PM172 · DATASHEET

PM172 power and revenue meter datasheet

PM172 Series: advanced high accuracy power and revenue meter.

Transcribed from the SATEC Australia datasheet TBV1.0, 28 September 2026 (PDF, 7 pages, 585 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PM172 is a compact, multi-function, three-phase AC power meter and Class 0.2S revenue meter. It is designed for users ranging from electrical panel builders to substation operators, with more than 100 measured parameters for feeder monitoring, utility substations, industrial SCADA and distribution automation.

A bright three-row LED display with a load bar graph sits on a detachable display module that can be located up to 1000 m from the meter. Built-in Time of Use tariffs, event and data recorders, harmonic analysis and waveform capture sit alongside two independent communication ports supporting Modbus, DNP3 and Profibus DP, with an Ethernet option for Expertpower.

PM172P: Multi-functional three-phase power meter with harmonic analysis, setpoint control and digital I/O.

PM172E: Adds a Class 0.2S TOU revenue meter, an event recorder and multi-channel data recorders.

PM172EH: Adds extended harmonic analysis, fast waveform recorders and voltage disturbance monitoring.

Main features

Feature capabilities

Multi-functional three-phase power meter

  • 3 voltage and 3 current transformer-isolated AC inputs for direct connection to the power line or via potential and current transformers
  • True RMS volts, amps, power, power factor, neutral current, voltage and current unbalance and frequency
  • Ampere, volt, THD and TDD demand meter
  • 1-cycle real-time and 1-second average measurements
  • 25, 50, 60 and 400Hz operation

Harmonic analysis

  • Embedded harmonic analyser: voltage and current THD, current TDD and K-Factor up to the 40th order
  • Voltage and current harmonic spectrum and angles up to the 40th order (PM172EH)
  • Harmonic power and energy (PM172EH)

Programmable controller and alarms

  • Embedded programmable controller with 16 control setpoints
  • Programmable thresholds and delays with relay output control
  • 1-cycle response time
  • Four six-digit counters for counting pulses or events

Billing and TOU revenue meter (PM172E and PM172EH only)

  • Class 0.2S four-quadrant active, reactive and apparent energy, import and export, to AS/IEC 62053-22
  • Time of Use with 8 totalisation and tariff energy/demand registers x 8 tariffs
  • 4 seasons x 4 types of days and 8 tariff changes per day, with an easy programmable tariff schedule
  • Automatic daily profile for energy and maximum demand readings (total and tariff registers)
  • MV90xi compatible

Waveform and disturbance recording (PM172EH only)

  • Two waveform recorders with simultaneous 6-channel AC recording in a single plot
  • Sampling rates of 32 and 128 samples per cycle, with 20 pre-fault cycles
  • Up to 30 seconds of continuous recording at 32 samples per cycle
  • Real-time waveform capture and monitoring: simultaneous 6-channel 4-cycle capture at 128 samples per cycle
  • Voltage disturbance monitor with setpoint triggering

Event and data recording (PM172E and PM172EH only)

  • Event recorder for logging internal diagnostic events, control events and I/O operations
  • Eight data recorders with programmable data logs on a periodic basis and on any internal or external trigger
  • Real-time stamped logging of more than 100 parameters
  • 1 Mbyte onboard memory with battery backup

Display

  • Easy to read 3-row (2 x 4 characters + 1 x 6 characters) bright LED display
  • Adjustable update time, auto-scroll with adjustable page exposition time and auto-return to a default page
  • LED bar graph showing percent load against a user-definable nominal load current
  • Detachable display module with a 3-wire RS-485 interface, operating up to 1000 m from the meter
  • Optional colour touch screen graphical display

Inputs and outputs

  • 2 digital inputs for monitoring external contacts and receiving pulses from energy, water and gas meters
  • 2 relay outputs for alarms, controls and energy pulse output
  • Optional DIO module adds 2 digital inputs and 2 digital outputs (4 DI / 4 DO in total)
  • 2 optional optically isolated analogue outputs or analogue inputs with an internal power supply
  • Optional analogue expander providing an additional 2 x 8 analogue outputs

