PM172 · QUICK START GUIDE

PM172 quick start guide

PM172P/PM172E/PM172EH

Transcribed from the SATEC document PM172 Quick Start Guide, not printed, date not printed (PDF, 14 pages, 794 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.

Introduction

The PM172 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging from electrical panel builders to substation operators.

If you are familiar with the PM172 Powermeter, use this quick start guide to prepare the units for operation. If you are not familiar with the PM172, read the Installation and Operation Manual carefully before installing and using the unit.

This quick start guide does not contain information on all the features of PM172. See the Installation and Operation Manual for full operating details and features.

Assembly Instructions

Figure 1: Instrument Dimensions. Drawing not reproduced on this page. See page 2 of the PDF.

The PM172 is mounted in a standard 4-inch round or DIN92 square cutout.

Figure 2 STEP 1 (ANSI 4" round cutout): Mount the display module in cutout. Drawing not reproduced on this page. See page 3 of the PDF.

Figure 3 STEP 1 (DIN 92x92mm square cutout): Mount the display module in cutout. Drawing not reproduced on this page. See page 3 of the PDF.

Figure 4: Slide and position the meter on locating studs. Drawing not reproduced on this page. See page 4 of the PDF.

Figure 5: Affix the meter using the thumb nuts. Drawing not reproduced on this page. See page 4 of the PDF.

Electrical Installation

WarningIMPORTANT! Only qualified personnel can perform setup.
WarningAll incoming power sources must be turned off during installation. During operation of the Powermeter, hazardous voltages are present on the input terminals. Failure to observe precautions can result in serious or even fatal injury, or damage to equipment.
WarningRefer to the installation and operation manual for further information.

The figure below shows all the connectors and terminals on the rear side of the PM172.

Figure 6: Connections and Terminals. Drawing not reproduced on this page. See page 5 of the PDF.

WarningATTENTION Static-Sensitive Devices Handle Only at Static-Safe Workstations

The diagrams below show typical installations of the PM172.

Figure 7: Typical Installation 1. Drawing not reproduced on this page. See page 6 of the PDF.

The typical installation diagram above shows a 4-Wire Wye 3-element connection using 3 PTs and 3 CTs. The wiring mode is 4LL3 or 4Ln3.

Figure 8: Typical Installation 2. Drawing not reproduced on this page. See page 6 of the PDF.

The typical installation diagram above shows a 4-Wire Wye 2½-element connection using 2 PTs and 3 CTs. The wiring mode is 3LL3 or 3Ln3. The voltages must be balanced for the configuration to provide accurate power measurements.

There are approximately nine different wiring configurations in the PM17X Series. Refer to the Installation and Operational Manual for additional configurations.

For electrical installation of the display panel follow the following steps:

  1. Connect the remote display using the pinout tables below, either for a self-powered display or a remote powered display. Refer to the Installation and Operation Manual for the wiring schematic diagrams.
Pinout for a self-powered remote display
PM172 D15 Female PinoutSignalRemote Display D15 Male Pinout
1+12V1
5RS-485 + (plus)5
7RS-485 - (minus)7
8GND8
15Chassis15
Pinout for a remote display powered from an external 12V DC, 350 mA power source
PM172 D15 Female PinoutSignalRemote Display D15 Male Pinout
1 N.C.+12V1
5RS-485 + (plus)5
7RS-485 - (minus)7
8 N.C.GND8
15Chassis15
  1. Connect the DC or AC power.
  2. Connect the chassis ground.
  3. Connect the required wiring configuration.
  4. Connect the I/O connections as required. For I/O ratings, see the Technical Specifications section in the Installation and Operation Manual.

Using the Navigation Buttons

Figure 9: Navigation Buttons. Drawing not reproduced on this page. See page 7 of the PDF.

Setup is performed directly from the display panel or via the communication ports using PAS communication software.

In Data Display mode, the navigation buttons function as follows.

The MIN/MAX button switches to the Min/Max Maximum Demands display pages. When briefly pressed again, it switches back to the common measurements display.

The TDD/THD/ESC button switches between different total harmonics (THD/TDD) displays. Individual harmonic analysis is available in the PM172EH model only. When briefly pressed once again, it switches back to the common measurements display.

The UP and DOWN arrow buttons, labeled by arrowheads, scroll forwards and backwards through the display pages. Pressed briefly, they move one page forward or backward. If you hold the button down, the display pages are scrolled at rate of a twice per second.

Pressing both the UP and DOWN arrow buttons together returns to the first page within the current display.

The SELECT button operates once it’s released. The button has two functions:

The ENERGY/ENTER button switches to the Energy display. If TOU registers are configured in the meter, you can repeatedly press this button to scroll through all available TOU registers. When briefly pressed once again, it switches back to the common measurements display. The energy measurements are not available in the PM172P model. In this model the ENERGY/ENTER button is replaced by the ENTER button.

Auto Return

If no buttons are pressed for 30 seconds while the display Auto Return option is enabled, the display automatically returns to the main screen from any other measurement display.

