PM175 · QUICK START GUIDE
PM175 quick start guide
PM175 Series Powermeter
Transcribed from the SATEC document Quick Start Guide PM175 Series Powermeter, BG0456 REV.A2, date not printed (PDF, 13 pages, 1090 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.
Introduction
The PM175 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging from electrical panel builders to substation operators.
If you are familiar with the PM175 Powermeter, use this quick start guide to prepare the units for operation. If you are not familiar with the PM175, read the Installation and Operation Manual carefully before installing and using the unit.
This quick start guide does not contain information on all the features of PM175. See the Installation and Operation Manual for full operating details and features.
Assembly Instructions
Figure 1: Instrument Dimensions. Drawing not reproduced on this page. See page 2 of the PDF.
The PM175 may be mounted in a standard 4-inch round or DIN92 square cutout.
Figure 2 (ANSI 4" round cutout): Mounting the display unit. Drawing not reproduced on this page. See page 3 of the PDF.
Figure 3 (DIN 92x92mm square cutout): Mounting the display unit. Drawing not reproduced on this page. See page 3 of the PDF.
Figure 4: Slide and position the meter on locating studs. Drawing not reproduced on this page. See page 4 of the PDF.
Figure 5: Affix the meter using the thumb nuts (please do not over-tighten the nuts). Drawing not reproduced on this page. See page 4 of the PDF.
Electrical Installation
The figure below shows all the connectors and terminals on the rear side of the PM175.
Figure 6: Connections and Terminals (Digital Inputs, Analog Inputs/Outputs, Relay Outputs, AC Current inputs, AC Voltage Inputs, COM1 Port, COM2 Port, Chassis Ground, Power Supply). Drawing not reproduced on this page. See page 5 of the PDF.
The diagrams below show typical installations of the PM175.
Figure 7: Typical Installation 2. Drawing not reproduced on this page. See page 6 of the PDF.
The typical installation diagram above shows a 4-Wire Wye 3-element connection using 3 PTs and 3 CTs. The wiring mode is 4LL3 or 4Ln3.
Figure 8: Typical Installation 2. Drawing not reproduced on this page. See page 6 of the PDF.
The typical installation diagram above shows a 4-Wire Wye 2½-element connection using 2 PTs and 3 CTs. The wiring mode is 3LL3 or 3Ln3. The voltages must be balanced for the configuration to provide accurate power measurements.
There are approximately nine different wiring configurations in the PM17X Series. Refer to the Installation and Operational Manual for additional configurations.
For electrical installation of the display panel follow the following steps:
- Connect the remote display using the pinout tables below, either for a self-powered display or a remote powered display. Refer to the Installation and Operation Manual for the wiring schematic diagrams.
| PM175 D15 Female Pinout | Signal | Remote Display D15 Male Pinout |
|---|---|---|
| 1 | +12V | 1 |
| 5 | RS-485 + (plus) | 5 |
| 7 | RS-485 - (minus) | 7 |
| 8 | GND | 8 |
| 15 | Chassis | 15 |
| PM175 D15 Female Pinout | Signal | Remote Display D15 Male Pinout |
|---|---|---|
| 1 N.C. | +12V | 1 |
| 5 | RS-485 + (plus) | 5 |
| 7 | RS-485 - (minus) | 7 |
| 8 N.C. | GND | 8 |
| 15 | Chassis | 15 |
- Connect the DC or AC power.
- Connect the chassis ground.
- Connect the required wiring configuration.
- Connect the I/O connections as required. For I/O ratings, see the Technical Specifications section in the Installation and Operation Manual.
Auto Return
If no buttons are pressed for 30 seconds while the display Auto Return option is enabled, the display automatically returns to the main screen from any other measurement display.
The Auto Return option is enabled through the Display Setup menu
Auto Scroll
If no buttons are pressed for 30 seconds while in the common measurements display, and the Auto Scroll option is enabled in the meter, the display automatically scrolls through all available pages. The scroll interval is adjustable in the Display Setup menu.
To stop auto scrolling, briefly press the SCROLL button.
Basic Setup: Entering the Password
The setup change menu is secured by a four-digit user password. The meter is primarily shipped with the password preset to 0, and password protection disabled. You can change the password and enable password protection through the Access Control menu.
If authorization is not required, just press the ENTER button to move to the Main menu; otherwise enter a correct password to be authorized to access the meter setup.
Password entry display: PASS 0000, UP arrow button, PASS 0201, ENERGY/ENTER button. Drawing not reproduced on this page. See page 9 of the PDF.
To enter the password:
- Adjust the first digit with the UP and DOWN arrow buttons.
