BFM-II multi-circuit branch feeder monitor and revenue meter datasheet
Multi-circuit branch feeder monitor and revenue meter.
Transcribed from the SATEC Australia datasheet TBV1.0, 3 September 2026 (PDF, 9 pages, 1127 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The BFM II is a modular multi-circuit power meter that monitors up to 18 three-phase (54 single-phase) branch circuits from a single device, suiting applications from medium-voltage substation branch monitoring to commercial multi-tenant billing in shopping centres and office buildings. Suitable for both new and retrofit projects, it installs directly into new or existing switchboards.
Built around SATEC’s High Accuracy Current Sensors (HACS), the BFM II combines a Class 0.5S revenue meter with built-in RS-485 and Ethernet communications, modular digital and analogue I/O, and an optional 4G cellular modem. An optional Digital Fault Recorder (DFR) adds 36-channel waveform capture at 40×In for substation fault analysis.
Main features
Modular multi-circuit metering — up to 54 single-phase or 18 three-phase current channels from a single device
Dual input voltage — an optional second 3-phase voltage input module (VIM) for measuring a parallel power source
Modular digital & analogue I/O — up to 72 I/O points for pulse output, circuit-breaker status, analogue parameters and more
Optional Digital Fault Recorder (DFR) — 36-channel (12×3-phase) waveform capture at 40×In, triggered internally or externally
Multi-option current inputs — HACS (100–3,000A), RS5 5A split-core retrofit sensors, or FLEX 3VAC current-sensor interface
Communication — built-in RS-485 and Ethernet, with an optional 4G cellular modem
Open protocols — Modbus RTU/ASCII, DNP3.0, BACnet, IEC 60870-5-101/104
Revenue-grade, anti-tamper design to Class 0.5S accuracy
Feature capabilities
BFM II
Base multi-circuit meter — up to 18 three-phase or 54 single-phase current channels, Class 0.5S revenue metering and submetering
BFM II + DFR
Adds digital fault recording — 36-channel (12×3-phase) pre/post-fault waveform capture at 40×In for substation fault analysis
BFM II + VIM
Adds a second 3-phase voltage input module for measuring a parallel power source
Multi-Functional 3-Phase Smart Meter
True RMS volts, amps, power, power factor, neutral current and frequency, and many more
Ampere/Volt demand meter
50/60 Hz measurement
Billing / TOU Energy Meter
Class 0.5S AS/IEC 62053-22 four-quadrant active and reactive energy poly-phase static meter
Three-phase total and per-phase energy measurement — active, reactive and apparent energy counters
Time-of-Use: 8 energy/demand registers × 8 tariffs, 4 seasons × 4 day types, 8 tariff changes per day
Easily programmable tariff calendar schedule
Automatic 120-day daily profile log for energy and maximum demand (total and tariff registers), per submeter
Waveform and Digital Fault Recorder (optional — DFR version)
Independent product; limited to 12 three-phase current channels
Digital fault recording with pre/post-fault waveform capture on 36 current channels and 4 voltage channels, at 40×In
Triggered externally through digital inputs, or internally from the embedded fault detector
Automatic detection of fault category using sub-cycle measurements
Fault triggers include programmable thresholds and hysteresis, adjustable for specific substation conditions
Time-tagged fault events included in the fault event report
Harmonic Analyser
Individual voltage and current harmonic spectrum and angles, up to the 25th order harmonic
Voltage and current THD, TDD and K-Factor
Programmable Logical Controller
Embedded programmable controller
4 control setpoints — programmable thresholds and delays
Relay output control
1-cycle response time
Event and Data Recording
Non-volatile memory for timestamped event and data recording, per channel
Event recorder for internal diagnostic events and setup changes
Two data recorders — 2 separate programmable periodic data logs per channel
Real-Time Clock
Accuracy: maximum error of 5 seconds/month @ 25°C
Current Input Options
The BFM II features unique milliamp current inputs — each current-input module (CIM) is ordered for compatibility with one of three CT options below
HACS — 40mA input designed for SATEC HACS CTs (100–3,000A)
RS5 — 40mA input designated for 5A split-core HACS, reading 5A from a CT secondary; ideal for retrofit installation
FLEX — for interfacing 3VAC current-sensor output
