PMU PRO · DATASHEET

PMU PRO phasor measurement unit datasheet

Advanced P-Class and M-Class phasor measurement unit for wide area monitoring.

Transcribed from the SATEC Australia datasheet TBV1.0, 28 September 2026 (PDF, 8 pages, 938 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PMU PRO is an advanced phasor measurement unit built for distribution network operators, utilities, substations and renewable generators that need precise, time-aligned visibility of their grid. It measures synchronised voltage and current phasors, frequency and rate of change of frequency to IEEE C37.118.1 P-Class and M-Class performance, then streams that data over Ethernet via IEEE C37.118.2 or IEC 61850-9-2 sampled values.

Based on the familiar PRO Series look and feel, it combines 1 to 240 frames per second reporting and 1µs time stamp accuracy with IRIG-B or IEEE 1588 PTPv2 time synchronisation. Dual port Ethernet, RS-485, USB-C, a 1.77" colour display, 16GB of log memory and up to four side-by-side expansion modules complete a compact DIN rail package.

Current input options

Main features

Feature capabilities

Phasor measurement (P-Class and M-Class)

  • IEEE C37.118.1-2011, IEEE C37.118.1a-2014 and IEC/IEEE 60255-118-1:2018 P-Class and M-Class performance compliance
  • Three-phase voltage, current, and positive and negative sequence phasor measurements synchronised to a common UTC time reference
  • IEEE C37.118.1 synchronous frequency and rate of change of frequency (ROCOF) measurements
  • Expected steady-state total vector error (TVE) below 0.05%
  • Time-stamped measurements including phasor estimates, frequency deviation from nominal or actual frequency, and ROCOF, sent in synchrophasor data frames

IEC 61850-9-2 sampled values

  • Streaming of phasor data over Ethernet using the IEC 61850-9-2 multicast sampled value (SV) service
  • IEEE C37.118.2 compliant mapping of synchrophasor data, based on IEC 61850-9-2 and IEC 61850-9-5 guidelines
  • IEC 61850 supported on both Ethernet ports alongside Modbus/TCP, DNP3/TCP and IEC 60870-5-104

Time synchronisation

  • Clock synchronisation to a UTC time reference using an IRIG-B timecode source or an IEEE 1588 PTPv2 master clock
  • 1µs time stamp accuracy
  • Optically isolated IRIG-B port with B004/B005 timecode format
  • 1pps time synchronisation available via the digital inputs
  • Built-in real-time clock with battery backup

IEEE C37.118.2 data streaming (advanced protocol support)

  • Commanded client-server UDP and TCP data transmission, plus spontaneous UDP data transmission over IP
  • Reporting rates from 1 to 200 or 240 frames per second at 50 or 60Hz respectively
  • Five data streaming slots for continuous synchrophasor streaming via unicast UDP and/or TCP connections
  • 32-bit IEEE floating point or 16-bit scaled integer format, with conversion factors provided in configuration frames
  • Optional frame extensions with analogue data (total fundamental active, reactive and apparent power and displacement power factor) and digital status data for up to 32 inputs
  • Support for CFG-1, CFG-2 and CFG-3 configuration frames
  • In spontaneous UDP mode, CFG-2 or CFG-3 frames can be sent every 30 seconds without an explicit user command

Logging, recording and programming

  • Programmable controller with up to 32 control setpoints and half-cycle scan time
  • OR, AND and arithmetical logic functions, extensive triggers, programmable thresholds and delays, relay control and event-driven data recording
  • Event recorder for internal diagnostic events, power faults and operation of the logic controller and digital I/O
  • Eight data recorders with programmable datasets, logging periodically or on any internal or external trigger
  • 32 digital counters for internal events and external pulses
  • 16 interval timers from half a cycle to 24 hours for periodic recording and timed operations
  • 16GB memory for long-term data recording

Measurement inputs

  • Voltage inputs: measurement category CAT III, operating range up to 277/480V AC +25%
  • Variable current inputs: 5A or 1A nominal, selected at order
  • Built-in power supply: 57.7 to 277V AC / 48 to 290V DC