- Press the SELECT button to advance to the next digit.
- Adjust the remaining password digits in the same manner.
- Press ENTER to confirm the password.
If the password entered is correct, you move to the Main menu, otherwise you return to the previous menu.
Basic Configuration
Use the navigation buttons to set up the PM175 as required.
The table below shows the available options. The asterisk * shows the default settings.
The basic menu allows you to configure the basic meter settings that define the general operating characteristics of the device.
To enter the menu, select the “bASc” entry from the main menu by the UP and DOWN arrow buttons, and then press the ENTER button.
To select a setup option:
- Press the SELECT button to activate the middle window.
- Use the UP and DOWN arrow buttons to scroll to the desired option.
Menu display: bASc, ConF, 4Ln3. Drawing not reproduced on this page. See page 9 of the PDF.
To change the option:
- Press the SELECT button to activate the lower window.
- Use the UP and DOWN arrow buttons to select the desired option.
- Press ENTER to confirm your changes and to store your new setting, or press ESC to discard changes.
- Press ESC to exit the menu.
The table below lists the available options.
| Label | Parameter | Options | Default | Description |
|---|---|---|---|---|
| ConF | Wiring connection (configuration) mode | 3OP2, 4LN3, 3DIR2, 4LL3, 3OP3, 3LN3, 3LL3, 3BLN3, 3BLL3 | 4Ln3 | The wiring connection of the device |
| Pt | PT ratio | 1.0-6500.0 | 1.0 | The phase potential transformer’s primary to secondary ratio |
| Pt.F | PT Ratio multiplier | ×1, ×10 | ×1 | PT Ratio multiplication factor. Used in extra high voltage networks to accommodate the PT ratio for 500 kV and higher networks. |
| U.SEC | Nominal secondary voltage | 10-690 V | 120 V | The nominal secondary line-to-neutral (in configurations with a neutral wire) or line-to-line voltage (in 3OP2, 3OP3 and 3DIR modes) voltage. Used as a reference voltage for the EN50160 evaluation. |
| Ct | CT primary current | 1-20,000 A | 5 A | The primary rating of the phase current transformer |
| d.P | Power block demand period | 1, 2, 3, 5, 10, 15, 20, 30, 60 min, E=external sync | 30 min | The length of the demand period for power demand calculations. If the external synchronization is selected, a pulse front on the digital input DI1 denotes the start of the demand interval. |
| nd.P | The number of blocks in the sliding window | 1-15 | 1 | The number of blocks to be averaged for sliding window demands |
| Ad.P | Ampere, volt and THD demand period | 0-1800 sec | 900 sec | The length of the demand period for ampere, volt and THD demand calculations |
| Freq | Nominal frequency | 50,60 Hz | 60 Hz | The nominal line frequency |
| LoAd | Maximum demand load current | 0-10000 A | 0 | The maximum demand load current (0 = CT primary) |
Setting the Communications
You communicate with the meter via a changeable COM1 communication port, or through a second factory set serial RS-485/RS-422 COM2 port. Depending on what was ordered, the COM1 port is equipped with an RS-232/RS-422/RS-485 serial interface, with a dial-up modem for communicating through public telephone lines, or with an Ethernet module for communicating through the Internet.
To configure the PM175 communication via PAS:
- Select Configuration from the Tools menu. Under the Communication group of the Instrument Setup tab, select the type of a connection for your device.
- Enter the device communication address you assigned to the PM175.
- In the Sampling Rate box, select a rate at which PAS updates data on your screen when you continuously poll the device in the PAS Data Monitor.
The communication protocol and port settings in PAS must match the settings made in your device.
| Code | Parameter | Options | Description |
|---|---|---|---|
| Prot | Communications protocol | ASCII, rtu*, dnP3 | ASCII, Modbus RTU or DNP3.0 protocol |
| rS | Port Interface, depends on order | 232 = RS-232; 485 = RS-485; 422 = RS-422; dial = Dial-up Modem; Eth.= Ethernet | For non-serial interfaces this is not changeable, it is automatically detected by the meter |
| Addr | Device Address | Modbus: 1 (default) -247; DNP3.0: 0 (default) -255 | |
| bAud | Baud rate | 300 - 115,200 bps (19,200 bps*) | |
| dAtA | Data format | 7E, 8E (7/8 bits, even parity), 8N* (8 bits, no parity). 7E data format should not be used with the Modbus RTU and DNP3 protocols | |
| H.Sh | Handshaking (flow control) | nonE*=no flow control; SOFt=software (XON/XOFF); HArd=hardware (CTS) | |
| rtS | RTS mode | nonE* = not used; Forc = RTS is permanently asserted; CtrL = RTS is asserted during the transmission |
| Code | Parameter | Options | Description |
|---|---|---|---|
| Prot | Communications protocol | Rtu* = Modbus RTU; ASCII = Modbus ASCII; dnP3 = DNP3 | The communications protocol supported by the port |
| rS | Port Interface | 485* = RS-485; 422 = RS-422 | |
| Addr | Address | Modbus: 1*-247; DNP3: 0–65532 | Device network address |
| bAud | Baud rate | 300-115,200 bps (19,200 bps*) | The port baud rate. |
| dAtA | Data format and parity | 7E, 8N*, 8E | 7E data format should not be used with the Modbus RTU and DNP3 protocols |
Figure 10 COM1: Telephone Line Connection. Drawing not reproduced on this page. See page 12 of the PDF.
