PM130 PLUS · DATASHEET

PM130 PLUS power meter datasheet

High Performance Multi-function Power Meter.

Transcribed from the SATEC Australia datasheet TBV1.0, 2 September 2026 (PDF, 7 pages, 849 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PM130 PLUS is a compact multi-function, three-phase AC power meter designed to meet the requirements of users ranging from electrical panel builders to substation operators. Measurement inputs and power supply comply with Measuring Category II.

The series offers a bright multi-row LED display, a standard RS-485 port with an optional plug-in second communications module, and a selection of digital I/O and analogue output modules — with all models suited to both 4-inch round and 92×92 mm square panel cutouts.

PM130P: Base model — voltage, current, power & frequency measurement and control.

PM130E: Adds energy measurement & data logging.

PM130EH: Adds harmonic analysis to the PM130E feature set.

Main features

Feature capabilities

Billing / TOU energy meter (PM130E and PM130EH only)

  • Class 0.5S IEC 62053-22 four-quadrant active and reactive energy polyphase static meter
  • Three-phase total and per-phase energy measurement — active, reactive and apparent energy counters
  • Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 day types, 8 tariff changes per day
  • One-time programmable tariff calendar schedule
  • Automatic daily energy and maximum demand profile log for total and tariff registers

Harmonic analyser (PM130EH only)

  • Voltage and current THD, current TDD and K-Factor, up to the 40th order harmonic
  • Voltage and current harmonic spectrum and angles

Real-time waveform capture

  • Real-time "scope mode" waveform monitoring
  • Simultaneous 6-channel, one-cycle waveform capture at 64 samples per cycle
  • Accessed via Power Analysis Software (PAS), Expertpower or the eXpertConnect™ App

Programmable logical controller

  • Embedded programmable controller
  • 16 control setpoints — programmable thresholds and delays
  • Relay output control
  • 1-cycle response time

Event and data recording (PM130E and PM130EH only)

  • Non-volatile memory for long-term event and data recording
  • Event recorder for internal diagnostic events and setup changes
  • Two data recorders — periodic data logs plus automatic daily energy and max-demand profile log

Display

  • 3-row (2×4 characters + 1×5 characters) bright LED display, adjustable update time and brightness
  • Auto-scroll with adjustable page exposition time; auto-return to a default page
  • LED bar graph showing percent load against a user-definable nominal load current

Real-time clock

  • Internal clock with 20-second retention time
  • Optional battery backup via the TOU+4DI module

I/O options

  • TOU+4DI — 4 digital inputs, 1 ms scan time, battery-backed real-time clock, records the last five input-change events with timestamps
  • 4DIO — 4 digital inputs and 2 relay outputs, 1-cycle update; unlatched, latched, pulse and KYZ operation; solid-state or electromechanical relay option
  • 12DIO — 12 digital inputs, 4 relay outputs, optional Ethernet or RS-485 port
  • 4AO — 4 optically isolated analogue outputs, internal power supply; 0–20 mA / 4–20 mA / 0–1 mA / ±1 mA, 1-cycle update

Communications

  • Standard 2-wire RS-485 port
  • Protocols: Modbus RTU, ASCII, DNP3.0; optional IEC 60870-5-101; with Ethernet: Modbus/TCP, DNP3/TCP; optional IEC 60870-5-104
  • Expertpower client for SATEC's Expertpower internet services (via Ethernet)
  • TCP notification client to a remote Modbus/TCP server, on event or on a time basis (via Ethernet)
  • eXpertConnect™ App — connects directly to the meter for on-site setup and readings

Measurement

  • Direct voltage measurement up to 690 V
  • 5A — up to 10A via conventional 5A CTs (see the solid-core and split-core current transformer ranges)
  • 1A — up to 2A via conventional 1A CTs (see the solid-core and split-core current transformer ranges)
  • HACS — remote sensors from 100 A up to 3000 A with built-in shorting circuit; Class 0.5S system accuracy (meter plus sensor); requires 3× HACS ordered separately
  • RS5 — a separate connection scheme underneath HACS: remote split-core sensor for straightforward retrofit onto a 5A conventional CT circuit; requires 3× RS5 HACS ordered separately

