Which BFM-DFR records should I collect after a disturbance?

BFM-II DFR manufacturer datasheet cover
BFM-II DFR datasheet cover; confirm the installed variant.

The BFM-II Digital Fault Recorder (DFR) keeps several separate records for each sub-meter. This article lists them, shows how PAS retrieves them, and explains which settings decided what was captured. It covers PAS only, not the front display.

SATEC Australia's advice: after a feeder disturbance, collect all of these records with PAS before anyone changes the setup or resets the logs. For firmware, the manual itself says to "Ensure that stored data and configuration parameters setups are recorded before firmware download".

It applies to the BFM-II DFR as described in SATEC's BFM II EM and DFR Operation and Installation Manual, BG0588 Rev. A12 (July 2024), firmware reference "V37.2.XX – Energy Meter and Digital Fault Recorder, up to 12 3Ph sub-meters". It does not apply to the standard BFM-II energy meter or to the BFM136, which are different products with different records.

Record these details first

SATEC Australia's advice: before you retrieve anything, write down:

  • the model and serial number from the device label (the manual shows a separate DFR device label, Figure 1-2);
  • the firmware version, because the manual says to "Use the following firmware references to check your device's options";
  • the device base address and the addresses of the sub-meters involved, because each sub-meter has its own address and its own logs;
  • the device clock reading next to your PC's time.

The device clock is read in the PAS RTC dialog. The manual says to select a site with the base device address, go on line, and then select RTC from the Monitor menu. The dialog shows the current PC time and the time in your device; to synchronise the device clock with the PC clock, you click Set.

SATEC Australia's advice: note the difference between the two times, but do not press Set until the records are retrieved. That way the difference you noted still applies to the time stamps in the records.

The base address is the address of sub-meter 1. If several meters on the site share one network, the existing article How do I address multiple BFM meters on RS-485 or Ethernet? explains how the sub-meter address blocks work.

What the DFR records for each sub-meter

The manual lists these records for each sub-meter on a DFR. Every one is a wrap-around file: when it is full, the newest record overwrites the oldest.

RecordWhat the manual says it holdsCapacity per sub-meter
Fault logFault events; the fault recorder "records time-tagged fault events into the fault event report"1,000 records
Waveform logCaptured waveforms500 records
Data log #13 (fault data trend)Factory preset "for RMS trending on the fault events": V1–V3, I1–I3, In and zero-sequence voltage17,000 records
Data logs #2, #3 and #4General-purpose data logs17,000 records each
Data log #1Periodic interval data17,000 records
Event logGeneral device events, including diagnostics, in the first Event log; time-tagged set-point events where a set-point is set to record them2,000 most recent events

General device events, including the device diagnostics, go into the first Event log, which is accessed at the device base address.

These are record counts, not a period of time. How far back they reach depends on how often faults occur and how the recorders are set up. The manual gives no retention period.

What decides whether anything was captured

The fault recorder is set up in PAS under Meter Setup → Memory/Log → Fault Recorder. Some settings there decide what you will find:

  • Recorder Enabled. The manual says "The Fault recorder can be globally disabled or enabled in your device."
  • Trigger Enabled. Each internal trigger must be enabled on its own. If the box is unchecked, "the Fault Recorder does not respond to the trigger".
  • Digital triggers. "The external triggering is enabled for the Fault recorder by default and cannot be disabled by the user." Each input is mapped to the matching sub-meter: "DI #1 is mapped to SM #1, DI #2 is mapped to SM #2, etc."
  • Waveform Log On Start / On End. By default, On Start is checked and On End is unchecked. These settings enable waveform logging when the fault event starts or ends.
  • 1-cycle RMS Plot Log Enabled. This setting, unchecked by default, "Enables concurrent RMS trace plot to the data log file while the fault event continues". It uses Data log #13.

The manual says the factory-set "Overcurrent trigger can be used along with the second Undervoltage trigger combined by logical AND". It also says "The Zero-Sequence Voltage trigger and the Voltage Unbalance trigger are disabled by default."

SATEC Australia's advice: save a copy of the as-found fault recorder setup with the records, so that the results can be read against the settings that produced them.

How to retrieve the records in PAS

PAS retrieves the logs from each sub-meter and saves them on your PC in the MS Access database format.

  1. Connect PAS to the device and select the sub-meter's site.
  2. Retrieve Data log #1 and the Event log. The manual says data logs #2, #3, #4 and #13 are recorded and retrieved in the same way as Data log #1.
  3. Retrieve the Waveform log and Fault log from the Logs drop-down menu.
  4. Repeat for each sub-meter involved, including the base address for the device-wide events.

For general PAS log retrieval and site files, see PAS.

The manual does not say that retrieving a log clears it. Clearing is a separate PAS command: Monitor → Reset can clear log files in each sub-meter. SATEC Australia's advice: do not use Reset on the log files while collecting evidence.

Before any firmware update

The manual's firmware notes say: "Ensure that stored data and configuration parameters setups are recorded before firmware download". They also say: "If firmware download process is interrupted for some reason or below instructions are not followed properly that can result in data loss".

Clock and time stamps

The manual gives the real-time clock accuracy as a maximum error of 5 seconds per month at 25 °C. It says a backup lithium battery "keeps the meter clock running when the meter goes to standby after the main power is OFF".

The manual's SNTP client section is marked "(Future)". If the clock time has been lost, the device reports diagnostic code 11, "RTC fault".

For an overview of clock methods across SATEC meters, see Clock synchronisation across SATEC meters. The existing article Replacing the BFM-II backup battery covers the standard BFM-II; it is not confirmed whether it applies to the DFR.

What to send to support

SATEC Australia's advice: when you contact SATEC Australia about a disturbance, include:

  • the label details, firmware version and addresses you recorded;
  • the clock difference you noted;
  • the PAS database files with the retrieved records;
  • the as-found fault recorder setup;
  • the diagnostics shown in PAS or on the display.

Contact SATEC Australia technical support through our contact form.

Source review: 22 November 2026.