High Performance Power Quality Analyser with PMU and Fault Recording.
Transcribed from the SATEC Australia datasheet TBV1.0, 29 September 2026 (PDF, 8 pages, 2518 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The PM180 is a multi-microprocessor power quality analyser that combines a Class A power quality analyser, a Class 0.2S energy meter, a digital fault recorder, a phasor measurement unit and a programmable bay controller in one instrument. It is designed for substation and industrial automation, where one IED can replace several separate devices and save cost, panel space and wiring.
Four voltage inputs (the fourth AC/DC) and four current inputs are standard. Three hot-swap expansion slots take transient recorder, fault recorder, PMU, digital input, relay, analogue I/O, communication and auxiliary power supply modules. Built-in RS-485, Ethernet, USB and IRIG-B ports support Modbus, DNP3, IEC 60870-5-101/104 and optional IEC 61850.
Main features
Power quality to IEC 61000-4-30 Class A, Edition 3
Active energy Class 0.2S per AS/IEC 62053-22
Harmonics and interharmonics to the 63rd order
EN 50160 and IEEE 1159 statistics and reports
Disturbance direction detection for sags and swells
Fast transient recorder up to 2 kV at 1024 samples per cycle
Digital fault recorder for currents up to 200 A (40 x In)
Distance to fault calculation
IEEE C37.118.1 M-Class and P-Class PMU
IEC 61850 Edition 2 with GOOSE messaging
Bay controller for 2 circuit breakers and 14 switches
256 MB memory with 3.5 min of continuous waveform recording
Feature capabilities
Versions
PM180-X: Transducer version with no display. Includes a DIN rail mounting kit.
PM180-G: PM180 with a 5.7" colour graphic touch screen display (RGM180).
PM180-D: PM180 with a 3-line ultra-bright LED display (RDM180).
Multi-function power and energy meter
Real-time cycle-by-cycle true RMS voltage, current, power, power factor, demand and energy
Class 0.2S active energy per AS/IEC 62053-22 and Class 0.2 per ANSI C12.20
Class 0.5S reactive energy per IEC 62053-24
Time of Use with 16 energy sources including external pulse inputs, 4 seasons, 4 daily profiles and 8 tariff changes per day
KYZ or KY pulse output and a calibration LED (via the optional display)
Power quality
Analysis in full compliance with IEC 61000-4-30 Class A, Edition 3 (2015)
Sags, swells, interruptions, frequency and voltage variations
Flicker per IEC 61000-4-15 and voltage unbalance
Individual voltage and current harmonics per IEC 61000-4-7, interharmonics and directional power harmonics (load or source) to the 63rd
Voltage and current THD, current TDD, K-factors and V-I angles
Vector diagram and symmetrical components; frequency to 3 decimal places
Built-in statistics and reports per EN 50160 and IEEE 1159
Disturbance direction detection showing whether sags and swells come from upstream or downstream
Programmable thresholds and hysteresis
Optional redundant auxiliary power supply to capture major dips and interruptions
Distance to fault calculation
Compensation for CT and PT errors, for an average accuracy of 0.5%
Single lines, parallel lines, partially parallel lines and lines with a branch
Detects three-phase, two-phase, two-phase to ground and single-phase to ground short circuits, and single-phase open wire
Reports fault classification, distance to fault (km) and fault duration
Digital fault recorder (DFR module for 200 A fault currents)
Direct reading of fault currents up to 200 A (40 x In from the CT secondary)
Dual current inputs for separate metering and protection CT connections (optional)
Programmable fault threshold and hysteresis
Zero-sequence currents and voltages, unbalance, undervoltage and neutral current
Ready-to-use fault reports with fault current magnitude and duration, coincident voltage magnitude, waveforms and RMS trace
Selectable pre-fault and post-fault recording length, triggered by any internal or external condition
Disturbance capture and waveforms from multiple locations
View faults and receive alerts in Expertpower
Phasor measurement unit (PMU module)
IEEE C37.118.1 M-Class and P-Class
Three-phase voltage and current phasors synchronised to a common UTC time reference
Synchronous frequency and rate of change of frequency (ROCOF)
Expected steady-state total vector error (TVE) below 0.5%
Streaming from 1 to 50 or 60 frames per second at 50 or 60 Hz
IEEE C37.118.2 commanded client-server UDP and TCP and spontaneous UDP transmission
Optional frame extensions with total power, power factor and digital status data
Phasor streaming via the IEC 61850-9-2 sampled value (SV) service
PTP (IEEE 1588) time synchronisation; includes the transient recorder
Fast transient recorder (TRM-180 or PMU module)
Records voltage transients up to 2 kV (line to ground) at 1024 samples per cycle per channel
Four voltage channels with 10 MΩ high-impedance inputs
Bay controller (BCU)
Monitoring and control of 2 circuit breakers and 14 circuit switches
One-pole and three-pole switch position monitoring using two or six contacts
Select-close and select-open outputs for secure switching, with configurable command pulse duration
Supervision of command execution and reporting on operation termination
Interlocking logic with secure timed-out interlocking bypass
Indication of non-controllable breaker trips and switch position substitution
Counting and logging of breaker and switch operations
PLC configurator based on IEC 61131-3 using Function Block Diagram or Ladder Diagram
% reading 0.3; % FS 0.002; conditions |PF| ≤ 0.9; range ±2,000,000 kvar
Apparent power
% reading 0.2; % FS 0.002; conditions |PF| ≥ 0.5; range 0 to 2,000,000 kVA
Power factor
% reading 0.35; conditions |PF| ≥ 0.5, I ≥ 2% FSI; range -0.999 to +1.000
Frequency
% reading 0.002; conditions 40 to 70 Hz; range 40.000 to 70.000 Hz
Voltage and current THD
% reading 1.5; % FS 0.2; conditions THD ≥ 1% FS; range 0 to 999.9%
Active energy
Class 0.2S per AS/IEC 62053-22; range 0 to 999,999.999 MWh
Reactive energy
Class 0.5S per IEC 62053-24; range 0 to 999,999.999 Mvarh
Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit, calculated at 1 second average. It does not include errors introduced by external potential and current transformers. Printed as a five-column table (parameter, % reading, % FS, conditions, range); blank cells are left out.
Standards compliance
Accuracy
Active energy: Class 0.2S per AS/IEC 62053-22
Active energy: Class 0.2 per ANSI C12.20
Reactive energy: Class 0.5S under conditions per IEC 62053-24:2014 @ 0 ≤ |PF| ≤ 0.9
Power quality
IEC 61000-4-30 Class A, Edition 3: power quality measurement methods
IEC 61000-4-7: harmonics and interharmonics measurement
IEC 61000-4-15: flicker measurement
EN 50160: power quality in European electricity supply networks