Current input options

  • 5A or 1A secondary inputs for standard CTs
  • Optional High Accuracy Current Sensors (HACS)
  • 5A split core remote HACS option for retrofit installations

Communications

  • Two independent communication ports for local and remote meter reading and setup
  • COM1 options: RS-232/422/485, Ethernet 10/100BaseT or Profibus DP
  • COM2: RS-422/485
  • Modbus RTU and ASCII, Modbus/TCP, DNP3, DNP3/TCP, GE EGD producer, Profibus DP and SATEC ASCII protocols
  • Ethernet port is Expertpower enabled, with a TCP notification client

Real-time clock and firmware

  • Precise internal clock and calendar with battery backup
  • Time synchronisation via a communication port or digital input
  • Easy field upgrading of device firmware through any communication port

Software support

  • Power Analysis Software (PAS) for meter setup, data retrieval and analysis
  • Expertpower web platform for energy monitoring and management reports
  • eXpertConnect™ App for mobile connection to the meter for configuration, readings and diagnostics

Applications

  • Utility substations
  • Feeder monitoring
  • Industrial SCADA
  • Distribution automation
  • Revenue and tariff metering
  • Electrical panel builders

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Environmental conditions
Operating temperature-20°C to 60°C (-4°F to 140°F)
Storage temperature-25°C to 80°C (-13°F to 176°F)
Humidity0 to 95% non-condensing
Construction
Display module127 x 127 mm (max.)
Meter body114 x 114 mm
Panel mountingANSI 4" round or DIN 92 x 92 mm square cutout
DIN rail mounting35 mm DIN rail
Weight1.23 kg (2.7 lb)
Case enclosurePlastic PC/ABS blend
Front panelPlastic PC
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Power supply
120/230V AC, 110/220V DC option85 to 264V AC 50/60Hz, 88 to 290V DC
Burden10W
12V DC option9.6 to 19V DC
24V DC option19 to 37V DC
48V DC option37 to 72V DC
IsolationInput to output 3000V AC; input to ground 2000V AC
Wire sizeUp to 12 AWG (3.5 mm²)
Voltage inputs
Operating range690V AC line-to-line, 400V AC line-to-neutral
Direct input and via PTUp to 828V AC line-to-line, up to 480V AC line-to-neutral
Input impedance500 kΩ
Burden< 0.4VA at 400V; < 0.04VA at 120V
Overvoltage withstand1000V AC continuous; 2000V AC for 1 second
Galvanic isolation3500V AC
Wire sizeUp to 12 AWG (3.5 mm²)
Current inputs
Galvanic isolation3500V AC
Wire size12 AWG (up to 3.5 mm²)
Current inputs: 5A secondary
Operating range10A RMS continuous
Burden< 0.1VA
Overload withstand15A RMS continuous; 300A RMS for 1 second
Current inputs: 1A secondary
Operating range2A RMS continuous
Burden< 0.02VA
Overload withstand6A RMS continuous; 80A RMS for 1 second
Frequency
Measurement range15Hz to 480Hz
Calibration frequency25, 50, 60 or 400Hz (upon order)
Relay outputs
Relays2 relays rated at 3A/250V AC; 3A/30V DC
Contacts2 contacts (SPST Form A)
IsolationContacts to coil 2000V AC for 1 minute; open contacts 1000V AC
Operate / release time10 ms max. / 5 ms max.
Update time1 cycle
Wire size14 AWG (up to 1.5 mm²)
Communication ports: COM1 RS-232 or RS-422/485 (optional module)
PortOptically isolated, 2000V RMS, DB9 female
Baud rateUp to 115.2 kbps
ProtocolsModbus RTU, DNP3 and SATEC ASCII
Communication ports: COM1 Ethernet (optional module)
PortTransformer-isolated 10/100BaseT, RJ45
ProtocolsModbus/TCP (port 502), DNP3/TCP (port 20000), GE EGD producer
