PM175 · DATASHEET

PM175 power quality analyser datasheet (TFT display)

Power Quality Analyser with 5.7" Touch Screen Colour Display.

Transcribed from the SATEC Australia datasheet TBV1.0, 29 September 2026 (PDF, 6 pages, 2860 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PM175 is a compact multifunction three-phase AC power meter and power quality analyser. It is designed for users ranging from electrical panel builders to substation operators who need revenue-grade energy data and EN 50160 power quality reporting in one instrument.

Users can choose a bright 3-row LED display or a 5.7" colour graphic touch screen. The display module is detachable and can be mounted up to 1000 m from the meter. Two communication ports support local and remote meter reading and setup over serial, Ethernet (TCP/IP) and Profibus.

PM175: Power quality analyser with a bright 3-row LED display.

PM175-TFT: PM175 with a 5.7" colour graphic touch screen display.

RPM075: Transducer version without a local display.

Main features

Feature capabilities

Measurements

  • 3 voltage and 3 current transformer-isolated AC inputs for direct connection or via PTs and CTs
  • True RMS volts, amps, power, power factor and frequency
  • Neutral current plus voltage and current unbalance
  • Ampere, volt, THD and TDD demand meter
  • Class 0.2S accuracy (1A and 5A versions)

Energy and Time-of-Use

  • 8 tariff energy/demand registers x 8 tariffs
  • 4 seasons x 4 types of day with 8 tariff changes per day
  • Easily programmable tariff schedule
  • Automatic daily profile of energy and maximum demand readings for total and tariff registers

Power quality recorder

  • EN 50160 power quality recorder (GOST 13109 or GOST 54149 also selectable)
  • Compliance statistics and EN 50160 harmonics survey statistics
  • Onboard power quality analyser with programmable thresholds and hysteresis
  • Ready-to-use reports

Harmonic analyser

  • Embedded harmonic analyser
  • Voltage and current THD, current TDD and K-factor
  • Voltage and current harmonic spectrum and angles up to the 50th order
  • Inter-harmonics THD

Waveform recording

  • Two waveform recorders with simultaneous 6-channel AC recording in a single plot
  • Sampling rates of 32, 64 and 128 samples per cycle
  • 20 pre-fault cycles
  • Up to 30 seconds of continuous recording at 32 samples per cycle
  • Real-time waveform capture and monitoring: 6 channels, 4 cycles at 128 samples per cycle

Logging and memory

  • Event recorder for internal diagnostics, control events and I/O operations
  • 16 data recorders with programmable logs on a periodic basis or on any internal or external trigger
  • 1 MB RAM with battery backup for long-term data and waveform recording
  • Precise internal clock with battery backup

Embedded controller

  • 16 control setpoints
  • Programmable thresholds and delays
  • Relay output control
  • 1/2-cycle response time

Inputs and outputs

  • 2 standard plus 2 optional digital inputs for external contacts and pulses from energy, water and gas meters
  • 2 standard plus 2 optional relay outputs for alarms, control and energy pulses
  • 2 optional optically isolated analogue outputs with internal power supply
  • 2 optional optically isolated analogue inputs with internal power supply
  • Optional analogue expander with an additional 2 x 8 analogue outputs

Display options: one or two displays per meter

  • Detachable display module with a 3-wire RS-485 interface, up to 1000 m from the meter
  • LED: bright 3-row display (2 x 4 characters + 1 x 6 characters) with adjustable update time, auto-scroll, auto-return to a default page and a percent-load LED bar graph
  • TFT: 5.7" colour graphic touch screen with easy-to-read screens for monitoring complex information at a glance
  • Touch screen operation keeps setup and configuration simple

Communications

  • Two independent communication ports
  • COM1: RS-232/RS-422/RS-485, Ethernet 10/100BaseT (Expertpower enabled) or Profibus DP
  • COM2: RS-422/RS-485
  • Modbus RTU, Modbus ASCII and Modbus/TCP
  • DNP3 and DNP3/TCP (Level 1 Rev. 2.3)
  • Full speed USB port on the PM175-TFT display

