PMU PRO · IDENTIFY

What should I identify before selecting or installing a PMU PRO?

PMU PRO product illustration
PMU PRO product illustration; confirm the installed ordering code and options.

Quick answer

The PMU PRO order string covers the current inputs (5 A or 1 A), the calibration frequency (50 Hz or 60 Hz), the power supply, up to three optional I/O modules and up to one auxiliary power supply. Before connecting the instrument to the power source, the manual says to check the labels on its front and side to ensure it has the appropriate power supply, voltage inputs and current inputs. The clock must be synchronised to UTC from an IRIG-B timecode source or an IEEE 1588 PTPv2 master clock, and each choice limits other ports or network layouts. SATEC Australia's advice: decide the time source before ordering or wiring.

Applies to

This page covers the PMU PRO Phasor Measurement Unit, a DIN rail mounted unit described in the PMU PRO Installation and Operation Manual, BG0649 Rev. A1. The manual lists separate PMU PRO protocol reference guides, BG0650 to BG0655. SATEC Australia's advice: don't use the PM180 PMU module instructions or the PRO series meter manuals for the PMU PRO.

The order-string fields

The SATEC Australia datasheet lists these fields:

FieldOrder codes listed
ModelPMU PRO
Current inputs5A, 1A
Calibration frequency50HZ, 60HZ
Power supplyACDC
Optional I/O modules (max. 3 per device)EMR4, SSR4, 4DIOS-DRC, 4DIOR-DRC, DI8-DRC, DI8-24/48/125/250, 4AO
Auxiliary power supply (max. 1 per device)AUX-ACDC, AUX-24DC

At a 50 Hz system frequency the manual lists reporting rates of 1, 2, 5, 10, 25, 50, 100 and 200 frames/s. The 60 Hz list runs to 240 frames/s.

Check the labels before wiring

Before connecting the instrument to the power source, the manual says to check the labels on the front and side of the instrument to ensure that it is equipped with the appropriate power supply, voltage inputs and current inputs. It also says that under no circumstances should the instrument be connected to a power source if it is damaged.

The manual and the datasheet state the main supply range, the auxiliary supply range and the module list differently. SATEC Australia's advice: don't apply a rating from either document to a unit without checking its label, and contact SATEC Australia support before wiring if the label doesn't match the documents you are using.

Where to find the serial number and firmware

  • Front display: the Monitor menu includes Device Info. The manual says these screens provide information about the device serial number and firmware versions, as well as detailed information about communication port settings.
  • PAS: with the On-line icon checked, open the site tree pane, right-click the device's site name and select Properties. The manual says the Properties window provides information about the device's factory settings and device firmware.

SATEC Australia's advice: record the serial number and firmware versions before commissioning or asking for support.

Choices that change the installation

IRIG-B and RS-485. The manual says the RS-485 port shares input circuitry with the IRIG-B port, so only one of them can be used at a time.

PTP and daisy chaining. The two Ethernet ports can be daisy-chained to a switch in a linear or ring topology. The manual says daisy chaining is not available for PTP-enabled devices: only one of them, directly connected to the 1588 switch, can have PTP synchronization enabled, and only using a linear topology. For PTP, the Ethernet port must be connected to an IEEE 1588 grandmaster clock through a 1588 PTPv2 peer-to-peer transparent clock switch.

Expansion modules. The manual says up to 2 expansion modules can be normally connected without overloading the device power supply, and connecting the third expansion module requires the auxiliary power supply.

Current inputs. The manual gives separate current input ratings for 5A secondary and 1A secondary inputs.

Safety before installation

The manual says to ensure that all incoming power sources are turned off before installation. It also says the secondary of an external current transformer must never be allowed to be open circuit when the primary is energized. SATEC Australia's advice: installation is work for a qualified person following the site's isolation procedure.

What to send SATEC Australia

SATEC Australia's advice: if you are unsure which variant you have or need, send:

  1. a clear photo of the front and side labels;
  2. the order code, if known;
  3. the serial number and firmware versions from Device Info;
  4. the planned time source (IRIG-B or PTP) and whether RS-485 is needed;
  5. the CT secondary rating and network frequency.

Contact SATEC Australia technical support through our contact form.

Manuals and source pages

  • PMU PRO Installation and Operation Manual, BG0649 Rev. A1, June 2024. Printed page numbers match the PDF pages. Labels and safety, page 13; module power, page 16; ports, pages 16–19; time source, pages 22–23; reporting rates, page 24; Device Info, pages 40 and 43; PAS properties, page 84. Open the manual in a new tab.