The Auto Return option is enabled through the Display Setup menu

Auto Scroll

If no buttons are pressed for 30 seconds while in the common measurements display, and the Auto Scroll option is enabled in the meter, the display automatically scrolls through all available pages. The scroll interval is adjustable in the Display Setup menu.

To stop auto scrolling, briefly press the SCROLL button.

Basic Setup: Entering the Password

The setup change menu is secured by a four-digit user password. The meter is primarily shipped with the password preset to 0, and password protection disabled. You can change the password and enable password protection through the Access Control menu.

If authorization is not required, just press the ENTER button to move to the Main menu; otherwise enter a correct password to be authorized to access the meter setup.

Display example: PASS 0000, UP arrow button, PASS 0201, ENERGY/ENTER button. Drawing not reproduced on this page. See page 9 of the PDF.

To enter the password:

  1. Adjust the first digit with the UP and DOWN arrow buttons.
  2. Press the SELECT button to advance to the next digit.
  3. Adjust the remaining password digits in the same manner.
  4. Press ENTER to confirm the password.

If the password entered is correct, you move to the Main menu, otherwise you return to the previous menu.

Basic Configuration

Use the navigation buttons to set up the PM172 as required.

The table below shows the available options. The asterisk * shows the default settings.

The basic menu allows you to configure the basic meter settings that define the general operating characteristics of the device.

To enter the menu, select the “bASc” entry from the main menu, and then press the ENTER button.

To select a setup option:

  1. Press the SELECT button to activate the middle window.
  2. Use the UP and DOWN arrow buttons to scroll to the desired option.

Display example: bASc, ConF, 4Ln3. Drawing not reproduced on this page. See page 9 of the PDF.

To change the option:

  1. Press the SELECT button to activate the lower window.
  2. Use the UP and DOWN arrow buttons to select the desired option.
  3. Press ENTER to confirm your changes and to store your new setting, or press ESC to discard changes. The table below lists the available options.
  4. Press ESC to exit the menu.
Basic setup options
LabelParameterOptionsDefaultDescription
ConFWiring connection (configuration) mode3OP2, 4LN3, 3DIR2, 4LL3, 3OP3, 3LN3, 3LL3, 3BLN3, 3BLL34Ln3The wiring connection of the device
PtPT ratio1.0-6500.01.0The phase potential transformer’s primary to secondary ratio
Pt.FPT Ratio multiplier×1, ×10×1PT Ratio multiplication factor. Used in extra high voltage networks to accommodate the PT ratio for 500 kV and higher networks.
U.SECNominal secondary voltage10-690 V120 VThe nominal secondary line-to-neutral (in configurations with a neutral wire) or line-to-line voltage (in 3OP2, 3OP3 and 3DIR modes) voltage. Used as a reference voltage for the EN50160 evaluation.
CtCT primary current1-20,000 A5 AThe primary rating of the phase current transformer
d.PPower block demand period1, 2, 3, 5, 10, 15, 20, 30, 60 min, E=external sync15 minThe length of the demand period for power demand calculations. If the external synchronization is selected, a pulse front on the digital input DI1 denotes the start of the demand interval.
nd.PThe number of blocks in the sliding window1-151The number of blocks to be averaged for sliding window demands
Ad.PAmpere, volt and THD demand period0-1800 sec900 secThe length of the demand period for ampere, volt and THD demand calculations
FreqNominal frequency50,60 Hz60 HzThe nominal line frequency
LoAdMaximum demand load current0-10000 A0The maximum demand load current (0 = CT primary)
WarningAlways specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs.
WarningThe maximum value for the product of the phase CT primary current and PT ratio is 57,500,000. If the product is greater, power readings are zeroed.

Setting the Communications

You communicate with the meter via a changeable COM1 communication port, or through a second factory set serial RS-485/RS-422 COM2 port.

Communications Connections

Several communication options are available for the PM172:

The RS-232/RS-422/RS-485 port is the standard port for COM1. Other options are ordered separately. Connections to the Ethernet RJ45 connector and to the telephone RJ11 connector are made through a cable adaptor provided with your meter (if ordered).

A full description of the communication protocols is found in the PM172 protocol guides provided with your meter.

COM1 RS-232 Connection

COM1 RS-232 connection: 9-pin D-type connector on the rear panel. Drawing not reproduced on this page. See page 11 of the PDF.

Connector 9-pin D-type female
PinSignal
1RS-232 RTS
2RS-232 RxD
3RS-232 TxD
4RS-232 CTS
5RS-232 Signal ground

To configure the PM172 communication via PAS:

  1. Select Configuration from the Tools menu.
  2. Under the Communication group of the Instrument Setup tab, select the type of a connection for your device.
  3. Set the device communication address you assigned to the PM172.
  4. In the Sampling Rate box, select a rate at which PAS updates data on your screen when you continuously poll the device in the PAS Data Monitor.

The communication protocol and port settings in PAS must match the settings made in your device.