Unique design

  • Pass-through CT connection for minimal burden
  • Auxiliary CT connection terminal for simple installation
  • Dual panel mounting — 92×92 mm square or 4-inch round cutout
  • Add-on modular design for a second communications port, digital I/O or analogue outputs

Meter security

  • Password security protecting meter setups and accumulated data from unauthorised changes

Upgradeable firmware

  • Firmware upgrade via a serial or Ethernet port

Software support

  • PAS — SATEC's bundled configuration and data-acquisition tool, including waveforms, phasors and harmonics
  • Expertpower — SATEC's internet-based energy management software, with no client software installation required
  • eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Environmental conditions
Operating temperature−30°C to 60°C (−22°F to 140°F)
Storage temperature−40°C to 85°C (−40°F to 185°F)
Humidity0–95% RH, non-condensing
Construction and materials
Weight0.70 kg (1.54 lb)
Dimensions [H×W×D]114×114×109 mm (4.5×4.5×4.3")
Case enclosurePC/ABS blend plastic
Front panelPC plastic
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
LabelsPolyester film (UL94-V0)
Power supply
120/230V AC-DC option85–265V AC 50/60/400 Hz, 88–290VDC · 9VA burden · 2500V AC isolation (input to ground)
12VDC option9.5–18V DC · 4VA burden · 1500V DC isolation
24/48VDC option18.5–58VDC · 4VA burden · 1500VDC isolation · up to 12 AWG (3.5 mm²) wire
Voltage inputs
Operating range690VAC line-to-line, 400VAC line-to-neutral
Direct / via PTUp to 790VAC L-L, up to 460VAC L-N
Input impedance1000 kΩ
Burden @ 400V / 120V<0.4 VA / <0.04 VA
Over-voltage withstand1000VAC continuous, 2000VAC for 1 s
Wire sizeUp to 12 AWG (3.5 mm²)
Current inputs (via CT)
Wire size12 AWG (3.5 mm²)
Galvanic isolation3500VAC
5A secondary / RS5Continuous 10A RMS · <0.2VA burden @ In=5A · overload 15A RMS continuous, 300A RMS 1 s
1A secondaryContinuous 2A RMS · <0.02VA burden @ In=1A · overload 3A RMS continuous, 80A RMS 1 s
Standard CT rangeSolid-core and split-core current transformers, 5A-3000A primary
HACS remote sensors100–3000 A per sensor rating — see the HACS datasheet
Sampling and resolution
Sampling rate128 samples/cycle
Display/measurement resolutionLow (1A, 1V) or high (0.01A, 0.1V) — field-programmable in the meter; no factory order code required
Optional relay outputs: electromechanical (4DI/DO or 12DI/DO module)
Rating2 or 4 relays, 5A/250VAC or 5A/30VDC, 1 contact (SPST Form A)
Galvanic isolation3000VAC (contacts–coil) · 750VAC (open contacts)
Operate / release time10 ms max / 5 ms max
Wire size14 AWG (1.5 mm²)
Optional relay outputs: solid-state (4DI/2DO module)
Rating2 relays, 0.15A/250V AC/DC, 1 contact (SPST Form A)
Galvanic isolation3750VAC 1 min
Operate / release time1 ms max / 0.25 ms max
Optional digital inputs
Type4 or 12 inputs (4DI/2DO or 12DI/4DO module); dry contact, internally wetted @ 24VDC, or wet contact @ 250VDC (12DI/4DO only)
SensitivityOpen >100 kΩ · closed <100 Ω
Galvanic isolation3750VAC 1 min
Scan time1 ms
Optional analogue outputs
Ranges (on order)±1 mA · 0–20 mA · 4–20 mA · 0–1 mA
Isolation2500VAC 1 min
Accuracy0.5% FS
Update time1 cycle
Communication ports: COM1 — RS-485
Isolation / baud3000VAC 1 min · up to 115.2 kbps
ProtocolsModbus RTU, DNP3, SATEC ASCII
Communication ports: COM2 (optional module)
EthernetTransformer-isolated 10/100BaseT · Modbus/TCP (502), DNP3/TCP (20000) · 4 simultaneous connections
App connectioneXpertConnect™ App — direct meter connection for setup and readings
Profibus DP (IEC 61158)RS-485 isolated · 9600 bit/s–12 Mbit/s auto-detect · 32 bytes in/out
RS-232/422/485Isolated · up to 115.2 kbps · Modbus RTU, DNP3, SATEC ASCII
Real-time clock
Standard meter clockNon-backed · ~1 min/month error @ 25°C · 30 s retention
TOU module clockBattery-backed · ~7 s/month error @ 25°C (±2.5ppm) · 36-month retention
Display module
TypeHigh-brightness 7-segment LED, two 4-digit + one 5-digit window
Bar graph3-colour LED, 40–110% load
Keypad6 push buttons

