EM132 · QUICK START GUIDE

EM132 and EM133 quick start guide

Quick Start Guide EM132-133 expertmeter™

Transcribed from the SATEC document EM132-133 Quick Start Guide, BG0504 REV.A3, date not printed (PDF, 10 pages, 1231 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.

Mechanical Installation

Figure 1: Instrument Dimensions. Drawing not reproduced on this page. See page 2 of the PDF.

Figure 2: Mounting the EM13X on DIN Rail or on flat surface. Drawing not reproduced on this page. See page 3 of the PDF.

Use flat screwdriver to disassemble the EM133 from the rail, by inserting the screwdriver to the plastic window to pull down the black plastic DIN RAIL retainer

WarningIMPORTANT! Only qualified personnel can perform setup. All incoming power sources must be turned off during installation. During operation of the Powermeter, hazardous voltages are present on the input terminals. Failure to observe precautions can result in serious or even fatal injury, or damage to equipment. Please refer to the installation and operation manual for further information.

Typical Electrical Installation

Figure 3:Common Wiring Mode: 4LL3 or 4Ln3. Drawing not reproduced on this page. See page 4 of the PDF.

Wiring configurations
Wiring ConfigurationSetup Code
3-wire 2-element Direct connection using 2 CTs3dir2
4-wire Wye 3-element direct connection using 3 CTs4Ln3 or 4LL3
4-wire Wye 3-element connection using 3 PTs, 3 CTs4Ln3 or 4LL3
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs3OP2
4-wire Wye 2½ -element connection using 2 PTs, 3 CTs3Ln3 or 3LL3
3-wire 2½ -element Open Delta connection using 2 PTs, 3 CTs3OP3
4-wire 3-element Delta direct connection using 3 CTs4Ln3 or 4LL3
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs3bLn3 or 3bLL3
Refer to the Installation and operation manual for the wiring schematics diagrams

Electrical Installation

Figure 4: CT Wiring options. Upper drawing: EM133-SE Model, Currents – direct connection with internal CT 50A (100A). Lower drawing: Currents – Transformer connection with External CT 40mA secondary, sensor leads marked RED (+) and ORANGE (-). Drawing not reproduced on this page. See page 5 of the PDF.

Module Installation

This section applies to the I/O and Communication modules.

Figure 5: PM130 PLUS modules (MODULE 4DI/2DO, MODULE ETHERNET, MODULE 4 ANALOG OUT). Drawing not reproduced on this page. See page 6 of the PDF.

Figure 6: Mounting module. Drawing not reproduced on this page. See page 6 of the PDF.

Module Connector Cover. Remove Module Connector Cover before assembling module

Refer to the Installation and operation manual for the wiring schematics diagrams and setup parameters
WarningCAUTION! Before I/O Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.

Basic Setup

All setups can be performed directly from the display panel or via communication ports using PAS communication software, except for Communications and Display setups, which must be performed directly at the instrument panel.

EM133 front panel with callouts: Alphanumeric LCD display, RS-485 COM1 port Activity LED, Navigation Buttons, IR COM3 port, Phrases presence LED, Wh/varh PULSE LED, Device Label ID. Drawing not reproduced on this page. See page 7 of the PDF.

To set the CT Primary current, perform the following steps:

Display screenshots for each step (time and NORM screen, Enter Password, Reset/Basic/Exit, Basic Conf 4Ln3, Basic CT 5000). Drawing not reproduced on this page. See page 7 of the PDF.

Data Display: Navigating in Display Mode

The front panel has a simple interface that allows you to display numerous measurement parameters in up to 38 display pages. For easier reading, the parameters are divided into three groups; each group is accessible by pressing the ↵ key and each group page is accessible by pressing the ▲ key.

The initial display is as described below:

Initial display: time, date, NORM, T1. Drawing not reproduced on this page. See page 8 of the PDF.

First push on ↵ will display Energy measurement parameters, by pushing ▲ will navigate to imp., exp. active/reactive, etc …as described below:

Second push on ↵ will display MAX DMD parameters, by pushing ▲ will navigate to MAX DMD P, Q, S, I, etc …as described below:

Third push on ↵ will display Votage/Current measurements, by pushing ▲ will navigate to V (L-N), V (L-L), I, Power, PF, THD, TDD, F, etc …as described below:

Basic Menu

Basic Menu
CodeParameterOptionsDescription
ConFWiring mode3OP23-wire open delta using 2 CTs
4Ln34-wire Wye using 3 PTs (default)
3dir23-wire direct connection using 2 CTs
4LL34-wire Wye using 3 PTs
3OP33-wire open delta using 3 CTs
3Ln34-wire Wye using 2 PTs
3LL34-wire Wye using 2 PTs
3bLn33-wire Broken delta using 2 PTs, 3 CTs
3bLL33-wire Broken delta using 2 PTs, 3 CTs
Pt RatioPT ratio1.0∗ - 6,500.0The potential transformer ratio
Pt Factor
CtCT primary current1-50,000A (5*)The primary rating of the current transformer
PowDmdPerPower demand period1, 2, 5, 10, 15*, 20, 30, 60, EThe length of the period for power demand calculations, in minutes. E = external synchronization
Num.Per.Number of power demand periods1-15 (1*)The number of demand periods to be averaged for sliding window demands 1 = block interval demand calculation
ADmdPer.Ampere/Volt demand period0-1800 (900*)The length of the period for volt/ampere demand calculations, in seconds. 0 = measuring peak current
FrequencyNominal frequency25, 50, 60, 400 (Hz)The nominal power utility frequency
MaxDmdLd
- Default setup

