Transcribed from the SATEC Australia datasheet TBV1.0, 2 September 2026 (PDF, 7 pages, 849 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The PM130 PLUS is a compact multi-function, three-phase AC power meter designed to meet the requirements of users ranging from electrical panel builders to substation operators. Measurement inputs and power supply comply with Measuring Category II.
The series offers a bright multi-row LED display, a standard RS-485 port with an optional plug-in second communications module, and a selection of digital I/O and analogue output modules — with all models suited to both 4-inch round and 92×92 mm square panel cutouts.
PM130P: Base model — voltage, current, power & frequency measurement and control.
PM130E: Adds energy measurement & data logging.
PM130EH: Adds harmonic analysis to the PM130E feature set.
Main features
3 voltage inputs and 3 current-transformer-isolated AC inputs for direct connection to the power line or via potential and current transformers
True RMS volts, amps, power, power factor, neutral current, voltage and current unbalance, frequency
Ampere/Volt demand meter
25/50/60/400 Hz measurement capability
Selection of I/O plug-in modules from 4DI/2DO up to 12DI/4RO, with communications
Standard RS-485 port plus an optional plug-in RS-232/422/485, Ethernet or Profibus module
Dual panel mounting — 92×92 mm square or 4-inch round cutout
Feature capabilities
Billing / TOU energy meter (PM130E and PM130EH only)
Class 0.5S IEC 62053-22 four-quadrant active and reactive energy polyphase static meter
Three-phase total and per-phase energy measurement — active, reactive and apparent energy counters
Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 day types, 8 tariff changes per day
One-time programmable tariff calendar schedule
Automatic daily energy and maximum demand profile log for total and tariff registers
Harmonic analyser (PM130EH only)
Voltage and current THD, current TDD and K-Factor, up to the 40th order harmonic
Voltage and current harmonic spectrum and angles
Real-time waveform capture
Real-time "scope mode" waveform monitoring
Simultaneous 6-channel, one-cycle waveform capture at 64 samples per cycle
Accessed via Power Analysis Software (PAS), Expertpower or the eXpertConnect™ App
Programmable logical controller
Embedded programmable controller
16 control setpoints — programmable thresholds and delays
Relay output control
1-cycle response time
Event and data recording (PM130E and PM130EH only)
Non-volatile memory for long-term event and data recording
Event recorder for internal diagnostic events and setup changes
Two data recorders — periodic data logs plus automatic daily energy and max-demand profile log
Display
3-row (2×4 characters + 1×5 characters) bright LED display, adjustable update time and brightness
Auto-scroll with adjustable page exposition time; auto-return to a default page
LED bar graph showing percent load against a user-definable nominal load current
Real-time clock
Internal clock with 20-second retention time
Optional battery backup via the TOU+4DI module
I/O options
TOU+4DI — 4 digital inputs, 1 ms scan time, battery-backed real-time clock, records the last five input-change events with timestamps
4DIO — 4 digital inputs and 2 relay outputs, 1-cycle update; unlatched, latched, pulse and KYZ operation; solid-state or electromechanical relay option
12DIO — 12 digital inputs, 4 relay outputs, optional Ethernet or RS-485 port
4AO — 4 optically isolated analogue outputs, internal power supply; 0–20 mA / 4–20 mA / 0–1 mA / ±1 mA, 1-cycle update
Expertpower client for SATEC's Expertpower internet services (via Ethernet)
TCP notification client to a remote Modbus/TCP server, on event or on a time basis (via Ethernet)
eXpertConnect™ App — connects directly to the meter for on-site setup and readings
Measurement
Direct voltage measurement up to 690 V
5A — up to 10A via conventional 5A CTs (see the solid-core and split-core current transformer ranges)
1A — up to 2A via conventional 1A CTs (see the solid-core and split-core current transformer ranges)
HACS — remote sensors from 100 A up to 3000 A with built-in shorting circuit; Class 0.5S system accuracy (meter plus sensor); requires 3× HACS ordered separately
RS5 — a separate connection scheme underneath HACS: remote split-core sensor for straightforward retrofit onto a 5A conventional CT circuit; requires 3× RS5 HACS ordered separately
Unique design
Pass-through CT connection for minimal burden
Auxiliary CT connection terminal for simple installation
Dual panel mounting — 92×92 mm square or 4-inch round cutout
Add-on modular design for a second communications port, digital I/O or analogue outputs
Meter security
Password security protecting meter setups and accumulated data from unauthorised changes
Upgradeable firmware
Firmware upgrade via a serial or Ethernet port
Software support
PAS — SATEC's bundled configuration and data-acquisition tool, including waveforms, phasors and harmonics
Expertpower — SATEC's internet-based energy management software, with no client software installation required
eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
Environmental conditions
Operating temperature
−30°C to 60°C (−22°F to 140°F)
Storage temperature
−40°C to 85°C (−40°F to 185°F)
Humidity
0–95% RH, non-condensing
Construction and materials
Weight
0.70 kg (1.54 lb)
Dimensions [H×W×D]
114×114×109 mm (4.5×4.5×4.3")
Case enclosure
PC/ABS blend plastic
Front panel
PC plastic
PCB
FR4 (UL94-V0)
Terminals
PBT (UL94-V0)
Plug-in connectors
Polyamide PA6.6 (UL94-V0)
Labels
Polyester film (UL94-V0)
Power supply
120/230V AC-DC option
85–265V AC 50/60/400 Hz, 88–290VDC · 9VA burden · 2500V AC isolation (input to ground)
12VDC option
9.5–18V DC · 4VA burden · 1500V DC isolation
24/48VDC option
18.5–58VDC · 4VA burden · 1500VDC isolation · up to 12 AWG (3.5 mm²) wire