Modules may be mixed and matched across up to 54 channels (max. 2 CIM modules per device)
I/O Options
9DI / 18DI — 9 or 18 digital inputs (dry contact / 24, 125 or 250VDC), 1-cycle update time; unlatched, latched, pulse and KYZ operation; energy pulses
9RO — 9 Form A relay outputs, 5A @ 250VAC or 30VDC, 1-cycle update time (max. 2 modules per device)
4AI — 4 analogue inputs; selection of ±1mA, 0–20mA, 4–20mA and 0–1mA ranges, 0.5% FS accuracy, 2-cycle update time
Up to 4 I/O modules per device
Modular Design and Expansion
Add-on modular design — up to 2 current-input modules, up to 4 digital/analogue I/O modules, 1 voltage-input module and 1 auxiliary power supply module per device
EXT-BFM II extension cable for connecting optional modules remotely
DIN-rail mounting
Communications
Built-in 2-wire RS-485 port, plus Ethernet 10/100Base-T
Optional 4G cellular modem, with automatic fallback to 2G/3G
Serial TTL RS-232 connection to the meter, up to 460.8 kbps
Meter Security
3-level password access, protecting meter setups and accumulated data from unauthorised changes
Upgradeable Firmware
Firmware upgrade via a serial or Ethernet port
Software Support
PAS — SATEC’s bundled configuration and data-acquisition tool, including waveforms, phasors and harmonics
eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics
Any third-party software supporting the open-protocol suite
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
Voltage inputs — main voltage module and VIM module
Installation
Category III
Nominal voltage
277/480V AC
Voltage range tolerance
±15%
Input impedance
0.35 MΩ
Measurement burden, powered by AUX supply — burden for 277V
≈ 0.08 VA
Measurement burden, powered by AUX supply — burden for 120V
≈ 0.02 VA
Measurement burden, powered by measurement inputs — burden for 277V
≈ 24 VA
Measurement burden, powered by measurement inputs — burden for 120V
≈ 16 VA
Galvanic isolation
4kV AC @ 1 min withstanding insulation
Connector type
Removable, 4 terminals
Wire size
Up to 10 AWG (up to 6 mm²)
Terminal pitch
10 mm
AC current inputs
Burden
<0.15 VA
Recommended wire size
18 AWG (1 mm²)
Isolation
600V
Terminal pitch
5 mm
The BFM II is compatible with SATEC High Accuracy Current Sensors (HACS) only. These CTs, supplied as solid-core or split-core, range from 5A to 3,000A primary input. Caution: Connecting the device’s built-in current inputs (5mA for RS5 and 40mA for other HACS) with standard 1A or 5A outputs will irreparably harm your device! For full HACS specs, see the HACS datasheet.
Power supply — self-energised (three or single-phase, from any phase)
Nominal voltage
120/208–277/480V AC (L-N/L-L)
Input range
70–561V AC, 50/60 Hz
Burden for 277V
<17 VA
Unit may be self-energised from voltage inputs, or by the AUX power supply module
AUX power supply module
Withstanding insulation
4kV AC @ 1 min
AC/DC power supply
L/+, N/− and GND
Rated input @ operating temperature −25°C to 60°C
50–290V AC 50/60Hz · 40–290V DC
Max. power output @ operating temperature −25°C to 60°C
10 W
Rated input @ operating temperature −40°C to 70°C
50–290V AC @ 50/60Hz · 90–290V DC
Max. power output @ operating temperature −40°C to 70°C
10 W
Recommended wire size
18 AWG (1 mm²), 600V isolation
Terminal pitch
7.5 mm, three pins
Built-in communication — serial communication (RS-485), optically isolated port
Isolation
4kV AC @ 1 min
Connector type
Removable, 3 terminals
Terminal pitch
5 mm
Wire size
Up to 12 AWG (up to 2.5 mm²)
Baud rate
Up to 115,200 bps
Supported protocols
Modbus RTU/ASCII, DNP3.0
Built-in communication — Ethernet port
Transformer-isolated
10/100Base-T port
Isolation
4kV AC @ 1 min
Connector type
RJ45 modular
Supported protocols
Modbus TCP (port 502), DNP3/TCP (port 20000)
Simultaneous connections
5 sockets; SNTP time synchronisation
Built-in communication — USB port, isolated USB 1.1
Withstanding insulation
4kV AC @ 1 min
Connector type
A male, standard USB cable, max. 2 m
Supported protocols
Modbus RTU
Optional modular communication — cellular modem
Type
4G, with fallback to 2G/3G per network
Withstanding isolation
4kV AC @ 1 min
Connector type
SMA
Supported protocols
Modbus TCP (port 502), DNP3.0/TCP (port 20000)
Optional modular communication — display COM / connector
Baud rate
Up to 460,800 bps
Supported protocols
Modbus RTU
Serial TTL RS-232 non-isolated port, for connecting to the Graphic Display Module
Optional modular I/O — 18 digital inputs — 9/18 DI (up to 4 modules)
Optional modular I/O — 9 relay output — SPST Form A