Communication Port Menu: COM1 setting

COM1 setting
CodeParameterOptionsDescription
ProtocolCommunications protocolASCII∗, rtu, dnP3ASCII, Modbus RTU (default) or DNP3.0 protocol
InterfaceInterface standard485RS-485 interface (default)
AddressAddressASCII: 0 (default) - 99, Modbus: 1 (default) -247, DNP3.0: 0 (default) -255
Baud RateBaud rate110, 300, 600, 1200, 2400, 4800, 9600 (default), up to 115,200 bps
Data/PartyData format7E, 8E (7/8 bits, even parity), 8n (default) (8 bits, no parity)
Snd.Delay

Input and Output Ratings

Input and Output Ratings
3 voltage inputs57/98-400/690 VACDIRECT INPUT - Nominal: 690V line-to-line voltage, 828V maximum; 400V line-to-neutral, 480V maximum - Burden: <0.5 VA. INPUT USING PT - Burden: <0.15 VA
3 voltage inputsVoltage input terminals4 x Maximum wire section: 2.5 mm² (12 AWG)
3 current nputs (Galvanic isolation)/5A(10A)INPUT VIA CT with 5A secondary output - Burden: <0.2VA, Overload withstands: 20A RMS continuous, 300A RMS for 0.5 second.
3 current nputs (Galvanic isolation)/1A(2A)INPUT VIA CT with 1A secondary output - Burden: <0.05VA, Overload withstands: 3A RMS continuous, 80A RMS for 0.5 second.
3 current nputs (Galvanic isolation)50A(100A)INPUT VIA CT with 50A direct connection - Burden: < 0.05VA, Overload withstands: 120A RMS continuous, 2000A RMS for 0.5 second.
3 current nputs (Galvanic isolation)40mA:(optional)INPUT VIA CT with 40mA secondary output, using external CT – Split Core CT or Solid Core CT – primary 100-1200A maximum rating
3 current nputs (Galvanic isolation)Current input terminals3 x Maximum wire section: 16 mm²
Communication port COM1EIA RS-485 standardOptically isolated, max. speed 115.2Kb/s
Communication port COM1COM1 terminals3 x Maximum wire section: 2.5 mm²
Communication port COM3IR COM portInfra Red, max. speed 38.4Kb/s
Power Supply (Galvanically isolated)40-300V AC/DC (standard)50/60 Hz - 9VA
Power Supply (Galvanically isolated)Power Supply input terminals3 x Maximum wire section: 2.5 mm²
MODULE 2DI/DODIGITAL INPUT x 2 optically isolated inputsDry contact, internally wetted @ 5VDC
MODULE 2DI/DODIGITAL OUTPUT x 10.15A/250 VAC - 400 VDC, 1 contact (SPST Form A)
MODULE 2DI/DO2DI/DO terminals5 x Maximum wire section: 2.5 mm²
MODULE 4DI/2DO (Optional)DIGITAL INPUT x 2 optically isolated inputsDry contact, internally wetted @ 24VDC
MODULE 4DI/2DO (Optional)DIGITAL OUTPUT x 2 EMR5A/250 VAC; 5A/30 VDC, 1 contact (SPST Form A)
MODULE 4DI/2DO (Optional)DIGITAL OUTPUT x 2 SSR0.15A/250 VAC - 400 VDC, 1 contact (SPST Form A)
MODULE 4DI/2DO (Optional)4DI/2DO terminals9 x Maximum wire section: 2.5 mm²
MODULE 4 AO (Optional)ANALOG OUT x 4 optically isolated outputs (4 different options)±1 mA, maximum load 5 kΩ (100% overload)
MODULE 4 AO (Optional)ANALOG OUT x 4 optically isolated outputs (4 different options)0-20 mA, maximum load 510 Ω
MODULE 4 AO (Optional)ANALOG OUT x 4 optically isolated outputs (4 different options)4-20 mA, maximum load 510 Ω
MODULE 4 AO (Optional)ANALOG OUT x 4 optically isolated outputs (4 different options)0-1 mA, maximum load 5 k Ω (100% overload)
MODULE 4 AO (Optional)4 AO terminals5 x Maximum wire section: 2.5 mm²
Communication port COM2 (Optional)Ethernet10/100 Base T, auto adaptation speed, Max. speed 100Mb/s
Communication port COM2 (Optional)ETH connectorShielded RJ45 cable
Communication port COM2 (Optional)ProfibusMax. speed 12 Mb/s
Communication port COM2 (Optional)Profibus terminals5 x Maximum wire section: 2.5 mm2 (12 AWG) or using terminal to DB9 converter: P/N AC0153 REV.A2
Communication port COM2 (Optional)EIA RS-232-422/485 standardOptically isolated, max. speed 115.2Kb/s – to be connected to GPRS modem if ordered
Communication port COM2 (Optional)COM2 terminals5 x Maximum wire section: 2.5 mm² And DB9 connector