Display

  • High contrast 1.77" TFT colour graphics display with configurable backlight
  • Multilanguage support
  • Two diagnostic LEDs and four push buttons

Built-in I/O

  • Two optically isolated digital inputs: 24V DC dry contact, programmable de-bounce from 1ms to 1s, control setpoints and 1pps time synchronisation, 1ms sampling
  • One solid state relay output: unlatched, latched and pulse operation, fail-safe alarm operation, programmable pulse width and direct remote control through communications
  • One optically isolated analogue input for 1mA to 20mA signals

Communications

  • RS-485 serial port up to 115,200 bps with Modbus RTU/ASCII and DNP3
  • Dual 10/100Base-T Ethernet ports supporting Modbus/TCP, DNP3/TCP, IEC 60870-5-104, IEC 61850, IEEE C37.118.2 and IEEE 1588 PTPv2
  • Up to 10 simultaneous non-intrusive Ethernet connections
  • USB 2.0 port (Type C)

Expansion modules (optional, ordered separately)

  • Up to four expansion modules fitted side by side
  • Up to two I/O modules are self-energised; a third I/O module requires an auxiliary power supply module
  • 8 DI: eight optically isolated digital inputs, dry contact or 24/48/125/250V DC wet inputs, 1ms sampling, pulse counting and 1pps time synchronisation
  • 4 RO: four electromechanical (EMR) or solid state (SSR) relay outputs with unlatched, latched, pulse and fail-safe operation
  • 4 DI + 2 RO combo module
  • 4 AO: four isolated universal analogue outputs configurable for ±1mA, 0 to 1mA, 0 to 5mA, ±5mA, 0 to 20mA or 4 to 20mA
  • Auxiliary power supply modules (88 to 264V AC / 90 to 290V DC, or 24V DC) power the whole device including up to three extra I/O modules

Software support

  • Power Analysis Software (PAS): free configuration and data acquisition tool for remote configuration and monitoring
  • Expertpower: SATEC web platform for energy data, alarms and reporting through the built-in Expertpower client
  • eXpertConnect™ App: mobile connection to the meter for configuration, readings and diagnostics

Applications

  • Suited to a wide range of grid and site monitoring applications.
  • Wide area monitoring
  • Power quality
  • Substation automation
  • Renewable energy
  • Energy management
  • Industrial monitoring
  • SCADA ready

