1 00:00:03,600 --> 00:00:09,925 Welcome to this demonstration on how to change the CT ratio, or primary current 2 00:00:09,925 --> 00:00:14,008 setting, on an EM235 PRO SATEC power quality meter. 3 00:00:14,008 --> 00:00:20,173 In this example, we've chosen a two hundred amp CT with a five amp secondary. 4 00:00:20,173 --> 00:00:23,536 Enter two hundred for the primary current. 5 00:00:23,536 --> 00:00:25,778 That's a forty-to-one ratio. 6 00:00:27,400 --> 00:00:31,206 Next, check the rating label on the side of your meter. 7 00:00:31,206 --> 00:00:36,673 Here, five with ten in brackets identifies the five slash ten amp version: five 8 00:00:36,673 --> 00:00:39,233 amps nominal and ten amps continuous. 9 00:00:44,133 --> 00:00:50,029 The one slash two amp version uses one amp nominal and two amps continuous. 10 00:00:50,029 --> 00:00:53,566 Match your CT secondary to the nominal input. 11 00:00:53,566 --> 00:00:59,226 The EM235's programmable CT primary range is one to fifty thousand amps. 12 00:00:59,226 --> 00:01:01,113 Let's enter two hundred. 13 00:01:02,533 --> 00:01:07,961 For the SATEC HACS version, with a forty milliamp secondary, only use SATEC- 14 00:01:07,961 --> 00:01:10,746 supplied High Accuracy Current Sensors. 15 00:01:10,746 --> 00:01:13,531 If you're unsure, please consult SATEC. 16 00:01:15,200 --> 00:01:18,387 Let's start by using the down arrow to open Setup. 17 00:01:20,167 --> 00:01:22,085 The default password is nine. 18 00:01:22,085 --> 00:01:25,460 If it's been changed, use your configured password. 19 00:01:25,460 --> 00:01:30,224 If you don't have it, ask your administrator, or contact SATEC for help. 20 00:01:32,800 --> 00:01:35,896 Next, press the up arrow seven times to reach nine. 21 00:01:35,896 --> 00:01:36,927 Then press check. 22 00:01:42,467 --> 00:01:45,340 Now move down to Apply, then press check to continue. 23 00:01:48,633 --> 00:01:51,698 Next, open General Setup, then Basic Setup. 24 00:01:51,698 --> 00:01:55,974 Scroll down to the CT primary current field and press check. 25 00:01:59,767 --> 00:02:01,677 Next, use Up to select delete. 26 00:02:01,677 --> 00:02:02,823 Press check twice. 27 00:02:04,367 --> 00:02:06,483 Now move down to two, then press check. 28 00:02:09,233 --> 00:02:11,772 Following this, use Up to reach zero. 29 00:02:11,772 --> 00:02:14,379 Press check twice to make two hundred. 30 00:02:16,700 --> 00:02:19,443 Now move down to Apply, and press check to save. 31 00:02:21,767 --> 00:02:26,625 After making the change, check that the CT primary current shows two hundred amps. 32 00:02:29,233 --> 00:02:30,171 Great work! 33 00:02:30,171 --> 00:02:33,410 Scan for the EM235, PM335 User Manual. 34 00:02:33,410 --> 00:02:37,671 Get in touch with us any time, we're here to help.