Standards compliance

Accuracy

  • Complies with IEC 62053-22, Class 0.5S (PM130E / PM130EH)
  • Meets ANSI C12.20-1998, Class 10, 0.5%

Electromagnetic immunity

  • Complies with IEC 61000-6-2
  • IEC 61000-4-2 level 3 — electrostatic discharge
  • IEC 61000-4-3 level 3 — radiated electromagnetic RF fields
  • IEC 61000-4-4 level 3 — electrical fast transient
  • IEC 61000-4-5 level 3 — surge
  • IEC 61000-4-6 level 3 — conducted radio frequency
  • IEC 61000-4-8 — power-frequency magnetic field
  • Meets ANSI/IEEE C37.90.1 — fast transient SWC

Electromagnetic emission

  • Complies with IEC 61000-6-4 — radiated/conducted Class A
  • Complies with IEC CISPR 22 — radiated/conducted Class A

Safety and construction

  • Meets IEC 61010-1:2006

AC and impulse insulation

  • Complies with IEC 62052-11 — 2500VAC for 1 minute
  • 6kV/500Ω @ 1.2/50 μs impulse

Ordering information

MODEL – CURRENT – CALIBRATION – POWER – PROTOCOL – MOUNTING – MODULE

Model
Power versionPM130P-PLUS
Energy & harmonic versionPM130EH-PLUS
Energy onlyPM130E-PLUS
Current inputs
5 Ampere5
1 Ampere1
High Accuracy Current Sensors (HACS) — 100–3000A, requires 3× HACS ordered separatelyHACS
RS5 — remote split-core sensor, retrofit scheme underneath HACS, requires 3× RS5 HACS ordered separatelyRS5
Calibration frequency
25 Hz / 50 Hz / 60 Hz / 400 Hz25HZ / 50HZ / 60HZ / 400HZ
Power supply
85–265V AC / 85–290V DCACDC
9.5–18V DC1DC
18.5–58V DC (24VDC, 48VDC)23DC
Communication protocol
Modbus and DNP 3.0—
Modbus and IEC 60870-101/104870
Mounting
Panel mount (standard)—
DIN rail mountingDIN

Expansion module (max. 1 per instrument, order separately) — see Expansion modules below.

Expansion modules

Max. 1 per instrument, order separately.

Expansion module
4 Analogue Outputs: ±1mA / 0–20mA / 0–1mA / 4–20mA / 0–3mA / ±3mA / 0–5mA / ±5mAAO1–AO8
Ethernet (TCP/IP)ETH
PROFIBUSPRO
RS232/422/485RS232
4 Digital Inputs / 2 Relay Outputs, 250V/5A ACDIOR
4 Digital Inputs / 2 SSR Outputs, 250V/0.1A ACDIOS
TOU + 4 Digital InputsTOD
12 Digital Inputs (dry contact) / 4 Relay Outputs 250V/5A AC12DIOR-DRC
12 Digital Inputs (250VDC) / 4 Relay Outputs 250V/5A AC12DIOR-250V
12DIOR variants with Ethernet or RS-485 - optional…-ETH / …-485

Downloads and related