Figure 11 COM1: Ethernet Connection. Drawing not reproduced on this page. See page 12 of the PDF.
Communicating via the Internet
If you are communicating through the Ethernet port, define the IP address of your meter on the network.
To define the IP address:
- On the Instrument Setup tab, select Internet Site.
- Click on the Connection tab.
- Select the IP Address and type in the IP address of your meter. The default IP address preset at the factory is 192.168.0.203.
- In the Protocol box, select the communications protocol for the TCP port. The meter can provide Modbus/TCP connections on TCP port 502 and DNP3/TCP connections on port 20000. The host port is set automatically as you select the protocol. Select Modbus RTU for Modbus/TCP or DNP3 for DNP3/TCP.
- In the Wait for Answer box, adjust the time that PAS waits for a connection before announcing an error and the number of retries PAS uses to receive a response from the device if communications fail.
Input and Output Ratings
| 3 voltage inputs | 690 V: (standard) | DIRECT INPUT - Nominal: 690V line-to-line voltage, 790V maximum; 400V line-to-neutral, 460V maximum - Burden: <0.4 VA. INPUT USING PT - Burden: <0.15 VA |
| 3 voltage inputs | 120 V: (optional) | INPUT USING PT - Nominal: 120V line-to-line voltage, 144V maximum - Burden: <0.04 VA |
| 3 voltage inputs | Voltage input terminals | Maximum wire section: 4 mm2 (10 AWG) |
| 3 current inputs (Galvanically isolated) | 5A: (standard) | INPUT VIA CT with 5A secondary output - Burden: 2.5 to 4 mm2 (13-11 AWG) wire from CT. Operating range: continuous 10A RMS Burden: < 0.1 VA. Overload withstand: 15A RMS continuous, 10A RMS for 1 second. |
| 3 current inputs (Galvanically isolated) | 1A:(optional) | INPUT VIA CT with 1A secondary output - Burden: 2.5 to 4 mm2 (13-11 AWG) wire from CT. Operating range: continuous 2A RMS Burden: < 0.02 VA. Overload withstand: 3A RMS continuous, 80A RMS for 1 second. |
| Communication port COM1 | EIA RS-485 standard | Optically isolated, max. speed 115.2Kb/s |
| Communication port COM1 | COM1 terminals | 3 x Maximum wire section: 2.5 mm2 (12 AWG) |
| Communication port COM1 (Optional) | Profibus | Max. speed 12 Mb/s |
| Communication port COM1 (Optional) | Profibus terminals | 5 x Maximum wire section: 2.5 mm2 (12 AWG) or using terminal to DB9 converter: P/N AC0153 REV.A2 |
| Communication port COM2 (Optional) | Ethernet | 10/100 Base T, auto adaptation speed, Max. speed 100Mb/s |
| Communication port COM2 (Optional) | ETH connector | Shielded RJ45 cable |
| Power Supply (Galvanically isolated) | 120/230 V AC/DC (standard) | 85-265VAC, 88-290VDC; 50/60/400 Hz 9VA |
| Power Supply (Galvanically isolated) | 12 VDC (optional) | 9.5-18 VDC |
| Power Supply (Galvanically isolated) | 24/48 VDC (optional) | 18.5-72 VDC |
| Power Supply (Galvanically isolated) | Power Supply input terminals | 3 x Maximum wire section: 2.5 to 4 mm2 (13-11 AWG) |
Downloads and related
- Download the PDF (BG0456 REV.A2, 1090 KB)
- Read the PDF in the document library
- Product support: answers, documents and videos
- All quick start guides as web pages
- Which PM175 display drawing applies to my panel?
- What does the PM175 LED display's CT primary setting mean?
- Is the PM175 PRO a suitable replacement for my legacy PM175?
Questions about this document? Use the contact form.