BFM-II DFR multi-feeder power monitor and digital fault recorder datasheet
Multi-Feeder Power Monitor and Digital Fault Recorder.
Transcribed from the SATEC Australia datasheet TBV1.1, 16 September 2026 (PDF, 8 pages, 1322 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The BFM-II DFR is a multi-feeder power monitor and digital fault recorder built for utility distribution substations. A single device monitors six, eight or up to twelve three-phase feeders on a common bus voltage. It connects to the existing CTs and PTs alongside legacy electromechanical protection relays, so it adds measurement and automation data without interfering with the protection scheme.
A modular design supports clip-on current sensors, plug-in digital and analogue I/O, relay outputs and an optional cellular modem. RS-485, Ethernet and USB ports are standard, with Modbus, DNP 3.0 and BACnet support. An integrated graphical touch screen, 256 MB of onboard memory and a universal AC/DC auxiliary supply complete the package.
Main features
Monitors six, eight or up to twelve three-phase feeders in a single device
True RMS volts, amps, active, reactive and apparent power, power factor, frequency and THD
Per-phase and total measurement for most parameters
Power quality monitoring of voltage and current harmonics
Digital fault recording with pre-fault and post-fault waveform capture
Class 0.5S accuracy to AS/IEC 62053-22 and 0.2% to ANSI C12.20
256 MB of onboard memory for event, waveform and data logs
Standard RS-485, Ethernet and USB ports, with an optional cellular modem
Modbus RTU/ASCII, DNP 3.0 and BACnet protocol support
Integrated graphical touch screen, with an optional remote display
DIN rail or enclosure installation
Universal auxiliary supply, 50 to 290 VAC or 40 to 290 VDC
Feature capabilities
Digital fault recording
Pre-fault and post-fault waveform capture on recorded events
Event records and captured waveforms viewed through Power Analysis Software (PAS)
Waveform export to COMTRADE format for third-party fault analysis tools
256 MB of onboard memory for long-term event and waveform storage
Multi-feeder power monitoring
Six, eight or up to twelve three-phase feeders on a common bus voltage
True RMS volts, amps, active, reactive and apparent power, power factor and frequency
Per-phase as well as total measurement for most parameters
Hundreds of parameters measured on each load through advanced digital signal processing
Power quality monitoring
Voltage and current harmonic measurement
Total harmonic distortion on voltage and current
Detailed harmonic capture with direction, viewed in PAS
Energy measurement and accuracy
Class 0.5S energy accuracy to AS/IEC 62053-22
ANSI C12.20-2010, Class 100 and Class 400, accuracy 0.2%
Three-phase and per-phase energy measurement on every monitored feeder
Accuracy held across an operational ambient range of −25 °C to +60 °C
Retrofit without an outage
Clip-on current sensors fit onto existing 5 A secondary circuits
Non-intrusive to the protection relays, with no change to the protection scheme
Ultra low burden, up to 20 x 5 A (100 A) maximum
CS1S split-core sensor with a 16 mm (0.63 in) opening and a 2.5 m cable
Sensors can be located up to 274 m (900 ft) from the meter
An entire substation can be updated in a single day
Display options
Integrated 3.5 inch touch-panel LCD graphic TFT display at 320 x 240
View each circuit one at a time, with a programmable screen saver
Optional RGM-180 remote display with a 5.7 inch touch colour screen
Remote display connects over Ethernet or serial
Communications
COM1: optically isolated RS-485 up to 115,200 bps, Modbus RTU/ASCII and DNP 3.0
Ethernet: transformer-isolated 10/100Base-T with Modbus TCP (502), DNP3/TCP (20000) and BACnet
Up to five simultaneous Ethernet connections, with SNTP time synchronisation
Isolated USB 1.1 port for local connection over Modbus RTU
Optional cellular modem with a second RS-422/485 communications port
Plug-in I/O modules — maximum 2 modules per device
18 optically isolated digital inputs, dry contact or 24, 48, 125 and 250 VDC variants
Nine SPST Form A relay outputs rated 5 A at 250 VAC or 5 A at 30 VDC
Four optically isolated analogue inputs with 0.5% FS accuracy
Current input modules in six-channel and eighteen-channel versions
Data recording and timekeeping
256 Mbytes of standard onboard memory
Real-time clock accurate to better than 5 seconds per month at 25 °C
Event, trend and waveform logs retrieved over any communications port
Software support
Power Analysis Software (PAS) configures the device and monitors real-time data, and is bundled with every SATEC device at no charge
Expertpower is SATEC's browser-based energy management, billing and power quality platform, with no client software to install
The eXpertConnect™ App gives mobile access to energy, demand and cost data drawn from Expertpower
Installation
DIN rail or enclosure installation
Universal auxiliary power supply for AC or DC operation
Removable plug-in connectors throughout for straightforward commissioning
Installation requires no outage on the monitored circuits
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
Environmental conditions
Operating temperature
−30 °C to +70 °C (−22 °F to 158 °F)
Storage temperature
−40 °C to +85 °C (−40 °F to 185 °F)
Humidity
0 to 95% RH, non-condensing
Altitude
≤ 2000 m
Construction
Width
278 mm (18 channels) to 554 mm (54 channels)
Height
128 mm
Depth
72.5 mm
Weight
1.6 kg (36 channels)
Materials
Enclosure & panels
Polycarbonate
PCB
FR4 (UL94-V0)
Terminals
PBT (UL94-V0)
Plug-in connectors
Polyamide PA6.6 (UL94-V0)
Packaging case
Carton and Stratocell polyethylene foam brackets
Labels
Polyester film (UL94-V0)
Power supply
Configuration
Three-phase supply, 1, 2 or 3-phase operation, 3 x 120/208 to 277/480 VAC
Input range
50 to 290 VAC / 40 to 290 VDC, 50/60 Hz
Max. power
10 W
Burden at 277 V
< 17 VA
Withstand insulation
4 kV AC at 1 min
Wire size
Up to 10 AWG (up to 6 mm²)
Terminal pitch
10 mm, 4 pins plus signal ground stud
AC voltage inputs (V1, V2, V3, VN)
Measuring range
3 x 120/208 to 277/480 VAC
Input impedance
10 MΩ
Burden at 277 V
≈ 0.08 VA
Burden at 120 V
≈ 0.02 VA
Galvanic isolation
4 kV AC at 1 min
Connector type
Removable, 4 terminals
Wire size
Up to 10 AWG (up to 6 mm²)
Terminal pitch
10 mm
AC current inputs I1–I36 — standard HACS
Input
Via SATEC HACS, 100 A to 3000 A
Operating range
Maximum continuous 120% of I max, 120 A for HACS 100 A