Advanced P-Class and M-Class phasor measurement unit for wide area monitoring.
Transcribed from the SATEC Australia datasheet TBV1.0, 28 September 2026 (PDF, 8 pages, 938 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The PMU PRO is an advanced phasor measurement unit built for distribution network operators, utilities, substations and renewable generators that need precise, time-aligned visibility of their grid. It measures synchronised voltage and current phasors, frequency and rate of change of frequency to IEEE C37.118.1 P-Class and M-Class performance, then streams that data over Ethernet via IEEE C37.118.2 or IEC 61850-9-2 sampled values.
Based on the familiar PRO Series look and feel, it combines 1 to 240 frames per second reporting and 1µs time stamp accuracy with IRIG-B or IEEE 1588 PTPv2 time synchronisation. Dual port Ethernet, RS-485, USB-C, a 1.77" colour display, 16GB of log memory and up to four side-by-side expansion modules complete a compact DIN rail package.
Current input options
PMU PRO 5A
5A nominal current inputs for connection to standard secondary CTs.
PMU PRO 1A
1A nominal current inputs for 1A CT secondary circuits.
Main features
IEEE C37.118.1-2011, C37.118.1a-2014 and IEC/IEEE 60255-118-1:2018 P-Class and M-Class compliance
Synchronised three-phase voltage, current and sequence phasors
Synchronous frequency and ROCOF measurements
Advanced IEEE C37.118.2 data streaming over UDP and TCP
IEC 61850-9-2 multicast sampled value streaming
Reporting rates from 1 to 200/240 frames per second at 50/60Hz
Expected steady-state TVE below 0.05% and 1µs time stamp accuracy
IRIG-B and IEEE 1588 PTPv2 time synchronisation
Dual port Ethernet, RS-485 and USB-C communications
Up to four expansion modules and 16GB log memory
Feature capabilities
Phasor measurement (P-Class and M-Class)
IEEE C37.118.1-2011, IEEE C37.118.1a-2014 and IEC/IEEE 60255-118-1:2018 P-Class and M-Class performance compliance
Three-phase voltage, current, and positive and negative sequence phasor measurements synchronised to a common UTC time reference
IEEE C37.118.1 synchronous frequency and rate of change of frequency (ROCOF) measurements
Expected steady-state total vector error (TVE) below 0.05%
Time-stamped measurements including phasor estimates, frequency deviation from nominal or actual frequency, and ROCOF, sent in synchrophasor data frames
IEC 61850-9-2 sampled values
Streaming of phasor data over Ethernet using the IEC 61850-9-2 multicast sampled value (SV) service
IEEE C37.118.2 compliant mapping of synchrophasor data, based on IEC 61850-9-2 and IEC 61850-9-5 guidelines
IEC 61850 supported on both Ethernet ports alongside Modbus/TCP, DNP3/TCP and IEC 60870-5-104
Time synchronisation
Clock synchronisation to a UTC time reference using an IRIG-B timecode source or an IEEE 1588 PTPv2 master clock
1µs time stamp accuracy
Optically isolated IRIG-B port with B004/B005 timecode format
1pps time synchronisation available via the digital inputs
Built-in real-time clock with battery backup
IEEE C37.118.2 data streaming (advanced protocol support)
Commanded client-server UDP and TCP data transmission, plus spontaneous UDP data transmission over IP
Reporting rates from 1 to 200 or 240 frames per second at 50 or 60Hz respectively
Five data streaming slots for continuous synchrophasor streaming via unicast UDP and/or TCP connections
32-bit IEEE floating point or 16-bit scaled integer format, with conversion factors provided in configuration frames
Optional frame extensions with analogue data (total fundamental active, reactive and apparent power and displacement power factor) and digital status data for up to 32 inputs
Support for CFG-1, CFG-2 and CFG-3 configuration frames
In spontaneous UDP mode, CFG-2 or CFG-3 frames can be sent every 30 seconds without an explicit user command
Logging, recording and programming
Programmable controller with up to 32 control setpoints and half-cycle scan time
OR, AND and arithmetical logic functions, extensive triggers, programmable thresholds and delays, relay control and event-driven data recording
Event recorder for internal diagnostic events, power faults and operation of the logic controller and digital I/O
Eight data recorders with programmable datasets, logging periodically or on any internal or external trigger
32 digital counters for internal events and external pulses
16 interval timers from half a cycle to 24 hours for periodic recording and timed operations
16GB memory for long-term data recording
Measurement inputs
Voltage inputs: measurement category CAT III, operating range up to 277/480V AC +25%
Variable current inputs: 5A or 1A nominal, selected at order
Built-in power supply: 57.7 to 277V AC / 48 to 290V DC
Display
High contrast 1.77" TFT colour graphics display with configurable backlight
Multilanguage support
Two diagnostic LEDs and four push buttons
Built-in I/O
Two optically isolated digital inputs: 24V DC dry contact, programmable de-bounce from 1ms to 1s, control setpoints and 1pps time synchronisation, 1ms sampling
One solid state relay output: unlatched, latched and pulse operation, fail-safe alarm operation, programmable pulse width and direct remote control through communications
One optically isolated analogue input for 1mA to 20mA signals
Communications
RS-485 serial port up to 115,200 bps with Modbus RTU/ASCII and DNP3
IEC 61850-9-2 sampled values, with mapping based on IEC 61850-9-5 guidelines
IEEE 1588 PTPv2 and IRIG-B time synchronisation
Electromagnetic emission
Complies with IEC 61000-6-4: radiated and conducted, class A
Complies with CISPR 22: radiated and conducted, class A
Safety
Meets IEC 61010-1:2006
AC and impulse insulation
Meets AS/IEC 62052-11: 4,000V AC for 1 minute
6kV / 500Ω at 1.2/50µs impulse
Degree of protection: IP51
Ordering information
MODEL – CURRENT – CAL. FREQ. – POWER – I/O MODULES – AUX. POWER
Model
PMU PRO DIN rail mount phasor measurement unit
PMU PRO
Current inputs
5 ampere
5A
1 ampere
1A
Calibration frequency
50Hz
50HZ
60Hz
60HZ
Power supply
88 to 320V AC / 40 to 290V DC
ACDC
Optional I/O modules (max. 3 per device) and the auxiliary power supply module (max. 1 per device) complete the order string — see Expansion modules below.
Expansion modules
Optional I/O modules: max. 3 per device. Auxiliary power supply: max. 1 per device.
Optional I/O modules (max. 3 per device)
4 relay outputs, 250V / 5A AC
EMR4
4 SSR outputs, 250V / 0.1A AC
SSR4
4 digital inputs (dry contact at 24V DC) + 2 SSR outputs
4DIOS-DRC
4 digital inputs (dry contact at 24V DC) + 2 EMR outputs