Connections4 simultaneous (4 Modbus/TCP, or 2 Modbus/TCP + 2 DNP3/TCP)
Communication ports: COM1 Profibus DP, IEC 61158 (optional module)
PortRS-485 optically isolated, DB9 female
Baud rate9600 bit/s to 12 Mbit/s (auto detection)
Data32 bytes input, 32 bytes output
Communication ports: COM2 RS-422/485
PortOptically isolated, 2000V RMS, removable 5-pin connector
Baud rateUp to 115.2 kbps
ProtocolsModbus RTU, DNP3 and SATEC ASCII
RS-485 networkUp to 32 devices
Wire sizeUp to 14 AWG (1.5 mm²)
Real-time clock and memory
Clock accuracyTypical error 30 seconds per month at 25°C
Log memory1 Mbyte onboard memory with battery backup
Warranty
Product warranty3 years
Warranty of accuracy10 years
Digital inputs
Inputs2 dry contact inputs
SensitivityOpen at input resistance > 100 kΩ; closed at < 100 Ω
Galvanic isolation2000V RMS
Internal power supply15V
Scan time1 ms
Wire size14 AWG (up to 1.5 mm²)
Optional analogue inputs
Inputs2 optically isolated analogue inputs
Ranges (upon order)±1 mA (1.2 kΩ); 0-1 mA (2.4 kΩ); 0-20 mA (250 Ω); 4-20 mA (250 Ω)
Isolation2000V RMS
Accuracy0.5% FS
Scan time1 cycle
Wire size14 AWG (up to 1.5 mm²)
Optional analogue outputs
Outputs2 optically isolated analogue outputs, internal power supply
Ranges (upon order)±1 mA and 0-1 mA (max. load 5 kΩ); 0-20 mA and 4-20 mA (max. load 510 Ω)
Isolation2000V RMS
Accuracy0.5% FS
Update time1 cycle
Wire size14 AWG (up to 1.5 mm²)
Display module
DisplayHigh-brightness seven-segment LEDs, two 4-digit and one 6-digit windows
Keypad6 push buttons
CommunicationEIA RS-485 port with 12V supply voltage
ConnectorDB15, 15 pins
DistanceUp to 1000 m (3200 ft)
Supply / consumption12V DC ±10% / 2W
Wire sizeUp to 14 AWG (1.5 mm²)
Measurement accuracy
VoltageFull scale at input range: 120V x PT at 120V; 400V x PT at 690V. Accuracy: 0.2% reading, 0.01% FS. Conditions: 10% to 120% FS. Range: 0 to 1,150,000V
Line currentFull scale at input range: CT. Accuracy: 0.2% reading, 0.02% FS. Conditions: 1% to 200% FS. Range: 0 to 40,000A
Neutral currentAccuracy: 0.4% reading
Active powerFull scale at input range: 0.36 x PT x CT at 120V; 1.2 x PT x CT at 690V. Accuracy: 0.2% reading, 0.02% FS. Conditions: |PF| ≥ 0.5 (note 1). Range: -10,000,000 kW to +10,000,000 kW
Reactive powerFull scale at input range: 0.36 x PT x CT at 120V; 1.2 x PT x CT at 690V. Accuracy: 0.3% reading, 0.04% FS. Conditions: |PF| ≤ 0.9 (note 1). Range: -10,000,000 kvar to +10,000,000 kvar
Apparent powerFull scale at input range: 0.36 x PT x CT at 120V; 1.2 x PT x CT at 690V. Accuracy: 0.2% reading, 0.02% FS. Conditions: |PF| ≥ 0.5 (note 1). Range: 0 to 10,000,000 kVA
Power factorFull scale at input range: 1.000. Accuracy: 0.2% FS. Conditions: |PF| ≥ 0.5, I ≥ 2% FSI. Range: -0.999 to +1.000
FrequencyAccuracy: 0.02% reading. Range: 15Hz to 480Hz
Total harmonic distortion, THD V (I), %Vf (%If)Full scale at input range: 999.9. Accuracy: 1.5% reading, 0.1% FS. Conditions: THD ≥ 1%, V (I) ≥ 10% FSV (FSI). Range: 0 to 999.9
Total demand distortion, TDD, %Full scale at input range: 100. Accuracy: 1.5% FS. Conditions: TDD ≥ 1%, I ≥ 10% FSI. Range: 0 to 100
Active energy, import and exportClass 0.2S under conditions as per AS/IEC 62053-22:2003. Range: 0 to 999,999.999 MWh
Reactive energy, import and exportClass 0.2S under conditions as per AS/IEC 62053-22:2003, |PF| ≤ 0.9. Range: 0 to 999,999.999 Mvarh
Apparent energyClass 0.2S under conditions as per AS/IEC 62053-22:2003. Range: 0 to 999,999.999 MVAh

