BFM-II DFR · DATASHEET

BFM-II DFR multi-feeder power monitor and digital fault recorder datasheet

Multi-Feeder Power Monitor and Digital Fault Recorder.

Transcribed from the SATEC Australia datasheet TBV1.1, 16 September 2026 (PDF, 8 pages, 1322 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The BFM-II DFR is a multi-feeder power monitor and digital fault recorder built for utility distribution substations. A single device monitors six, eight or up to twelve three-phase feeders on a common bus voltage. It connects to the existing CTs and PTs alongside legacy electromechanical protection relays, so it adds measurement and automation data without interfering with the protection scheme.

A modular design supports clip-on current sensors, plug-in digital and analogue I/O, relay outputs and an optional cellular modem. RS-485, Ethernet and USB ports are standard, with Modbus, DNP 3.0 and BACnet support. An integrated graphical touch screen, 256 MB of onboard memory and a universal AC/DC auxiliary supply complete the package.

Main features

Feature capabilities

Digital fault recording

  • Pre-fault and post-fault waveform capture on recorded events
  • Event records and captured waveforms viewed through Power Analysis Software (PAS)
  • Waveform export to COMTRADE format for third-party fault analysis tools
  • 256 MB of onboard memory for long-term event and waveform storage

Multi-feeder power monitoring

  • Six, eight or up to twelve three-phase feeders on a common bus voltage
  • True RMS volts, amps, active, reactive and apparent power, power factor and frequency
  • Per-phase as well as total measurement for most parameters
  • Hundreds of parameters measured on each load through advanced digital signal processing

Power quality monitoring

  • Voltage and current harmonic measurement
  • Total harmonic distortion on voltage and current
  • Detailed harmonic capture with direction, viewed in PAS

Energy measurement and accuracy

  • Class 0.5S energy accuracy to AS/IEC 62053-22
  • ANSI C12.20-2010, Class 100 and Class 400, accuracy 0.2%
  • Three-phase and per-phase energy measurement on every monitored feeder
  • Accuracy held across an operational ambient range of −25 °C to +60 °C

Retrofit without an outage

  • Clip-on current sensors fit onto existing 5 A secondary circuits
  • Non-intrusive to the protection relays, with no change to the protection scheme
  • Ultra low burden, up to 20 x 5 A (100 A) maximum
  • CS1S split-core sensor with a 16 mm (0.63 in) opening and a 2.5 m cable
  • Sensors can be located up to 274 m (900 ft) from the meter
  • An entire substation can be updated in a single day

Display options

  • Integrated 3.5 inch touch-panel LCD graphic TFT display at 320 x 240
  • View each circuit one at a time, with a programmable screen saver
  • Optional RGM-180 remote display with a 5.7 inch touch colour screen
  • Remote display connects over Ethernet or serial

Communications

  • COM1: optically isolated RS-485 up to 115,200 bps, Modbus RTU/ASCII and DNP 3.0
  • Ethernet: transformer-isolated 10/100Base-T with Modbus TCP (502), DNP3/TCP (20000) and BACnet
  • Up to five simultaneous Ethernet connections, with SNTP time synchronisation
  • Isolated USB 1.1 port for local connection over Modbus RTU
  • Optional cellular modem with a second RS-422/485 communications port

Plug-in I/O modules — maximum 2 modules per device

  • 18 optically isolated digital inputs, dry contact or 24, 48, 125 and 250 VDC variants
  • Nine SPST Form A relay outputs rated 5 A at 250 VAC or 5 A at 30 VDC
  • Four optically isolated analogue inputs with 0.5% FS accuracy
  • Current input modules in six-channel and eighteen-channel versions

Data recording and timekeeping

  • 256 Mbytes of standard onboard memory
  • Real-time clock accurate to better than 5 seconds per month at 25 °C
  • Event, trend and waveform logs retrieved over any communications port

Software support

  • Power Analysis Software (PAS) configures the device and monitors real-time data, and is bundled with every SATEC device at no charge
  • Expertpower is SATEC's browser-based energy management, billing and power quality platform, with no client software to install
  • The eXpertConnect™ App gives mobile access to energy, demand and cost data drawn from Expertpower

Installation

  • DIN rail or enclosure installation
  • Universal auxiliary power supply for AC or DC operation
  • Removable plug-in connectors throughout for straightforward commissioning
  • Installation requires no outage on the monitored circuits