Security and firmware

  • Password security for setup parameters and resets via the front panel and communications
  • Tampering attempts recorded to the device event log
  • Easy field upgrade of device firmware through any communication port

Software support

  • PAS Power Analysis Software for setup, data retrieval and analysis
  • Expertpower web platform via the Ethernet port
  • eXpertConnect™ App for mobile access to energy data
  • MV90xi compatible

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Environmental conditions
Operating temperature-20°C to +60°C (-4°F to 140°F)
Storage temperature-25°C to +80°C (-13°F to 176°F)
Humidity0 to 95% RH non-condensing
Construction
Weight1.23 kg (2.7 lb)
Dimensions (HxWxD)127 x 127 x 143 mm (5 x 5 x 5.6")
Power supply
120/230V AC, 110/220V DC optionRated input 85-264V AC 50/60 Hz, 88-290V DC, burden 10W
IsolationInput to output 3000V AC, input to ground 2000V AC
12V DC optionRated input 9.6-19V DC
24V DC optionRated input 19-37V DC
48V DC optionRated input 37-72V DC
Wire sizeUp to 12 AWG (up to 3.5 mm²)
Materials
Case enclosurePlastic PC/ABS blend
Display bodyPlastic PC/ABS blend
Front panelPlastic PC
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
Packaging caseCarton and Stratocell® (polyethylene foam) brackets
LabelsPolyester film (UL94-V0)
Real-time clock
AccuracyTypical error 30 seconds per month at 25°C
Log memory
Onboard memory1 MB with battery backup
Voltage inputs
Operating range690V AC L-L, 400V AC L-N
Direct input and input via PTUp to 828V AC line-to-line, up to 480V AC line-to-neutral
Input impedance1 MΩ
Burden for 400V<0.4 VA
Burden for 120V<0.04 VA
Overvoltage withstand1kV AC continuous, 2kV AC for 1 second
Galvanic isolation3500V AC
Wire sizeUp to 12 AWG (up to 3.5 mm²)
Current inputs
Operating range5A: continuous 10A RMS, burden <0.1 VA; 1A: continuous 2A RMS, burden <0.02 VA
Overload withstand5A: continuous 15A RMS, 300A for 1 second; 1A: continuous 6A RMS, 80A for 1 second
Galvanic isolation3500V AC
Wire size12 AWG (up to 3.5 mm²)
Relay outputs
Relays2 relays rated 3A/250V AC and 3A/30V DC, 2 contacts (SPST Form A)
Galvanic isolationBetween contacts and coil 2000V AC for 1 minute, between open contacts 1000V AC
Operate time10 ms max.
Release time5 ms max.
Update time1 cycle
Wire size14 AWG (up to 1.5 mm²)
Digital inputs
Inputs2 digital inputs, dry contacts
Galvanic isolation2000V RMS
Internal power supply15V
Scan time1 ms
Wire size14 AWG (up to 1.5 mm²)
Optional analogue inputs
Inputs2 analogue inputs (optically isolated)
Ranges (upon order)±1 mA (100% overload), 0-1 mA (100% overload), 0-20 mA, 4-20 mA
Isolation2000V RMS
Accuracy0.5% FS
Scan time1 cycle
Wire size14 AWG (up to 1.5 mm²)
Optional analogue outputs
Outputs2 analogue outputs (optically isolated)
Ranges (upon order)0-20 mA and 4-20 mA, max. load 510 Ω; ±1 mA and 0-1 mA, max. load 5 kΩ (100% overload); ±5 mA and 0-5 mA, max. load 5 kΩ
Isolation2000V RMS
Power supplyInternal
Accuracy0.5% FS
Update time1 cycle
Wire size14 AWG (up to 1.5 mm²)
LED display module
DisplayHigh-brightness seven-segment digital LEDs, two 4-digit and one 6-digit windows
Keypad6 push buttons
CommunicationEIA RS-485 port with 12V supply voltage
Connector typeDB15, 15 pins
Wire sizeUp to 14 AWG (up to 1.5 mm²)
DistanceUp to 1000 m (3200 ft)
COM1: RS-232 port (optional module)
PortSerial EIA RS-232, optically isolated
Isolation2000V RMS
Connector typeDB9 female
Baud rateUp to 115.2 kbps
Supported protocolsModbus RTU, Modbus ASCII, DNP3 (firmware V25.2.01 and later)
COM1: RS-422/RS-485 port (optional module)
PortRS-422/RS-485, optically isolated
Isolation2000V RMS
Connector typeDB9 female
Baud rateUp to 115.2 kbps
Supported protocolsModbus RTU, Modbus ASCII, DNP3 (firmware V25.2.01 and later)
COM1: Ethernet port (optional module)
PortTransformer-isolated 10/100BaseT Ethernet
Connector typeRJ45 modular
Supported protocolsModbus/TCP on port 502, DNP3/TCP on port 20000 (firmware V25.2.01 and later)
Simultaneous connections4 (4 Modbus/TCP or 2 Modbus/TCP + 2 DNP3/TCP)
COM2
PortRS-422/RS-485, optically isolated
Isolation2000V RMS
Connector typeRemovable, 5 pins
Wire sizeUp to 14 AWG (up to 1.5 mm²)
Baud rateUp to 115.2 kbps
Supported protocolsModbus RTU, Modbus ASCII, DNP3 (firmware V25.2.01 and later)
TFT display module
Display5.7" colour graphic touch screen
USBFull speed USB port
DistanceUp to 1000 m from the meter

