PM175 · DATASHEET

PM175 power quality analyser datasheet (LED display)

Power Quality Analyser and Revenue Meter with Detachable LED Display.

Transcribed from the SATEC Australia datasheet TBV1.0, 29 September 2026 (PDF, 5 pages, 439 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

Superseded: this meter has been superseded by the PRO Series PM175. This datasheet is kept for existing installations and support. For new projects see the PM175 PRO.

The PM175 is a compact multifunction three-phase AC power meter and power quality analyser. It was designed for users ranging from electrical panel builders to substation operators who need revenue-grade energy data and EN 50160 power quality reporting in one instrument.

A bright three-row LED display gives clear local readings. The display module is detachable and can be mounted up to 1000 m from the meter. Two communication ports support local and remote meter reading and setup over serial lines, LAN and the internet.

Current input options

Main features

Feature capabilities

Measurements

  • Class 0.2S revenue accuracy
  • 128 samples per cycle true RMS measurements
  • Fast real-time cycle-by-cycle measurements
  • Four-quadrant measurements
  • Min/Max values for instantaneous and demand readings
  • Accepts all wiring configurations, selectable from the front panel or via communications

Energy and Time-of-Use

  • Class 0.2S active and apparent energy per AS/IEC 62053-22:2003
  • 8 totalisation and tariff energy/demand registers x 8 tariffs
  • 4 seasons x 4 types of day with 8 tariff changes per day
  • Easily programmable tariff schedule
  • Automatic daily profile of energy and maximum demand readings for total and tariff registers

EN 50160 Power Quality Recorder

  • EN 50160 compliance statistics and harmonics survey statistics
  • Onboard power quality analyser with programmable thresholds and hysteresis
  • Ready-to-use reports
  • Customisable EN 50160 power quality recorder
  • IEEE 519 power quality evaluation
  • Flicker measurement per IEC 61000
  • Sag/swell detection and automatic reporting

Full Harmonic Analyser

  • Individual voltage and current harmonics up to the 50th order
  • Voltage inter-harmonics up to the 50th order
  • Voltage and current THD, current TDD and K-factor
  • Power harmonics and harmonic flow (direction of harmonics)
  • Voltage and current harmonic spectrum and angles
  • Conforms with harmonic standards IEEE 1159 and G5/4

Waveform and Transient Recording

  • Two independent simultaneous waveform recorders
  • Each records complete three-phase voltage and current waveforms
  • Recording resolution from 32 up to 128 samples per cycle
  • Up to 16 pre-fault and up to 2000 post-fault cycles
  • Transient recording with a minimum width of 156 µs at 50 Hz
  • Programmable memory partition

Event and Data Logging

  • Programmable event log with 1 ms time stamp
  • 16 programmable data log tables with up to 16 parameters each
  • Record intervals from 1 to 9999 seconds
  • 1 MB of non-volatile log memory
  • Fully programmable memory partition for event, data and waveform logs

Real-Time Clock

  • Real-time clock for time-stamped event, data and waveform logs
  • Typical error of 15 seconds per month at 25°C
  • Synchronisation with a GPS pulse input

Control and I/O

  • 2 relay outputs
  • 4 digital inputs
  • 4 analogue inputs (optional)
  • Up to 16 analogue outputs (optional)

Communications

  • Two independent communication ports
  • COM1: RS232/422/485 or Ethernet 10/100BaseT
  • COM2: RS422/485
  • Modbus RTU, Modbus ASCII, Modbus TCP/IP, DNP3 and Profibus DP
  • MV90xi compatible

Software Support

  • PAS Power Analysis Software for setup, data retrieval and analysis
  • Expertpower web platform via the Ethernet port
  • eXpertConnect™ App for mobile access to energy data