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Environmental conditions
Operating temperature−30 °C to +70 °C (−22 °F to 158 °F)
Storage temperature−40 °C to +85 °C (−40 °F to 185 °F)
Humidity0 to 95% RH, non-condensing
Altitude≤ 2000 m
Construction
Width278 mm (18 channels) to 554 mm (54 channels)
Height128 mm
Depth72.5 mm
Weight1.6 kg (36 channels)
Materials
Enclosure & panelsPolycarbonate
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
Packaging caseCarton and Stratocell polyethylene foam brackets
LabelsPolyester film (UL94-V0)
Power supply
ConfigurationThree-phase supply, 1, 2 or 3-phase operation, 3 x 120/208 to 277/480 VAC
Input range50 to 290 VAC / 40 to 290 VDC, 50/60 Hz
Max. power10 W
Burden at 277 V< 17 VA
Withstand insulation4 kV AC at 1 min
Wire sizeUp to 10 AWG (up to 6 mm²)
Terminal pitch10 mm, 4 pins plus signal ground stud
AC voltage inputs (V1, V2, V3, VN)
Measuring range3 x 120/208 to 277/480 VAC
Input impedance10 MΩ
Burden at 277 V≈ 0.08 VA
Burden at 120 V≈ 0.02 VA
Galvanic isolation4 kV AC at 1 min
Connector typeRemovable, 4 terminals
Wire sizeUp to 10 AWG (up to 6 mm²)
Terminal pitch10 mm
AC current inputs I1–I36 — standard HACS
InputVia SATEC HACS, 100 A to 3000 A
Operating rangeMaximum continuous 120% of I max, 120 A for HACS 100 A
Nominal measured current50 A RMS (HACS 100 A)
Burden< 0.15 VA
Overload withstand100 A RMS continuous
Connector typeRemovable, 6 terminals for 3 current inputs
Wire size10 AWG (2.5 to 6 mm²)
Terminal pitch5 mm
AC current inputs I1–I36 — optional RS5
InputVia SATEC HACS CS05S
Operating rangeMaximum continuous 20 A primary current
Nominal measured current5 A RMS primary current
Burden< 0.15 VA
Overload withstand12 A RMS continuous
Connector typeRemovable, 6 terminals for 3 current inputs
Wire size10 AWG (2.5 to 6 mm²)
Terminal pitch5 mm
Plug-in digital inputs — 18 DI
TypeOptically isolated, dry contact sensing (voltage-free)
Internal power supply5 VDC
SensitivityOpen at input resistance > 16 kΩ, closed at < 10 kΩ
Scan time½ cycle
Withstand insulation4 kV AC at 1 min
Wire size12 AWG (up to 2.5 mm²)
Terminal pitch3.81 mm
Plug-in analogue inputs — 4 AI
Ranges (on order)±1 mA (100% overload), 0 to 20 mA, 4 to 20 mA, 0 to 1 mA (100% overload)
Accuracy0.5% FS
Scan time2 cycles
Withstand insulation4 kV AC at 1 min
Wire size28 to 16 AWG (0.1 to 1.5 mm²), 600 V isolation
Terminal pitch3.81 mm
Relay outputs
Type9 relays, SPST Form A
Contact rating5 A at 250 VAC, 5 A at 30 VDC
Update time1 cycle
Recommended wire size18 AWG (1 mm²), 600 V isolation
Terminal pitch3.81 mm
Current sensors
CS1S split-core100 A, 16 mm (0.63 in) inner diameter, 2.5 m cable
RatingUp to 20 x 5 A (100 A) maximum
Real-time clock and memory
Clock accuracyBetter than 5 s/month at 25 °C
Onboard memory256 Mbytes standard
Display modules
GDM (option)3.5 inch touch-panel LCD graphic TFT, 320 x 240, serial TTL RS-232 non-isolated
GDM operating temp.−20 °C to +70 °C
RGM-180 (option)5.7 inch touch colour remote display, Ethernet or serial interface, programmable screen saver
COM1 — RS-485 (standard, MCM)
PortSerial EIA RS-485, optically isolated
Withstand insulation4 kV AC at 1 min
Baud rateUp to 115,200 bps
ProtocolsModbus RTU/ASCII, DNP 3.0
Connector typeRemovable, 3 terminals
Wire sizeUp to 12 AWG (up to 2.5 mm²)
Terminal pitch5 mm
COM3 — display port (standard, MCM)
PortSerial TTL RS-232, non-isolated, for the GDM
Baud rateUp to 460,800 bps
ProtocolsModbus RTU
USB port (standard, MCM)
PortIsolated USB 1.1
Withstand insulation4 kV AC at 1 min
Connector typeA male, standard USB cable, max. length 2 m
ProtocolsModbus RTU
Ethernet port (standard, MCM)
PortTransformer-isolated 10/100Base-T
Withstand insulation4 kV AC at 1 min
Connector typeRJ45 modular
ProtocolsModbus TCP (502), DNP3/TCP (20000), BACnet
Simultaneous connections5 sockets
Time synchronisationSNTP
Cellular modem (optional module)
TechnologyCellular modem, technology selected on order
Withstand insulation4 kV AC at 1 min
Connector typeSMA
ProtocolsModbus TCP (502), DNP 3.0/TCP (20000)

Standards compliance

Accuracy

  • Complies with AS/IEC 62053-22, Class 0.5S
  • Meets ANSI C12.20-2010, Class 100 and Class 400, accuracy 0.2%