Standards compliance

Accuracy

  • Class 0.2S per AS/IEC 62053-22 (1A and 5A versions)

Emission

  • EN 55011:1991
  • EN 55022:1994 Class A
  • EN 50081-2 Generic Emission Standard, Industrial Environment

Immunity

  • EN 50082-1:1992
  • EN 50082-2 Generic Immunity Standard, Industrial Environment
  • EN 61000-4-2, EN 61000-4-4:1995, EN 61000-4-8:1993
  • ENV 50140:1983, ENV 50141:1993, ENV 50204:1995 (900 MHz)

Safety

  • EN 61010-1:1993/A2:1995

Directives

  • EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
  • LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC

Ordering information

MODEL – VOLTAGE – CURRENT – CAL. FREQ. – POWER – I/O MODULE – COMMS

Model
PM175 power quality analyserPM175
PM175 with 5.7" touch screen colour graphic displayPM175-TFT
Transducer versionRPM075
Voltage inputs
690V AC nominal voltage input-
120V AC nominal voltage inputU
Current inputs
5 Ampere5
1 Ampere1
5A split core remote high accuracy current sensorRS5
High Accuracy Current Sensors (HACS), requires ordering of 3 HACSHACS
Calibration at frequency
50 Hz50Hz
60 Hz60Hz
Power supply
85-265V AC and 88-290V DCACDC
9.6-19V DC1DC
19-37V DC2DC
37-72V DC3DC
I/O module
2 digital inputs/2 digital outputs (standard)-
Additional 2 DI/2 DO (total 4 DI/4 DO)DIO
2 analogue outputs: ±1 mAAO1
2 analogue outputs: 0-20 mAAO2
2 analogue outputs: 0-1 mAAO3
2 analogue outputs: 4-20 mAAO4
2 analogue outputs: 0-5 mAAO5
2 analogue outputs: ±5 mAAO6
2 analogue inputs: ±1 mAAI1
2 analogue inputs: 0-20 mAAI2
2 analogue inputs: 0-1 mAAI3
2 analogue inputs: 4-20 mAAI4
Communication
Standard communications RS-232/422/485-
Ethernet (TCP/IP)ETH
ProfibusPRO

Downloads and related