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Voltage inputs
Measurement categoryCAT III
Operating range277/480V AC +25%
Input impedance4MΩ
Over-voltage withstand1,000V AC continuous; 2,000V AC for 1 second
Burden< 0.01VA at 120V; < 0.04VA at 400V
Isolation4,000V AC for 1 minute
Wire sizeUp to 10 AWG (4.5mm²)
Connector type4 pin, plug-in
Current inputs
Measurement categoryCAT III
Galvanic isolation4,000V AC for 1 minute
Wire sizeUp to 10 AWG (4.5mm²)
Current inputs: 5A input
Operating range10A RMS continuous
Burden< 0.2VA at 5A (10 AWG wire, 1m long)
Overload withstand15A RMS continuous; 200A RMS for ½ second (10 AWG wire)
Current inputs: 1A input
Operating range2A RMS continuous
Burden< 0.2VA at 1A (10 AWG wire, 1m long)
Overload withstand3A RMS continuous; 40A RMS for ½ second (10 AWG wire)
Power supply
Rated input57.7 to 277V AC at 50/60Hz; 48 to 290V DC
Tolerance±15%
Burden11VA AC; 6VA DC
Isolation4,000V AC for 1 minute
Wire sizeUp to 14 AWG (1.5mm²)
Auxiliary power supply (optional module): AC/DC module
Rated input88 to 264V AC / 90 to 290V DC
Output5W
Burden15VA
Withstand4kV AC for 1 minute
WiringL/+, N/-
Terminal pitch5mm
Wire sizeUp to 12 AWG (2.5mm²)
Auxiliary power supply (optional module): 24V DC module
Rated input9 to 36V DC
Output7W
Galvanic isolation4,000V AC for 1 minute
Terminal pitch5mm
Wire size14 AWG (up to 1.5mm²)
Built-in digital inputs (2 DI)
TypeDry contacts, internally wetted at 24V DC
Galvanic isolation4,000V AC for 1 minute
Internal power supply24V DC
Scan time1ms
Connector typeRemovable, 5 pin
Wire size14 AWG (up to 1.5mm²)
Terminal pitch5mm
Built-in digital output (1 DO)
TypeSolid state relay, 1 contact (SPST Form A)
Rating0.15A / 250V AC/DC
Galvanic isolation4,000V AC for 1 minute
Operate time1ms max.
Release time0.25ms max.
Update time1 cycle
Connector typeRemovable, 4 pin
Wire size14 AWG (up to 1.5mm²)
Built-in analogue input (1 AI)
TypeUniversal, -1mA to 20mA
Configurable ranges±1mA, 0 to 1mA, 0 to 20mA, 4 to 20mA
Accuracy< 0.5% FS
Galvanic isolation4,000V AC for 1 minute
Scan time1ms
Connector typeRemovable, 5 pin
Wire size14 AWG (up to 1.5mm²)
Terminal pitch5mm
Add-on digital inputs (8 DI)
TypeDry contacts, internally wetted at 24V DC, or wet contacts up to 250V DC
SensitivityOpen: input resistance > 100kΩ; Closed: input resistance < 100Ω
Galvanic isolation4,000V AC for 1 minute
Internal power supply24V DC
Scan time1ms
Connector typeRemovable, 2 × 5 pin
Wire size14 AWG (up to 1.5mm²)
Add-on digital outputs (4 DO): option 1, electromechanical relay, dry contact
Rating4 relays, 5A / 250V AC; 5A / 30V DC, 1 contact (SPST Form A)
Isolation, contacts to coil3,000V AC for 1 minute
Isolation, open contacts750V AC
Operate time10ms max.
Release time5ms max.
Wire size14 AWG (up to 1.5mm²)
Add-on digital outputs (4 DO): option 2, solid state relay, dry contact
Rating4 relays, 100mA / 800V AC, 1 contact (SPST Form A)
Isolation, contacts to coil5,000V AC for 1 minute
Isolation, open contacts800V peak
Operate time5ms max.
Release time5ms max.
Update time1 cycle
Wire size14 AWG (up to 1.5mm²)
Add-on combo module (4 DI + 2 RO)
SpecificationFour digital inputs and two relay outputs, as per the 8 DI and 4 DO modules above
Add-on analogue outputs (4 AO)
TypeUniversal (configurable) isolated analogue outputs
Scan time1ms
Ranges (manually or remotely programmed)±1mA, max. load 10kΩ (100% overload); 0 to 20mA, max. load 510Ω; 4 to 20mA, max. load 510Ω; 0 to 1mA, max. load 10kΩ (100% overload)
Accuracy0.5% FS
Wire size14 AWG (up to 1.5mm²)
Terminal pitch5mm
Communication ports: COM1 RS-485
TypeOptically isolated RS-485 port
Baud rate2,400 to 115,200 bps
Isolation4,000V AC for 1 minute
Supported protocolsModbus RTU, Modbus ASCII, DNP3
Connector type2 pin, plug-in
Wire sizeUp to 14 AWG (1.5mm²)
Communication ports: Ethernet (dual, 2 ports)
TypeTransformer-isolated 10/100Base-T, RJ45
Supported protocolsModbus/TCP (port 502), DNP3/TCP (port 20000), IEC 60870-5-104 (port 2404), IEC 61850 (port 102), IEEE C37.118.2, PTPv2 (IEEE 1588) time sync
Simultaneous connections10 (5 Modbus/TCP + 5 DNP3/TCP)
Isolation4,000V AC for 1 minute
Communication ports: USB port
TypeFull speed USB 2.0, Type C
Isolation4,000V AC for 1 minute
Supported protocolsModbus
Communication ports: IRIG-B port
TypeOptically isolated IRIG-B port
Timecode signalUnmodulated (pulse-width coded), 100pps
Signal level5V unbalanced
Timecode formatB004/B005
Isolation4,000V AC for 1 minute
Connector typePlug-in
Recommended cable50Ω low loss RG58A/U (Belden 8219 or equivalent)
Real-time clock
TypeBuilt-in real-time clock with battery backup
Accuracy, calibrated< 5ppm at 23°C
Battery typeCR1632 3V lithium button cell
Time retention5 years (typical)
Log memory and display
Log memory16GB for long-term data recording
Display1.77" colour TFT LCD, 128 × 160 pixels
Indicators2 diagnostic LEDs
Keypad4 push buttons
Environmental conditions
Operating temperature-25°C to +55°C (-13°F to 131°F)
No hardware failure-40°C to +70°C (-40°F to 158°F)
No display failure-20°C to +70°C (-4°F to 158°F)
Storage temperature-30°C to +85°C (-22°F to 185°F)
Humidity0 to 95% RH non-condensing
AltitudeUp to 2,000m above sea level
Degree of protectionIP51
Construction
MountingDIN rail
Dimensions (without expansion modules)89.5 × 72 × 90mm
Weight0.70kg (1.54lb)
Case enclosurePC/ABS plastic blend
Display bodyPC/ABS plastic blend
Front panelPC plastic
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
LabelsPolyester film (UL94-V0)

