PM172 · IDENTIFY

Which PM172 model, display and manual apply to my installation?

SATEC PM172 series powermeter, front panel with three rows of red LED digits
PM172 series product illustration from the manufacturer's manual cover

The established PM172 comes in three models, plus a version with no display. This page sets out how the documents describe each one, which manual applies, and what to note before asking for help.

The PM172 models

The manual describes the three models like this.

ModelManual's description
PM172P"basic model - offers all standard metering and control capabilities of the PM172 Series"
PM172E"adds to above an energy meter, an event recorder and a multi-channel data recorder"
PM172EH"adds to above extended harmonic analysis and incorporates a fast waveform recorder with the voltage disturbance monitor"

The SATEC Australia datasheet lists the RPM072 as the "PM172E-N transducer version, no display".

The manual marks the event recorder and data recorders as PM172E and PM172EH features, and the waveform recorders as a PM172EH feature.

The PM172 PRO is a different product. It has its own manual, the PM17X PRO Installation and Operation Manual (BG0657).

Read the rear label

The manual's rear-view drawing shows a label with the serial number (S/N), and boxes for these options:

  • the current input (1A CT or 5A CT)
  • the voltage input (690V or OPT.U)
  • the calibration frequency
  • the power supply, including the low DC options
  • analogue inputs or outputs
  • the COM1 option: RS-232/422/485, Ethernet, modem or Profibus

The manual says: "Before connecting your meter to the power source, check the label on the back of the device to ensure that it is equipped with the appropriate power supply."

SATEC Australia's advice: photograph the rear label before starting any work on the meter.

The SATEC Australia datasheet gives the order code as "MODEL – VOLTAGE – CURRENT – CAL. FREQ. – POWER – I/O MODULE – COMMUNICATION".

Firmware versions on the LED display

The manual says the display setup menu (diSP) lets you "view display and device firmware versions". Its table lists two SoFt items: "Display firmware version" and "Device firmware version". OPS is the primary-menu entry for reviewing setup options, and CHG is the entry for changing them.

These steps follow the manual's menu instructions.

  1. Press and release SELECT to open the primary menu. Press SELECT to activate the OPS window, then press ENTER.
  2. Press SELECT to highlight the upper item, use UP and DOWN until diSP appears, then press ENTER.
  3. Press SELECT to activate the middle window, then use UP and DOWN to scroll to each SoFt item. The lower item shows its value.
  4. Press ESC to exit.

Which manual applies

The Series PM172 Installation and Operation Manual, BG0399 Rev. A9, covers the PM172P, PM172E and PM172EH. The manual says the three-row LED display module "is freely detachable and can be located at a distance of up to 1000 meters from the device".

The datasheets also mention a touch-screen display:

  • The SATEC Australia datasheet lists an "Optional colour touch screen graphical display".
  • The factory's January 2020 datasheet describes a "5.7” large color graphic touch screen".

The installation manual's display instructions are for the LED display, and it doesn't mention a touch screen. SATEC Australia's advice: if your PM172 has a touch screen, contact SATEC Australia for its documentation, and don't follow the LED menu steps.

For the LED display module, the manual shows an ANSI 4" round cutout and a DIN 92x92mm square cutout. The meter itself can be mounted on a 35-mm DIN rail.

Dated documents give different figures

DocumentData recordersHarmonicsPM172EH waveform sampling
Manual BG0399 Rev. A9"Eight data recorders" (PM172E, PM172EH)THD, current TDD and K-Factor "up to 40th order harmonic""32 and 128 samples per cycle"
SATEC Australia datasheet TBV1.0 (28 September 2026)"Eight data recorders" (under "PM172E & PM172EH ONLY")THD, TDD and K-Factor "up to the 40th order"; spectrum and angles "up to the 40th order (PM172EH)""Sampling rates of 32 and 128 samples per cycle"
Factory datasheet, January 2020"16 data recorders" (PM172E, PM172EH)"harmonic spectrum and angles, up to 50th order""32, 64 and 128 samples per cycle"

None of these documents says which units the 2020 datasheet figures apply to. SATEC Australia's advice: if a recorder count or harmonic order matters to your job, give SATEC Australia the model, rear label details and firmware versions of your own unit, rather than relying on one document.

Current sensors other than standard CTs

Addenda to the PM17x manuals cover versions with external current sensors: PM17x-HACS, PM17x-RS5, and the PM172XSC5 and PM172XSC50 add-on series. They include rules for the CT primary current setting. SATEC Australia's advice: if the label shows one of these versions, give SATEC Australia the label details before reviewing the meter's setup.

Remote displays

To check an RPM072 remote display connection, see How do I check an RPM072 remote display connection?

What to send SATEC Australia

SATEC Australia's advice: include these details when you contact SATEC Australia about a PM172:

  • the model (PM172P, PM172E, PM172EH or RPM072), as marked on the unit or in the order documents
  • the serial number and a photo of the rear label
  • the display type: LED, touch screen or none
  • the display and device firmware versions (diSP, SoFt)
  • what you are trying to do, and which document you are using

Manuals and datasheets

Need help?

Contact SATEC Australia technical support through our contact form.