COM1 Settings

COM1 Settings
CodeParameterOptionsDescription
ProtCommunications protocolASCII, rtu*, dnP3ASCII, Modbus RTU or DNP3.0 protocol
rSPort Interface, depends on order232 = RS-232; 485 = RS-485; 422 = RS-422; dial = Dial-up Modem; Eth.= EthernetFor non-serial interfaces this is not changeable, it is automatically detected by the meter
AddrDevice AddressModbus: 1 (default) -247; DNP3.0: 0 (default) -255
bAudBaud rate300 - 115,200 bps (19,200 bps*)
dAtAData format7E, 8E (7/8 bits, even parity), 8N* (8 bits, no parity). 7E data format should not be used with the Modbus RTU and DNP3 protocols
H.ShHandshaking (flow control)nonE*=no flow control; SOFt=software (XON/XOFF); HArd=hardware (CTS)
rtSRTS modenonE* = not used; Forc = RTS is permanently asserted; CtrL = RTS is asserted during the transmission

COM2 Settings

COM2 Settings
CodeParameterOptionsDescription
ProtCommunications protocolRtu* = Modbus RTU; ASCII = Modbus ASCII; dnP3 = DNP3The communications protocol supported by the port
rSPort Interface485* = RS-485; 422 = RS-422
AddrAddressModbus: 1*-247; DNP3: 0–65532Device network address
bAudBaud rate300-115,200 bps (19,200 bps*)The port baud rate.
dAtAData format and parity7E, 8N*, 8E7E data format should not be used with the Modbus RTU and DNP3 protocols

Figure 10: COM1 Telephone Line Connection (cable adaptor AC0140). Drawing not reproduced on this page. See page 13 of the PDF.

Figure 11: COM1 Ethernet Connection (cable adaptor AC0139, RJ45). Drawing not reproduced on this page. See page 13 of the PDF.

Communicating via the Internet

If you are communicating through the Ethernet port, define the IP address of your meter on the network.

  1. On the Instrument Setup tab, select Internet Site.
  2. Click on the Connection tab.
  3. Select the IP Address and type in the IP address of your meter. The default IP address preset at the factory is 192.168.0.203.
  4. In the Protocol box, select the communications protocol for the TCP port. The meter can provide Modbus/TCP connections on TCP port 502 and DNP3/TCP connections on port 20000. The host port is set automatically as you select the protocol. Select Modbus RTU for Modbus/TCP or DNP3 for DNP3/TCP.
  5. In the Wait for Answer box, adjust the time that PAS waits for a connection before announcing an error and the number of retries PAS uses to receive a response from the device if communications fail.

Input and Output Ratings

Input and Output Ratings
3 voltage inputs690 V: (standard)DIRECT INPUT - Nominal: 690V line-to-line voltage, 790V maximum; 400V line-to-neutral, 460V maximum - Burden: <0.4 VA. INPUT USING PT - Burden: <0.15 VA
3 voltage inputs120 V: (optional)INPUT USING PT - Nominal: 120V line-to-line voltage, 144V maximum - Burden: <0.04 VA
3 voltage inputsVoltage input terminalsMaximum wire section: 4 mm2 (10 AWG)
3 current inputs (Galvanically isolated)5A: (standard)INPUT VIA CT with 5A secondary output - Burden: 2.5 to 4 mm2 (13-11 AWG) wire from CT. Operating range: continuous 10A RMS Burden: < 0.1 VA. Overload withstand: 15A RMS continuous, 10A RMS for 1 second.
3 current inputs (Galvanically isolated)1A:(optional)INPUT VIA CT with 1A secondary output - Burden: 2.5 to 4 mm2 (13-11 AWG) wire from CT. Operating range: continuous 2A RMS Burden: < 0.02 VA. Overload withstand: 3A RMS continuous, 80A RMS for 1 second.
Communication port COM1EIA RS-485 standardOptically isolated, max. speed 115.2Kb/s
Communication port COM1COM1 terminals3 x Maximum wire section: 2.5 mm2 (12 AWG)
Communication port COM1 (Optional)ProfibusMax. speed 12 Mb/s
Communication port COM1 (Optional)Profibus terminals5 x Maximum wire section: 2.5 mm2 (12 AWG) or using terminal to DB9 converter: P/N AC0153 REV.A2
Communication port COM2 (Optional)Ethernet10/100 Base T, auto adaptation speed, Max. speed 100Mb/s
Communication port COM2 (Optional)ETH connectorShielded RJ45 cable
Power Supply (Galvanically isolated)120/230 V AC/DC (standard)85-265VAC, 88-290VDC; 50/60/400 Hz 9VA
Power Supply (Galvanically isolated)12 VDC (optional)9.5-18 VDC
Power Supply (Galvanically isolated)24/48 VDC (optional)18.5-72 VDC
Power Supply (Galvanically isolated)Power Supply input terminals3 x Maximum wire section: 2.5 to 4 mm2 (13-11 AWG)