BFM136 · DATASHEET
BFM136 branch feeder monitor datasheet
Branch feeder monitor: up to 36 current circuits from a single device.
Transcribed from the SATEC Australia datasheet TBV1.0, 3 September 2026 (PDF, 7 pages, 232 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
SATEC’s BFM136 Branch Feeder Monitor™ is the solution in energy management metering for multi-point power solutions. Ideal for both new and retrofit projects, the BFM136 automatically provides metering, demand and energy readings, logging and multi-tariff (Time-of-Use) data for up to 36 circuits from a single compact device — perfect for multi-tenant facilities such as residential projects, office buildings, data centres and shopping malls.
The BFM136 monitors up to 36 currents via High Accuracy Current Sensors (HACS), each reporting the current consumed by a circuit at the panel board. Single or multiple circuits can be grouped per customer for billing, allowing simple reassignment without wiring changes as tenants move in and out. The BFM136’s user-defined, easily configured alarm system enables predictive maintenance action to avoid unnecessary outages.
Main features
- Monitors up to 12 three-phase, 18 two-phase or 36 single-phase circuits — or any combination — from a single device
- High Accuracy Current Sensors (HACS) rated from 100A to 3000A, each with a built-in automatic shorting protection circuit
- Voltage measurement range 120 (207) to 277 (480)V AC ±15%*, with an auto-ranging 88–552V AC power supply
- Built-in Time-of-Use (TOU) metering, stored on non-volatile memory to protect data against communication loss or power outage
- Standard Modbus RTU/TCP/ASCII communications and BACnet via RS-485 and Ethernet
- 8MB onboard data logging, plus automatic daily energy and maximum-demand profile logs
- 2×16 character local LCD display, with an optional RGM180 remote display
- Rugged, compact enclosure for wall or DIN-rail mounting; three-year warranty
Feature capabilities
Multi-point metering and logging
- Monitors up to 12 three-phase, 18 two-phase or 36 single-phase circuits, or any combination of single, two or three phase circuits
- Multi-point power, energy and demand data logging
- Local LCD display providing up to 36 channels of consumption readings for each tenant
Billing and Time-of-Use (TOU)
- TOU function stores energy consumption data according to the programmed time schedule, in compliance with the rates set by the local electricity supplier
- Daily energy tariff profile and maximum demands, programmable interval for load profile
- TOU information stored on non-volatile memory, protecting the data in case of communication loss or power outage
- Provides data for the assessment of penalty if the power factor falls below the level defined by the local electricity supplier
Data storage
- Real Time Clock (RTC) and Flash memory for data and event logging
- 8MB data logging capacity
- Logging for any type of parameter, for all profiles
Standard communication platforms
- Protocols: Modbus RTU, Modbus TCP/IP, Modbus ASCII, BACnet
- Standard RS-485 port
- Standard Ethernet TCP/IP
- Operates as up to 36 separate Modbus slaves for simple integration
Current and voltage inputs
- 36 current inputs per device, measured per phase with unique High Accuracy Current Sensors (HACS) rating from 100A to 3000A
- Voltage measurement range*: 120 (207) to 277 (480)V AC ±15%
- Auto-ranging power supply: 88–552V AC
Alarms and diagnostics
- User-defined and easily configured alarm system enables predictive maintenance action to avoid unnecessary outages
- Alarm configuration: over/under voltage, over current, over kVA, over/under frequency
- Self-diagnostic test, with password protection per meter
Software integration — PAS
- SATEC PAS (Power Analysis Software) provides real-time access to data, a downloading scheduler and automatic export to .mdb files for MS Access, MS Excel and database integration
- Remote setup and data viewing and analysis, including energy daily profile
Building management systems
- Open Modbus and BACnet protocols allow interfacing with any system, such as Building Management, HMI and more
- The BFM136 operates as up to 36 separated Modbus slaves for simple integration