Contact rating
5A @ 250VAC · 5A @ 30VDC
Update time
1 cycle
Recommended wire size
18 AWG (1 mm²), 600V isolation
Terminal pitch
3.81 mm
Optional modular I/O — 4 analogue inputs
Ranges (upon order)
±1mA · 0–20mA · 4–20mA · 0–1mA (100% overload)
Accuracy
0.5% FS
Scan time
2 cycles
Withstanding insulation
4kV AC @ 1 min
Recommended wire size
18 AWG (1 mm²), 600V isolation
Terminal pitch
3.81 mm
Real-time clock
Accuracy
Maximum error of 5 sec/month @ 25°C
Graphical display module — GDM (option)
Resolution
320 × 240
Operating temperature
−20°C to +70°C
Communication
Serial TTL RS-232 non-isolated port
3.5-inch touch-panel LCD graphic TFT display
Environmental conditions
Operating temperature
−30°C to +70°C (−22°F to 158°F)
Storage temperature
−40°C to +85°C (−40°F to 185°F)
Humidity
0–95% RH, non-condensing
Altitude
≤ 2000 m
Construction — overall dimensions
Width
278 mm / 10.94″ (18 channels) · 554 mm / 21.81″ (54 channels)
Height
128 mm / 5.04″
Depth
72.5 mm / 2.85″
Weight
1.6 kg (36 channels)
Mounting
DIN-rail mount
Construction — materials
Enclosure
Reinforced polycarbonate
Panels
Polycarbonate
PCB
FR4 (UL94-V0)
Terminals
PBT (UL94-V0)
Plug-in connectors
Polyamide PA6.6 (UL94-V0)
Packaging case
Carton and Stratocell (polyethylene foam) brackets
Labels
Polyester film (UL94-V0)
Measurement accuracy — Voltage
Full scale @ input range
VL = 120V · VL = 230V
Accuracy — % reading
0.1
Accuracy — % FS
0.005
Conditions
100 to 300V
Range
0 to Imax = 10,000A (HACS primary current)
Measurement accuracy — Line current
Full scale @ input range
Instrument current transformer CTs IL = 100A
Accuracy — % reading
0.2
Accuracy — % FS
0.005
Conditions
1 to 100% FS
Range
0 to Imax = 10,000A (HACS primary current); starting current 0.1% FS
Measurement accuracy — Active power
Full scale @ input range
2×Vmax×IL/1000, kW
Accuracy — % reading
1
Accuracy — % FS
0.02
Conditions
|PF| ≥ 0.5
Range
−120.000 to 120.000 kW
Measurement accuracy — Reactive power
Full scale @ input range
2×Vmax×IL/1000, kvar
Accuracy — % reading
1
Accuracy — % FS
0.02
Conditions
|PF| ≤ 0.9
Range
−120.000 to 120.000 kvar
Measurement accuracy — Apparent power
Full scale @ input range
2×Vmax×IL/1000, kVA
Accuracy — % reading
1
Accuracy — % FS
0.02
Conditions
|PF| ≥ 0.5
Range
0 to 120.000 kVA
Measurement accuracy — Power factor
Full scale @ input range
1.0
Accuracy — % reading
—
Accuracy — % FS
1.0
Conditions
|PF| ≥ 0.5, I ≥ 2% FSI
Range
−0.999 to +1.000
Measurement accuracy — Frequency
Full scale @ input range
—
Accuracy — % reading
0.02
Accuracy — % FS
—
Conditions
50Hz: 39.00 to 65.00Hz · 60Hz: 45.00 to 70.00Hz
Range
39Hz up to 70Hz
Measurement accuracy — Active energy import
Accuracy
Class 0.5 under conditions as per AS/IEC 62053-22; Class 0.5 under conditions as per ANSI C12, IEC 61557-12
Range
0 to 99,999,999.9 kWh
Measurement accuracy — Reactive energy import/export
Accuracy
Class 0.5 under conditions as per IEC/AS 62053-24, |PF| ≤ 0.9
Range
0 to 99,999,999.9 kvarh
Measurement accuracy — Apparent energy
Accuracy
Class 0.5 under conditions as per IEC 61557-12
Range
0 to 99,999,999.9 kVAh
FS: full scale (voltage or current). 1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ±1 digit. This does not include inaccuracies introduced by the user’s potential and current transformers. Accuracy calculated at 1-second average. 2. Specifications assume voltage and current waveforms with THD ≤ 5% for kvar, kVA and PF; reference operating temperature 20°C–24°C. 3. Measurement error is typically less than the maximum error indicated here. 4. Accuracy of the device complies with the AS/IEC 62053-22 Class 0.5S standard using solid-core HACS, and Class 1 when using split-core HACS.
Standards compliance
Accuracy
Complies with AS/IEC 62053-22, Class 0.5S
Meets ANSI C12.20-2010, Class 100, 400, accuracy 0.5%
Electromagnetic immunity
EMC per IEC 62052-11, AS/IEC 62053-22, ANSI C12.1 and ANSI C12.20
IEC61000-4-2 — electrostatic discharge, 15kV air / 8kV contact
AS/IEC 62053-22 — AC voltage tests related to ground, 4kV AC @ 1 min, for power and signal ports above 40V, or per UL 61010-1/916 for basic and/or double insulation and Installation Category III
Safety
UL 916
Atmospheric environment
Accuracy operational ambient temperature range: −25°C to +60°C
Operational ambient temperature range: −40°C to +70°C
Long-term damp heat withstand per IEC 68-2-3, <95% non-condensing, +40°C
Transport and storage temperature range: −40°C to +85°C