BFM136 · DATASHEET

BFM136 branch feeder monitor datasheet

Branch feeder monitor: up to 36 current circuits from a single device.

Transcribed from the SATEC Australia datasheet TBV1.0, 3 September 2026 (PDF, 7 pages, 232 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

SATEC’s BFM136 Branch Feeder Monitor™ is the solution in energy management metering for multi-point power solutions. Ideal for both new and retrofit projects, the BFM136 automatically provides metering, demand and energy readings, logging and multi-tariff (Time-of-Use) data for up to 36 circuits from a single compact device — perfect for multi-tenant facilities such as residential projects, office buildings, data centres and shopping malls.

The BFM136 monitors up to 36 currents via High Accuracy Current Sensors (HACS), each reporting the current consumed by a circuit at the panel board. Single or multiple circuits can be grouped per customer for billing, allowing simple reassignment without wiring changes as tenants move in and out. The BFM136’s user-defined, easily configured alarm system enables predictive maintenance action to avoid unnecessary outages.

Main features

Feature capabilities

Multi-point metering and logging

  • Monitors up to 12 three-phase, 18 two-phase or 36 single-phase circuits, or any combination of single, two or three phase circuits
  • Multi-point power, energy and demand data logging
  • Local LCD display providing up to 36 channels of consumption readings for each tenant

Billing and Time-of-Use (TOU)

  • TOU function stores energy consumption data according to the programmed time schedule, in compliance with the rates set by the local electricity supplier
  • Daily energy tariff profile and maximum demands, programmable interval for load profile
  • TOU information stored on non-volatile memory, protecting the data in case of communication loss or power outage
  • Provides data for the assessment of penalty if the power factor falls below the level defined by the local electricity supplier

Data storage

  • Real Time Clock (RTC) and Flash memory for data and event logging
  • 8MB data logging capacity
  • Logging for any type of parameter, for all profiles

Standard communication platforms

  • Protocols: Modbus RTU, Modbus TCP/IP, Modbus ASCII, BACnet
  • Standard RS-485 port
  • Standard Ethernet TCP/IP
  • Operates as up to 36 separate Modbus slaves for simple integration

Current and voltage inputs

  • 36 current inputs per device, measured per phase with unique High Accuracy Current Sensors (HACS) rating from 100A to 3000A
  • Voltage measurement range*: 120 (207) to 277 (480)V AC ±15%
  • Auto-ranging power supply: 88–552V AC

Alarms and diagnostics

  • User-defined and easily configured alarm system enables predictive maintenance action to avoid unnecessary outages
  • Alarm configuration: over/under voltage, over current, over kVA, over/under frequency
  • Self-diagnostic test, with password protection per meter

Software integration — PAS

  • SATEC PAS (Power Analysis Software) provides real-time access to data, a downloading scheduler and automatic export to .mdb files for MS Access, MS Excel and database integration
  • Remote setup and data viewing and analysis, including energy daily profile

Building management systems

  • Open Modbus and BACnet protocols allow interfacing with any system, such as Building Management, HMI and more
  • The BFM136 operates as up to 36 separated Modbus slaves for simple integration

Expertpower web service

  • Expertpower is SATEC's web-based energy management system for automated monitoring, complete billing service and advanced analysis
  • Delivers total visibility for entire power systems over the Internet
  • Provides alarms, power diagrams, power profiles and demands, events logging, history, graphs and waveforms

Design and installation

  • Compact design engineered to fit easily into existing panel boards, or be flush mounted nearby
  • Wall or DIN rail mounting
  • 2×16 characters local display; optional RGM180 remote display
  • Three-year warranty

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Input ratings — general
Nominal frequency50/60Hz (order-selectable)
AC voltage
Wiring4 wires: 3 phases + neutral
Maximum line-to-neutral voltage320V
Maximum line-to-line voltage552V
Burden per phase<1.5W
Isolation2.5kV RMS, 60Hz, 1 min — Impulse 6kV
PT ratio1–6500
AC current
Current circuits36 per device
Nominal current50% of HACS rating
Maximum input direct current100% of HACS rating
Maximum momentary overcurrent3000% of HACS rating
Burden per phase<0.1VA
Isolation2.5kV RMS, 60Hz, 1 min
Primary current range1–10,000A
Current sensorsRequires High Accuracy Current Sensors (HACS), 100–3000A rating — see the HACS datasheet
Hardware
LCD display2 rows, 16 digits each
Push buttons4
Non-volatile memory storage life20 years
RTC storage upon loss of power24 hours minimum, 1 week typical
Voltage input terminals10 AWG max.
Weight1.85 kg
Dimensions (H×W×D)4.2×13×2.3″ / 107×331×58mm
MountingWall or DIN rail
Environmental conditions
Operating temperature-20°C to 60°C (-4°F to 140°F)
Storage temperature-25°C to 80°C (-13°F to 176°F)
Humidity0 to 95% non-condensing
Communication — COM1 and COM2 (standard)
PortBuilt-in RS-485 and Ethernet
ProtocolsModbus RTU, Modbus TCP/IP, Modbus ASCII, BACnet
AddressingUp to 36 separate Modbus slaves per device
Measurement accuracy
Voltage0.3% reading + 0.05% FS (184–260V, VL=230V FS)
Line current0.5% reading + 0.05% FS (Instrument HACS, IL=100%)
Active / reactive / apparent power0.5S/1% reading + 0.02% FS
Power factor1.0% (|PF|≥0.5, I≥2% FSI)
Active energyClass 0.5S per AS/IEC 62053-22:2003
Reactive energyClass 1 per AS/IEC 62053-21:2003 (|PF|≤0.9)
Apparent energyClass 1 per AS/IEC 62053-21:2003

Accuracy expressed as (% of reading + % of full scale) ± 1 digit; does not include inaccuracies introduced by user potential/current transformers. Assumes voltage and current THD ≤5% for kVAr, kVA and PF; reference operating temperature 20–26°C.

Display module
Local display2×16 character LCD
Remote displayOptional RGM180
Measured parameters
Energy (per submeter)Import/export active, reactive & apparent energy totals; 6-tariff TOU energy
Average values (per feeder)Voltage, current, angles, kW, kVAr, kVA, power factor, frequency & neutral current, per phase and per submeter
Present & maximum demandVolts, amperes, kW, kVAr and kVA per phase and per submeter; 6-tariff demand per submeter
ServiceSelf-diagnostic test, password per meter, serial number, software version, COM1 & COM2 ID, current direction

Standards compliance

Accuracy

  • Complies with AS/IEC 62052-11:2003
  • Complies with AS/IEC 62053-22:2003, Class 0.5S
  • Meets ANSI C12.20-1998, Class 0.5

Electromagnetic immunity

  • IEC 61000-4-2:1995 — Electrostatic discharge
  • IEC 61000-4-3:2002 — Radiated electromagnetic RF fields
  • IEC 61000-4-4:1995 — Fast transient
  • IEC 61000-4-5:1995 — Conductive surge
  • IEC 61000-4-6:1996 — Conducted disturbance
  • IEC 61000-4-11:1994 — Voltage dip / interruption

Electromagnetic emission

  • EN 61000-3-2:2000 — Limits for harmonic current emissions
  • EN 61000-3-3:1995 — Limits of voltage changes, fluctuations and flicker

Safety

  • Complies with AS 62052-31
  • Complies with UL 61010-1:2003

Approvals in Australia