PAS · SITE PREPARATION

How do I prepare a PAS site and keep the meter's setup safe?

PAS site selection showing saved backup and working sites
PAS site selection from the recorded backup and duplication lesson.

Quick answer

In PAS, each meter has its own site database, an .mdb file that stores that meter's settings. The site records the meter's model and installed options, and its communication settings must match the meter's. SATEC Australia's advice is to read the meter's setup into a separate backup site before you change anything, and keep that file unchanged.

What to have ready

  • The exact meter model and its installed options. The site asks for the voltage and current inputs, any analogue output (the manual's "analog output"), and the logging memory size where the meter has onboard memory. SATEC Australia's advice is to fill these in from the meter you actually have, using its label and order documents.
  • How PAS will reach the meter. PAS can connect through a serial port, a modem, the Internet or local Ethernet, a cellular modem or USB. For a cellular modem, the manual refers you to the meter's own manual.
  • The meter's communication settings. For serial, PAS needs the COM port, baud rate, data format and protocol. For the Internet, it needs the IP address and protocol. In both cases it needs the device address. The protocol and port settings in PAS must match the settings in the meter. SATEC Australia's advice is to read the meter's own settings where its manual describes them, rather than assuming defaults.
  • Permission to connect. SATEC Australia's advice is to have the site owner's or operator's permission before you connect, and any password the meter needs. PAS asks for the password when it sends its first command to a password-protected meter.

If the meter is reached through a SATEC ETC gateway, SATEC Australia's advice is to read How do I connect and configure a SATEC ETC gateway? first. That article covers connecting and configuring the gateway.

Creating the site

  1. With On-line unchecked, open Tools > Configuration and select Sites on the Instrument Setup tab.
  2. Choose the folder, type a site name, select New, then OK.
  3. Select the meter model and fill in the Instrument Options. Use the Comments box for the meter's location or other details.
  4. Under Communication, select the connection type and enter the device address. Then set the port, protocol and time-outs on the Connection tab.

PAS creates a Sites folder when it is installed, and the manual advises keeping site databases there. You can't change site properties or communications while On-line is checked.

SATEC Australia's PAS lesson Create a blank site and check the connected meter works through these steps with an EM235, with a recording.

Connection settings that matter

SettingWhat the manual says
Serial portSelect the COM port, then set the same baud rate and data format as the meter.
ProtocolSelect the same protocol as the meter.
Response Time-outHow long PAS waits for the meter's reply before reporting a failure; it may need adjusting for a cellular modem.
Break Time-outMatters only for Modbus RTU, DNP3 and IEC 60870-5. The default of 10 ms is usually enough. If you often see "Communication failed", it may need increasing, but too much slows communications.
RetriesHow many attempts PAS makes before reporting a failure.
Internet portPAS fills in the TCP port to suit the protocol. The manual lists 502 for Modbus RTU, 20000 for DNP3.0, 2404 for IEC 60870-5, and 5002 for Modbus ASCII or SATEC ASCII. The port must match the meter's own setting.
Sampling RateHow often PAS updates data on screen in the Data Monitor.

Keeping the meter's setup safe

SATEC Australia's advice is to make the first read from a new site a backup:

  1. With the site online, use Meter Setup > Upload Setups into a new, clearly named backup site. Upload Setups updates the selected site database with the setups currently in the meter. In SATEC Australia's practice run on an EM133-XM with PAS V1.5.8.9, PAS warned that the current contents of the site database would be overwritten. So don't upload into a file whose settings you still need.
  2. Keep that backup unchanged, and make a separate working copy for any editing.
  3. Record the meter's identity, the date and the file names in the site's maintenance record.

The PAS lessons Upload the setups, then duplicate the backup and Check Site Config files: dates, size and copies work through these steps with an EM133-XM and PAS V1.5.8.9. The lessons themselves say that "PAS file-management steps apply across models; available programming menus differ".

Recorded logs are retrieved separately, with Upload Logs. The manual advises against storing data files in the Sites folder, to avoid confusion with the site databases.

Getting help

Contact SATEC Australia technical support through our contact form. SATEC Australia's advice is to have these details ready:

  • the meter model and order code;
  • your PAS version;
  • the connection type and the settings you entered;
  • the exact message PAS showed.

Manuals and source pages

  • PAS Getting Started, BG0337 Rev. A2:
    • Section 1.1.2 File Format, printed page 5 (PDF 5).
    • Section 2.1 Creating a New Site, printed pages 6–7 (PDF 6–7).
    • Section 2.2 Setting up Communications, printed pages 7–9 (PDF 7–9).
    • Chapter 3 Setting Up the Device, printed page 10 (PDF 10).
    • Section 4.1 Authorization, printed page 11 (PDF 11).
    • Section 5.1.5 Saving Data to a File, printed page 19 (PDF 19).
    • Chapter 6 Retrieving Recording Files, printed page 21 (PDF 21).
    • Available from the SATEC Australia manuals and datasheets page. Evidence checked 22 November 2026.