Note 1: at 80% to 120% of voltage FS, 1% to 200% of current FS and frequency 50/60Hz. PT: external potential transformer ratio. CT: primary current rating of external current transformer. FSV: voltage full scale. FSI: current full scale. Vf: fundamental voltage. If: fundamental current. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not include inaccuracies introduced by the user's potential and current transformers. Accuracy is calculated at a 1-second average. Specifications assume voltage and current waveforms with THD ≤ 5% for kvar, kVA and PF, and a reference operating temperature of 20°C to 26°C. Temperature coefficient: 0.008% / °C. Measurement error is typically less than the maximum error indicated.

Standards compliance

Accuracy

  • AS/IEC 62053-22 Class 0.2S (1A and 5A versions)
  • Accuracy per ANSI C12.20-1998

Electromagnetic immunity

  • EN 50082-1:1992
  • EN 50082-2 Generic Immunity Standard, Industrial Environment
  • EN 61000-4-2
  • ENV 50140:1983
  • ENV 50204:1995 (900MHz)
  • ENV 50141:1993
  • EN 61000-4-4:1995
  • EN 61000-4-8:1993

Electromagnetic emission

  • EN 55011:1991
  • EN 50081-2 Generic Emission Standard, Industrial Environment
  • EN 55022:1994 Class A

Safety

  • EN 61010-1:1993, A2/1995

Directives complied with

  • EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
  • LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC

Communication protocols

  • Modbus RTU, Modbus ASCII and Modbus/TCP
  • DNP3 and DNP3/TCP
  • Profibus DP (IEC 61158)
  • GE EGD producer

Ordering information

MODEL – VOLTAGE – CURRENT – CAL. FREQ. – POWER – I/O MODULE – COMMUNICATION

Model
Power meterPM172P-N
Power meter including revenue meterPM172E-N
Power meter including revenue meter, harmonic analysis and waveform capturePM172EH-N
PM172E-N transducer version, no displayRPM072
Voltage input
690V AC nominal voltage input (standard)No code
120V AC nominal voltage inputU
Current input
5 ampere5
1 ampere1
5A split core remote high accuracy current sensorRS5
High Accuracy Current Sensors (order 3 HACS separately)HACS
Calibration frequency
25Hz25HZ
50Hz50HZ
60Hz60HZ
400Hz400HZ
Power supply
85 to 264V AC and 88 to 290V DCACDC
9.6 to 19V DC1DC
19 to 37V DC2DC
37 to 72V DC3DC
I/O module
2 digital inputs / 2 digital outputs (standard)No code
Additional 2 DI / 2 DO (4 DI / 4 DO in total)DIO
2 analogue outputs, ±1 mAAO1
2 analogue outputs, 0-20 mAAO2
2 analogue outputs, 0-1 mAAO3
2 analogue outputs, 4-20 mAAO4
2 analogue inputs, ±1 mAAI1
2 analogue inputs, 0-20 mAAI2
2 analogue inputs, 0-1 mAAI3
2 analogue inputs, 4-20 mAAI4
Communication
RS-232/422/485 (standard)No code
Ethernet (TCP/IP)ETH
Profibus DPPRO