PM180 · OPTIONS
Which PM180 display and options are fitted or required?

Quick answer
The PM180 order string covers the display, voltage inputs, current inputs, calibration frequency, accuracy and power quality standard, main power supply and communication standard, plus optional plug-in modules, with a maximum of three modules per unit. SATEC Australia's advice: don't assume options are fitted from the model name or a brochure; confirm them from the unit's labels, the modules in its slots and its firmware version. Several modules need a minimum firmware version, and the PMU module also needs a particular CPU board. The Installation Manual and the manufacturer's datasheet give different conditions for the PMU module. SATEC Australia's advice: check with SATEC Australia before ordering a PMU retrofit.
Applies to
This page covers the PM180 described in the PM180 Installation Manual, BG0521 Rev. A10, and the PM180 Operation Manual, BG0525 Rev. A7. SATEC Australia's advice: don't use it for the portable EDL180 or the PMU PRO.
Display choices
The SATEC Australia datasheet lists these display options:
| Display | Code |
|---|---|
| Transducer version, no display. Includes DIN rail mounting kit | X |
| Graphic colour display, 5.7" touch screen | G |
| Graphic colour display, 5.7" touch screen with DIN rail mounting kit and 3 m remote cable | G-DIN |
| 3-line ultra-bright LED display | D |
| 3-line ultra-bright LED display with DIN rail mounting kit and 3 m remote cable | D-DIN |
From the SATEC Australia PM180 datasheet, page 7.
The Installation Manual's specifications list the RDM180 under the PM180-D model, the RDM312 under the PM180-M model, and the RGM180 5.7 inch touch-panel LCD under the PM180-G model. The RDM312 is not listed in the current datasheet's display options.
The overall dimensions are 220.00 mm wide, 152 mm high and 210.00 mm deep. The Installation Manual has separate figures for dimensions, panel mounting and DIN rail mounting. SATEC Australia's advice: use the drawing for the display and mounting you have chosen, not the overall dimensions, to plan the panel.
The other order-string fields
The datasheet lists these further fields:
- Voltage inputs: 690V AC nominal voltage input (-) or 120V AC nominal voltage input (U).
- Current inputs: 5, 1, CS1S, CS1H, HACS or FLEX.
- Calibration frequency: 50Hz or 60Hz.
- Accuracy and power quality standard: E (with EN 50160 full power quality), A (with IEEE 1159 full power quality) or G (GOST 13109 / GOST 54149).
- Power supply (main): ACDC.
- Communication standard: default (-) or default plus IEC 61850 (SISCO) (850).
The Installation Manual and the datasheet state the main power supply range differently. SATEC Australia's advice: check the unit's labels before wiring, and contact SATEC Australia support if a rating in the documents doesn't match the label.
How to tell what is fitted
The PM180 provides a total of 6 module slots: 3 fixed slots for the voltages, CPU and currents factory installed modules, and 3 general purpose field installable "hot swap" slots (#1, #2 and #3) for input/output, measurement and communication optional modules. The Installation Manual's Figure 2-25, Location of Modules, shows the layout.
The Operation Manual says to use these firmware references to check your device's options:
- V31.X4.XX - Basic fault + IEEE 1159 power quality recorder + IEC 61000-4-15 flicker
- V31.X5.XX - Basic fault + EN 50160 power quality recorder
- V31.X7.XX Basic Fault + GOST13109-97 + Flicker IEC 61000-4-15 + Harmonics IEC 61000-4-7
- V31.X8.XX Basic Fault + GOST 32144-2013 + Flicker IEC 61000-4-15 + Harmonics IEC 61000-4-7
- V31.1X.XX +IEC 61850 server option
From BG0525, printed page 11. Its footnote adds that from firmware version V31.X5.28, EN 50160 is user selectable, whether EN 50160:2007 or EN 50160:2010.
The Telnet command list includes "I - Display firmware information". SATEC Australia's advice: also check the modules and labels, because a firmware reference alone doesn't show which modules are fitted.
Module placement rules
The Installation Manual sets these restrictions:
| Module | Restriction in BG0521 Rev. A10 | Supported from firmware version |
|---|---|---|
| TXFX | Only one; must be plugged in at the first optional slot right after the CPU module | V31.XX.8 |
| CELLULAR | Only one; must be plugged in at the first optional slot right after the CPU module | V31.XX.15 |
| TRM | Only one; can be plugged in any optional slot (slot 1, 2 or 3) right after the CPU module | V31.XX.10 |
| DFR | Only one; can be plugged in at any optional slot (slot 1, 2 or 3) right after the CPU module | V31.XX.11 |
| PMU | Only one; only can function with PM180 N3 with new CPU board (AP1451 - with built-in IRIG-B input); can be plugged in any free slot | V31.XX.29 |
| 8DI/4RO | Up to three; whenever 16DI and 8DI/4RO modules are used in the same installation, the 16DI modules should be placed into lower slots before any 8DI/4RO module | V31.XX.28 |
If two or more communication modules are plugged in the PM180, only one COM2 port will be active.
The manufacturer's July 2024 datasheet says the PMU should be assembled on a unit with minimum version N3 and minimum firmware version v31.x.38, and must be housed next to the current module only. That differs from the Installation Manual's firmware version and slot rule above. SATEC Australia's advice: don't plan a PMU retrofit or move a PMU module until SATEC Australia has checked the exact unit.
Module limits in the order string
The datasheet allows a maximum of three plug-in modules per unit. It also lists per-type maximums: one PMU, one transient recorder, one fault recorder, 48 digital inputs, 24 relay outputs, 12 analogue inputs and 12 analogue outputs, and one auxiliary power supply. SATEC Australia's advice: treat these as separate limits; with only three slots, not all of them can be reached at once.
What to send SATEC Australia
SATEC Australia's advice: send:
- photos of the labels and of the module slot area, showing each module's markings;
- the order code, if known;
- the firmware version;
- the display type and how it is mounted;
- what you want to add or change, and why.
Contact SATEC Australia technical support through our contact form.
Manuals and source pages
- PM180 Installation Manual, BG0521 Rev. A10, June 2025. Displays, printed pages 2–3 / PDF pages 6–7; mounting drawings, printed pages 4–5 / PDF pages 8–9; modules, printed pages 13–20 / PDF pages 17–24; slot layout, printed page 21 / PDF page 25; dimensions, printed page 28 / PDF page 32; display models, printed page 33 / PDF page 37. Open the manual in a new tab.
- PM180 Operation Manual, BG0525 Rev. A7, April 2019. Firmware references, printed page 11 / PDF page 12; Telnet commands, printed page 47 / PDF page 48. Open the manual in a new tab.
- PM180 Power Quality Analyser Datasheet, SATEC Australia TBV1.0, 29 September 2026: ordering information, pages 7–8. Open the datasheet in a new tab.
- PM180 Datasheet, SATEC Ltd, July 2024: PMU module note, page 9. Open the datasheet in a new tab.
Source review: 22 November 2026.