updates.
Jump to a topic
About this recording
Presentation explainer with conceptual signal paths and product images. These are not wiring diagrams or a claim that every pictured meter supports every method.
Michael, Australian narration from ElevenLabs. Use captions, rewind or fullscreen whenever helpful.
Software updates: PAS and eXpertPower
PAS can copy the PC clock manually or use its enabled scheduler. eXpertPower can also update clock registers over Modbus. Register layout and write sequence belong to the specific model’s protocol guide; this overview does not provide a universal address or XPW schedule.
SNTP: time from a network server
SNTP means Simple Network Time Protocol. A supported meter periodically asks a configured time server for time. For the documented EM235/PM335 PRO setup, configure the SNTP client, server addresses and polling interval, select the clock source and check reachability through the first Ethernet interface.
PTP: a designed timing network
Precision Time Protocol, or PTP, uses a grandmaster reference and a compatible timing network. IEEE 1588 support, profile, switches and meter options must match. Connecting ordinary Ethernet is not enough to establish a precision-timing system. The PRO manual describes PTPv2 requirements; confirm them for the installed model.
IRIG-B: a dedicated time-code signal
IRIG-B carries time from a master clock to a supported input. Hardware and signal format must match. The PM180 PMU application note is one model-specific example; its PTP option also requires the applicable port. Do not assume that every SATEC meter has either interface.
ETC-II: updating downstream clocks
The ETC-II Data Server can periodically update supported downstream device clocks from the gateway’s clock. Check the gateway time, its own source and the enabled downstream update separately. This lesson does not claim universal PTP or IRIG-B support for ETC-II.
Check the result, not just the setting
Time zone and daylight-saving settings change the local time interpretation; they do not correct an inaccurate reference. Compare the required time basis, read back the meter clock and inspect available status or event information.
Understand what happens if the reference disappears, how the meter falls back and how synchronisation resumes. Avoid competing clock writers. Choose the method for the application rather than treating timestamp display resolution as a clock-accuracy guarantee.
Transcript and manuals
A meter reading tells you what happened. Its timestamp tells you when. If two meters have different clock times, comparing their events can give a misleading sequence. Keeping clocks aligned helps you compare logged demand, events and, on suitable analysers, disturbances across a site.
RTC means Real Time Clock: the meter's own date and time. Synchronisation adjusts that clock against a reference. The reference, the communication path and the meter's supported functions all matter. Display resolution is not the same thing as clock accuracy.
Start with software updates. In PAS, Monitor, then RTC shows the computer and meter times. Set updates the meter from the computer. For repeated updates, Logs, then Upload Scheduler includes RTC Synchronization Enable. The schedule must be enabled, PAS must remain running and online, and the meter must be reachable. The computer also needs a suitable time reference.
PAS and eXpertPower can update the meter's clock by writing its time registers over Modbus. Think of this as software sending the meter a new date and time. The register layout and permitted write sequence depend on the model, so a detailed integration uses that meter's protocol guide. For ongoing updates, configure the service or schedule and check the result. Simply reading the meter, or enabling a communications client, does not prove that clock updates are taking place.
SNTP stands for Simple Network Time Protocol. A supported meter periodically requests time from a network time server. The Pro series manual describes primary and secondary servers, a polling interval and an enable setting. It also requires SNTP to be selected as the clock source. For the documented EM235 and PM335 setup, the service uses the first Ethernet interface. Its network settings must allow it to reach the chosen server.
PTP means Precision Time Protocol. It distributes a common time reference over a suitably designed network. The Pro series manual describes an IEEE 1588, version two grandmaster and compatible network switches. Matching the supported profile and network arrangement is part of the design. Connecting a meter to an ordinary Ethernet network does not establish precision synchronisation.
IRIG-B carries a time code from a compatible master clock over a dedicated signal connection. As a specific example, the PM180 PMU documentation describes IRIG-B synchronisation and a PTP option requiring the appropriate Ethernet port. Use the instructions for the exact module, signal format and terminals. These options are not a promise that every SATEC meter has the same clock inputs.
The ETC-II shows another approach: a gateway can make periodic clock updates to supported connected devices from its own clock. Its manual describes enabling this within the Data Server. The gateway itself must have the right time. A gateway's clock, its time-source inputs and the updates it sends downstream are three separate things to check.
Time zone and daylight-saving settings are another part of the job. They control how time is interpreted or displayed locally; they do not repair an inaccurate reference clock. Check the installation's required time basis before comparing records. Avoid having different systems repeatedly set the same meter to different time references.
Finish by checking operation. Read back the meter time, inspect the available synchronisation status and review relevant events. Check what happens if the time source or network becomes unavailable. Choose a method supported by the actual meter and the accuracy the application needs. That gives the timestamps meaning, from routine energy records to detailed event analysis.
Manual references
- PAS Getting Started — Manual RTC update: page 13. Scheduler: pages 22–23.
- PRO installation and operation manual — BG0612 A8: SNTP pages 100–101; clock sources and local time pages 126–128.
- PM180 PMU application note — Time synchronisation and applicable ports: page 8.
- ETC-II installation and operation manual — BG0594 A5: downstream device RTC updates, page 18.