Expertpower web service
- Expertpower is SATEC's web-based energy management system for automated monitoring, complete billing service and advanced analysis
- Delivers total visibility for entire power systems over the Internet
- Provides alarms, power diagrams, power profiles and demands, events logging, history, graphs and waveforms
Design and installation
- Compact design engineered to fit easily into existing panel boards, or be flush mounted nearby
- Wall or DIN rail mounting
- 2×16 characters local display; optional RGM180 remote display
- Three-year warranty
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
| Nominal frequency | 50/60Hz (order-selectable) |
|---|
| Wiring | 4 wires: 3 phases + neutral |
|---|---|
| Maximum line-to-neutral voltage | 320V |
| Maximum line-to-line voltage | 552V |
| Burden per phase | <1.5W |
| Isolation | 2.5kV RMS, 60Hz, 1 min — Impulse 6kV |
| PT ratio | 1–6500 |
| Current circuits | 36 per device |
|---|---|
| Nominal current | 50% of HACS rating |
| Maximum input direct current | 100% of HACS rating |
| Maximum momentary overcurrent | 3000% of HACS rating |
| Burden per phase | <0.1VA |
| Isolation | 2.5kV RMS, 60Hz, 1 min |
| Primary current range | 1–10,000A |
| Current sensors | Requires High Accuracy Current Sensors (HACS), 100–3000A rating — see the HACS datasheet |
| LCD display | 2 rows, 16 digits each |
|---|---|
| Push buttons | 4 |
| Non-volatile memory storage life | 20 years |
| RTC storage upon loss of power | 24 hours minimum, 1 week typical |
| Voltage input terminals | 10 AWG max. |
| Weight | 1.85 kg |
| Dimensions (H×W×D) | 4.2×13×2.3″ / 107×331×58mm |
| Mounting | Wall or DIN rail |
| Operating temperature | -20°C to 60°C (-4°F to 140°F) |
|---|---|
| Storage temperature | -25°C to 80°C (-13°F to 176°F) |
| Humidity | 0 to 95% non-condensing |
| Port | Built-in RS-485 and Ethernet |
|---|---|
| Protocols | Modbus RTU, Modbus TCP/IP, Modbus ASCII, BACnet |
| Addressing | Up to 36 separate Modbus slaves per device |
| Voltage | 0.3% reading + 0.05% FS (184–260V, VL=230V FS) |
|---|---|
| Line current | 0.5% reading + 0.05% FS (Instrument HACS, IL=100%) |
| Active / reactive / apparent power | 0.5S/1% reading + 0.02% FS |
| Power factor | 1.0% (|PF|≥0.5, I≥2% FSI) |
| Active energy | Class 0.5S per AS/IEC 62053-22:2003 |
| Reactive energy | Class 1 per AS/IEC 62053-21:2003 (|PF|≤0.9) |
| Apparent energy | Class 1 per AS/IEC 62053-21:2003 |
Accuracy expressed as (% of reading + % of full scale) ± 1 digit; does not include inaccuracies introduced by user potential/current transformers. Assumes voltage and current THD ≤5% for kVAr, kVA and PF; reference operating temperature 20–26°C.
| Local display | 2×16 character LCD |
|---|---|
| Remote display | Optional RGM180 |
| Energy (per submeter) | Import/export active, reactive & apparent energy totals; 6-tariff TOU energy |
|---|---|
| Average values (per feeder) | Voltage, current, angles, kW, kVAr, kVA, power factor, frequency & neutral current, per phase and per submeter |
| Present & maximum demand | Volts, amperes, kW, kVAr and kVA per phase and per submeter; 6-tariff demand per submeter |
| Service | Self-diagnostic test, password per meter, serial number, software version, COM1 & COM2 ID, current direction |
Standards compliance
Accuracy
- Complies with AS/IEC 62052-11:2003
- Complies with AS/IEC 62053-22:2003, Class 0.5S
- Meets ANSI C12.20-1998, Class 0.5
Electromagnetic immunity
- IEC 61000-4-2:1995 — Electrostatic discharge
- IEC 61000-4-3:2002 — Radiated electromagnetic RF fields
- IEC 61000-4-4:1995 — Fast transient
- IEC 61000-4-5:1995 — Conductive surge
- IEC 61000-4-6:1996 — Conducted disturbance
- IEC 61000-4-11:1994 — Voltage dip / interruption
Electromagnetic emission
- EN 61000-3-2:2000 — Limits for harmonic current emissions
- EN 61000-3-3:1995 — Limits of voltage changes, fluctuations and flicker
Safety
- Complies with AS 62052-31
- Complies with UL 61010-1:2003
Approvals in Australia
- NMI pattern approval 14/2/80 Rev 3: Satec Model BFM136 Class 1 Electricity Meter.
Ordering information
BFM136-N-NMI-50HZ-ETH-S-CC
Downloads and related
- Download the datasheet (PDF, TBV1.0, 232 KB)
- Read the PDF in the document library