PMU PRO · SUPPORT RECORDS
What PMU PRO status and recorded data should I collect for support?

Quick answer
SATEC Australia's advice: before anyone resets, clears or reconfigures the unit, record what it is showing and keep copies of its records. The PMU PRO shows its status on a green device status LED, a red clock LED and icons and messages in the display status bar. PAS can upload the device settings to the site database and retrieve the event and data log files to a database on the PC.
Applies to
This page covers the PMU PRO Phasor Measurement Unit and its Installation and Operation Manual, BG0649 Rev. A1. SATEC Australia's advice: don't use it for the PM180 PMU module or the PRO series meters.
1. Read the front panel
The green device status LED flashes at 2 second intervals:
| Status | Description |
|---|---|
| Flashes once | The device is operational and works normally |
| Flashes twice | Device is in boot mode. This is normal when updating the device firmware. In other cases, it indicates missing or corrupted application firmware and requires user intervention to resolve the issue. |
| Flashes 3 times | Indicates a critical error, such as corruption of basic operating settings or a malfunction of the device clock, that requires user intervention and correction |
Table from BG0649, page 33.
The manual says the red warning LED flashes once a second when the PMU clock is not synchronized with the UTC time source, and turns off once the clock is synced to UTC time.
The status bar shows clock synchronisation as a coloured message:
| Message | Description |
|---|---|
| Testing | The device is trying to detect a signal from a UTC time source. When using a 1588 PTP time source, it can take up to a minute to calibrate and synchronize the device clock with the PTP master clock. |
| Locked | The device clock is locked to UTC time |
| Unlocked | The UTC time source previously synchronized to a GPS primary reference is now free-running based on its own internal oscillator. It is said to be in the holdover mode, as long as it is within its accuracy requirements. |
| Failure | The device has lost a signal from a UTC time source or the UTC master clock has lost a GPS signal |
Table from BG0649, page 34.
A diagnostic icon appears in the status bar whenever diagnostic messages occur. The manual says a black battery icon outlined by orange indicates that the lithium battery voltage is below the operating limit, and that the battery should be checked and replaced. This page doesn't give a battery replacement procedure.
SATEC Australia's advice: write down the LED patterns, the clock message and any icons shown.
2. Record the clock detail
The Monitor > Clock Status screen provides more detailed information about the device clock synchronisation and current time quality. The manual says that for the IRIG-B time source, no time error is reported.
With PTP, both Ethernet ports can be connected to the same or two different 1588 switches, and the device switches automatically to the other port whenever the signal is lost. The manual describes Telnet "time" and "ptp" commands for checking clock status and time accuracy. Telnet access requires at least level 2 password authorisation.
SATEC Australia's advice: note the time source in use and, for PTP, how each Ethernet port is connected.
3. Write down the diagnostics before clearing anything
All diagnostic events with time stamps are recorded in the device event log and can be inspected through the front display Events menu and through PAS. These diagnostic messages from Appendix E are among those relevant to timing and records:
| Diagnostic Code | Description | Reason |
|---|---|---|
| 8 | Power Down | Loss of power |
| 9 | Device reset | External restart via communications or in case of firmware upgrade |
| 10 | Configuration Reset | Corrupted setup data has been replaced with the default configuration |
| 11 | RTC Fault | The clock time has been lost. With auto-reset: cleared automatically once the clock is updated. |
| 12 | Configuration Fault | Factory, calibration or basic device configuration data has been corrupted |
| 13 | Battery Low | Low lithium battery. With auto-reset. Battery check or replacement is required. |
| 24 | IRIG-B/PTP: No Signal | The device has lost a signal from a UTC time source |
| 25 | IRIG-B/PTP: Time Unlocked | The UTC time source previously synchronized to a GPS primary reference is now free-running (holdover mode) based on its own internal oscillator |
Excerpt from BG0649, page 114.
In the event of a configuration reset, the manual says to check the affected settings through the device event log, and then verify the setup data. SATEC Australia's advice: photograph or write down the codes before anyone clears them.
4. Save the configuration in PAS
The manual's batch upload uploads all settings from the device to the device site database: check the On-line icon, select the device site, then select Upload Setups from the Meter Setup menu. Individual Download and Batch Download, using Send or Download Setups, update settings in the device.
SATEC Australia's advice: keep the uploaded site database unchanged as the as-found record.
5. Upload the logs
To retrieve recorded files on demand, the manual gives these steps:
- Select a device site from the list box on the PAS toolbar.
- Make sure the On-line icon on the PAS toolbar is checked.
- Click the Upload Log Files icon on the PAS toolbar or select Upload Logs from the Logs menu.
- Select a database or enter a name for the new database, and select the folder where you want to save it.
- Click "Select Logs" and check the boxes for the files you want to retrieve from the device.
- To retrieve data starting with a known date, check the "From" box and select the start date for retrieving data.
- To retrieve data recorded before a known date, check the "To" box and select the latest date to retrieve data.
- Click OK.
The manual says not to store data files in the "Sites" folder where site databases are located. Viewing a log online retrieves only new records that have not yet been read through this communication port. SATEC Australia's advice: use Upload Logs, not the online view, for the copy you send.
How far back the logs go
Each log file can contain up to 65535 records. When a file is full, recording stops until the file is cleared (non-wrap mode) or continues over old records (wrap-around mode). The eight data recorders record on a periodic basis and on any internal or external trigger, triggered via the logic controller. File sizes are set in the Memory/Log setup, on the Log Memory tab. SATEC Australia's advice: work out how far back a file reaches from its allocated records and how often it actually records, because the manual's recorder chapters give no single log retention figure.
Don't clear or change anything yet
The manual describes clearing device diagnostics, clearing counters, clearing the event log, clearing data logs, Clear All Files, and firmware update, after which the device reboots. SATEC Australia's advice: treat each of these, and any change to clock, time-source or network settings, as a separate authorised action taken only after the records above are kept.
What to send SATEC Australia
SATEC Australia's advice: send:
- the serial number and firmware versions from Device Info;
- the green LED pattern, red clock LED state and status-bar clock message;
- a photo or list of the diagnostic codes;
- the time source (IRIG-B or PTP), and for PTP the switch arrangement;
- the uploaded site database and the log database;
- when the problem started, and any power, network or setting changes around that time.
Contact SATEC Australia technical support through our contact form.
Manuals and source pages
- PMU PRO Installation and Operation Manual, BG0649 Rev. A1, June 2024. Printed page numbers match the PDF pages. Diagnostics and battery, page 21; time synchronisation, pages 22–23; recorders, page 26; Telnet, pages 27–28; LEDs and status bar, pages 33–34; clock status and device information, page 43; events menu, page 44; recorder setup, pages 68–70; clearing and firmware update, pages 73–77; upload setups, pages 83–84; log retrieval, pages 88–94; diagnostic messages, page 114. Open the manual in a new tab.
Source review: 22 November 2026.