Standards compliance

Accuracy

  • IEEE C37.118.1-2011 and IEEE C37.118.1a-2014 P-Class and M-Class performance
  • IEC/IEEE 60255-118-1:2018 P-Class and M-Class performance

Electromagnetic immunity

  • Complies with IEC 61000-6-2
  • IEC 61000-4-2 level 3: electrostatic discharge
  • IEC 61000-4-3 level 3: radiated electromagnetic RF fields
  • IEC 61000-4-4 level 3: electric fast transient
  • IEC 61000-4-5 level 3: surge
  • IEC 61000-4-6 level 3: conducted radio frequency
  • IEC 61000-4-8: power frequency magnetic field
  • Meets ANSI/IEEE C37.90.1: fast transient SWC

Communication protocols

  • IEEE C37.118.2 synchrophasor data transfer
  • IEC 61850-9-2 sampled values, with mapping based on IEC 61850-9-5 guidelines
  • IEEE 1588 PTPv2 and IRIG-B time synchronisation

Electromagnetic emission

  • Complies with IEC 61000-6-4: radiated and conducted, class A
  • Complies with CISPR 22: radiated and conducted, class A

Safety

  • Meets IEC 61010-1:2006

AC and impulse insulation

  • Meets AS/IEC 62052-11: 4,000V AC for 1 minute
  • 6kV / 500Ω at 1.2/50µs impulse
  • Degree of protection: IP51

Ordering information

MODEL – CURRENT – CAL. FREQ. – POWER – I/O MODULES – AUX. POWER

Model
PMU PRO DIN rail mount phasor measurement unitPMU PRO
Current inputs
5 ampere5A
1 ampere1A
Calibration frequency
50Hz50HZ
60Hz60HZ
Power supply
88 to 320V AC / 40 to 290V DCACDC

Optional I/O modules (max. 3 per device) and the auxiliary power supply module (max. 1 per device) complete the order string — see Expansion modules below.

Expansion modules

Optional I/O modules: max. 3 per device. Auxiliary power supply: max. 1 per device.

Optional I/O modules (max. 3 per device)
4 relay outputs, 250V / 5A ACEMR4
4 SSR outputs, 250V / 0.1A ACSSR4
4 digital inputs (dry contact at 24V DC) + 2 SSR outputs4DIOS-DRC
4 digital inputs (dry contact at 24V DC) + 2 EMR outputs4DIOR-DRC
8 digital inputs, dry contactDI8-DRC
8 digital inputs, 24, 48, 125 or 250V DC wetDI8-24/48/125/250
4 analogue outputs, configurable range4AO
Auxiliary power supply (max. 1 per device)
AC/DC, 88 to 264V AC / 90 to 290V DCAUX-ACDC
24V DC (9 to 36V DC)AUX-24DC

Downloads and related