EM235 PRO · FRONT-PANEL KEYPAD GUIDE
How do I set the CT ratio on an EM235 PRO?
Open Setup → General Setup → Basic Setup, edit CT PRIMARY, A, select APPLY and check the saved value.
Enter the CT's primary current in amps. In the worked example, a 200:5 A CT uses 200 A in CT PRIMARY; its calculated ratio is 40:1. Use the value from your own CT nameplate.
Watch the keypad demonstration
2 minutes 45 seconds · English captions · Synthetic narration. Demonstrated model: EM235 PRO; keypad firmware 40.5.9.47. Other model or firmware menus may differ.
Watch on YouTube (new tab) · Download English captions · Read the text transcript
Jump to a chapter
Check the meter input before choosing the value
Check the meter rating label and CT secondary. The standard input versions are 1 A nominal / 2 A continuous and 5 A nominal / 10 A continuous. The film demonstrates the 5/10 A version. The programmable CT primary range is 1–50,000 A.
HACS is a separate input option
For the SATEC 40 mA HACS version, use only SATEC-supplied High-Accuracy-Current-Sensors. This is a separate hardware input option; confirm the installed input version and consult SATEC if unsure. SATEC has confirmed a 40 mA AC secondary for HACS. The 20/40 mA documentation clarification is pending.
Change CT PRIMARY from the front panel
The button counts below follow the demonstrated firmware and example starting value. Follow the actual cursor and field on your meter.
Open Setup
Use Down to select Setup, then press the check key ✓. The default password is 9, if unchanged. Otherwise use the configured password; ask your administrator or SATEC if you do not have it.
In the demonstrated numeric keypad, press Up seven times from 1 to reach 9, then check. Press Down six times from 9 to APPLY, then check.
Find CT PRIMARY, A
Open General Setup → Basic Setup. Use Down to reach CT PRIMARY, A, then press check.
Enter the CT primary current
For this example, clear the displayed 50 and enter 200. Use Up twice from 1 to select delete; press check twice. Move Down three times to 2 and press check. Move Up seven times to 0; press check twice.
The entry should read 200 for the 200:5 A example. Either arrow can be used on the demonstrated numeric keypad; the video uses shorter routes.
Apply, then read back
Move Down five times from 0 to APPLY, then press check to save. Check that CT PRIMARY, A = 200 for this example.
What to check when you finish
- The CT nameplate, secondary current and meter nominal input match.
- CT PRIMARY contains the primary amps from your CT nameplate.
- APPLY was confirmed and the saved value reads back correctly.
This lesson covers the front-panel setting. It does not establish the correct CT selection or configuration for a particular installation.
Manuals and source references
- EM235/PM335 User Manual (new tab) — BG0612 Rev A8: navigation pages 70–72, Basic Setup page 104, CT-primary range page 105 and input ratings page 197.
- EM235 Quick Start Guide (new tab) — BG0634 Rev A1, page 3: password 9 and the Basic Setup path.
- PRO series datasheet — input options. For the HACS secondary, this guide follows SATEC’s technical clarification of 15 November 2026; the documentation revision is pending.
Source and film review: 15 November 2026. Match the model, input option and firmware before applying this demonstration.
Video transcript
Read the complete narration
Welcome to this demonstration on how to change the CT ratio, or primary current setting, on an EM235 PRO SATEC power quality meter. In this example, we've chosen a two hundred amp CT with a five amp secondary. Enter two hundred for the primary current. That's a forty-to-one ratio.
Next, check the rating label on the side of your meter. Here, five with ten in brackets identifies the five slash ten amp version: five amps nominal and ten amps continuous.
The one slash two amp version uses one amp nominal and two amps continuous. Match your CT secondary to the nominal input. The EM235's programmable CT primary range is one to fifty thousand amps. Let's enter two hundred.
For the SATEC HACS version, with a forty milliamp secondary, only use SATEC-supplied High Accuracy Current Sensors. If you're unsure, please consult SATEC.
Let's start by using the down arrow to open Setup.
The default password is nine. If it's been changed, use your configured password. If you don't have it, ask your administrator, or contact SATEC for help.
Next, press the up arrow seven times to reach nine. Then press check.
Now move down to Apply, then press check to continue.
Next, open General Setup, then Basic Setup. Scroll down to the CT primary current field and press check.
Next, use Up to select delete. Press check twice.
Now move down to two, then press check.
Following this, use Up to reach zero. Press check twice to make two hundred.
Now move down to Apply, and press check to save.
After making the change, check that the CT primary current shows two hundred amps.