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Construction
DimensionsHeight 114 mm, width 127 mm, length 114 mm
Weight1.23 kg (2.7 lb)
DisplayBright 3-row LED display, detachable and mountable up to 1000 m from the meter
Optional displayLCD colour touch screen graphical display
Voltage inputs
Operating range690V AC line-to-line, 400V AC line-to-neutral
ConnectionDirect or via PT (up to 828V AC line-to-line, up to 480V AC line-to-neutral)
Current inputs · 5A secondary
Operating range10A RMS continuous
Burden<0.1 VA
Overload withstand15A RMS continuous, 300A RMS for 1 second
Current inputs · 1A secondary
Operating range2A RMS continuous
Burden<0.02 VA
Overload withstand6A RMS continuous, 80A RMS for 1 second
General
Frequency15 Hz to 480 Hz
Burden8 VA
Operating temperature-20°C to +60°C
Humidity0 to 95% non-condensing
Real-time clockTypical error 15 seconds per month at 25°C
Inputs and outputs
Relay outputs2 relays rated 3A/250V AC and 3A/30V DC, 2 contacts (SPST Form A)
Digital inputs4
Analogue inputs4 (optional)
Analogue outputsUp to 16 (optional)
Analogue ranges±1 mA, 0-1 mA, 0-20 mA, 4-20 mA
Energy and accuracy
Accuracy classClass 0.2S per AS/IEC 62053-22:2003
Revenue accuracyPer ANSI C12.20-1998
Time-of-Use8 totalisation and tariff energy/demand registers x 8 tariffs, 4 seasons x 4 types of day, 8 tariff changes per day
Daily profileAutomatic daily profile of energy and maximum demand readings
Communications
PortsTwo independent communication ports
COM1RS232/422/485 or Ethernet 10/100BaseT
COM2RS422/485
RS485Up to 32 devices
ProtocolsModbus RTU, Modbus ASCII, Modbus TCP/IP, DNP3, Profibus DP
Memory and logging
Log memory1 MB non-volatile
Data logs16 tables, up to 16 parameters each, 1 to 9999 s intervals
Waveform logs2 recorders, 32 to 128 samples per cycle
Event log1 ms time stamp
Warranty
Product warranty3 years
Warranty of accuracy10 years
Measurement accuracy
Voltage (10-120% FS)0.2%
Current (10-200% FS), starting current 0.1% FS0.2%
Neutral current0.4%
Frequency0.02%
Power factor0.2%
Active power (W)0.2%
Reactive power (var)0.3%
Apparent power (VA)0.2%
Active energy (Wh)Class 0.2S per AS/IEC 62053-22:2003
Reactive energy (varh)Class 0.2S under conditions per AS/IEC 62053-22:2003, |PF| < 0.9
Apparent energy (VAh)Class 0.2S per AS/IEC 62053-22:2003
Total harmonic distortion (THD)0.1%
Total demand distortion (TDD)1.5%
Temperature coefficient0.008%/°C
Input circuit consumptionLess than 0.1 VA
Measured current range1% to 200%

Printed column headings: Parameter; Accuracy (Reading).

Standards compliance

Accuracy

  • AS/IEC 62053-22:2003 Class 0.2S
  • ANSI C12.20-1998

Power quality

  • EN 50160
  • IEC 61000-4-7 harmonics and inter-harmonics
  • IEC 61000 flicker
  • CBEMA/ITIC
  • IEEE 519 and IEEE 1159

Emission

  • EN 55011:1991
  • EN 55022:1994 Class A
  • EN 50081-2 Generic Emission Standard, Industrial Environment

Immunity

  • EN 50082-1:1992
  • EN 50082-2 Generic Immunity Standard, Industrial Environment
  • EN 61000-4-2, EN 61000-4-4:1995, EN 61000-4-8:1993
  • ENV 50140:1983, ENV 50141:1993, ENV 50204:1995 (900 MHz)

Safety

  • EN 61010-1:1993/A2:1995

Directives

  • EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
  • LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC

Ordering information

The PM175 with LED display is no longer offered for new orders. It has been superseded by the PRO Series PM175, which adds Class A power quality measurement per IEC 61000-4-30. SATEC Australia continues to support existing PM175 installations.