Electromagnetic compatibility

  • Complies with AS/IEC 62052-11, AS/IEC 62053-22, ANSI C12.1 and ANSI C12.20
  • IEC 61000-4-2: electrostatic discharge, air and contact
  • IEC 61000-4-3: electromagnetic RF fields, 10 V/m at 80 MHz to 1000 MHz
  • IEC 61000-4-4: fast transient burst, 4 kV on current and voltage circuits, 2 kV on auxiliary circuits
  • IEC 61000-4-5: surge, 6 kV on current and voltage circuits, 1 kV on auxiliary circuits
  • IEC 61000-4-6: conducted radio frequency, 10 V at 0.15 MHz to 80 MHz
  • IEC 61000-4-8: power frequency magnetic field
  • IEC 61000-4-12: damped oscillatory waves, 2.5 kV common mode and 1 kV differential mode
  • CISPR 22, Class B

Surge and transient withstand

  • ANSI C12.1 clause 4.7.3.3.1: 100 kHz ring wave surge, 6 kV at 0.5 kA, per IEEE C62.41.2-2002
  • ANSI C12.1 clause 4.7.3.3.2: line surge 1.2/50 µs and 8/20 µs, 6 kV at 3 kA, per IEEE C62.41.2-2002
  • ANSI C12.1 clause 4.7.3.11: surge withstand capability 2.5 kV, per IEEE C37.90.1

Insulation

  • AS/IEC 62052-11: insulation impulse 12 kV/50Ω at 1.2/50 µs
  • AS/IEC 62053-22: AC voltage tests related to ground, 4 kV AC at 1 min for power and signal ports above 40 V
  • Alternatively per UL 61010-1 and UL 916 for basic and double insulation, Installation Category III

Safety

  • Meets UL 916

Atmospheric environment

  • Accuracy operational ambient temperature range: −25 °C to +60 °C
  • Operational ambient temperature range: −40 °C to +70 °C
  • Long-term damp heat withstand per IEC 68-2-3, below 95% non-condensing at +40 °C
  • Transport and storage temperature range: −40 °C to +85 °C
  • IEC 60529: IP50

Vibration and shock

  • AS/IEC 62052-11, referencing IEC 60068-2-6: vibration 10 Hz to 150 Hz, transition frequency 60 Hz, constant movement amplitude 0.075 mm below 60 Hz, constant acceleration 9.8 m/s² (1 g) above 60 Hz
  • AS/IEC 62052-11, referencing IEC 60068-2-27: shock, half sine pulse, peak acceleration 30 gn (300 m/s²)
  • Transport vibration and shock: longitudinal 2.0 g, vertical 1.2 g, transversal 1.2 g

Ordering information

MODEL – POWER SUPPLY – FEEDER COUNT – FREQUENCY – CURRENT SENSOR – MODULE

BFM-II DFR multi-feeder monitor
6-Feeder Monitor. Monitors six three-phase feeders on a common bus voltage via clip-on current sensors for 5 A secondary circuitsBFM-II-DFR-ACDC-6F
8-Feeder Monitor. Monitors eight three-phase feeders on a common bus voltage via clip-on current sensors for 5 A secondary circuitsBFM-II-DFR-ACDC-8F
12-Feeder Monitor. Monitors twelve three-phase feeders on a common bus voltage via clip-on current sensors for 5 A secondary circuitsBFM-II-DFR-ACDC-12F
Frequency
50 Hz50HZ
60 Hz60HZ
Current sensors
100 A split-core current sensor. Inner diameter 16 mm (0.63 in), cable length 2.5 mCS1S
Digital input and output modules — ordered separately
18 Digital Input Module, dry contactDI18-DRC-BFM II
18 Digital Input Module, 24 VDCDI18-24V-BFM II
18 Digital Input Module, 48 VDCDI18-48V-BFM II
18 Digital Input Module, 125 VDCDI18-125V-BFM II
18 Digital Input Module, 250 VDCDI18-250V-BFM II
9-channel Relay Output Module. Maximum 2 modules per deviceRLY9-BFM II
Analogue input modules — ordered separately
4AI Module, ±1 mA. Four optically isolated analogue inputsAI1-BFM II
4AI Module, 0 to 20 mA. Four optically isolated analogue inputsAI2-BFM II
4AI Module, 0 to 1 mA. Four optically isolated analogue inputsAI3-BFM II
4AI Module, 4 to 20 mA. Four optically isolated analogue inputsAI4-BFM II
Current input modules — up to 2 per instrument
CIM 6, six-channel current input moduleC6H
CIM 18, eighteen-channel current input moduleC18H
CIM 6 for measuring with 5 A secondaryC6-RS5
CIM 18 for measuring with 5 A secondaryC18-RS5
Communication modules
None0
4G modem plus a second RS-422/485 communications portT4G-BFM-II