Welcome to this demonstration on how to change the CT ratio, or primary current setting, on an EM235 PRO SATEC power quality meter. In this example, we've chosen a two hundred amp CT with a five amp secondary. Enter two hundred for the primary current. That's a forty-to-one ratio. Next, check the rating label on the side of your meter. Here, five with ten in brackets identifies the five slash ten amp version: five amps nominal and ten amps continuous. The one slash two amp version uses one amp nominal and two amps continuous. Match your CT secondary to the nominal input. The EM235's programmable CT primary range is one to fifty thousand amps. Let's enter two hundred. For the SATEC HACS version, with a forty milliamp secondary, only use SATEC-supplied High Accuracy Current Sensors. If you're unsure, please consult SATEC. Let's start by using the down arrow to open Setup. The default password is nine. If it's been changed, use your configured password. If you don't have it, ask your administrator, or contact SATEC for help. Next, press the up arrow seven times to reach nine. Then press check. Now move down to Apply, then press check to continue. Next, open General Setup, then Basic Setup. Scroll down to the CT primary current field and press check. Next, use Up to select delete. Press check twice. Now move down to two, then press check. Following this, use Up to reach zero. Press check twice to make two hundred. Now move down to Apply, and press check to save. After making the change, check that the CT primary current shows two hundred amps. Great work! Scan for the EM235, PM335 User Manual. Get in touch with us any time, we're here to help.