PM335 PRO · WIRING DIAGRAM

Which PM335 PRO wiring diagram applies to my installation?

PM335 PRO product photograph
PM335 PRO product photograph from SATEC's product photo library

Quick answer

Table 3, Wiring Configurations, on page 31 of the EM235/PM335 PRO manual lists eight wiring configurations. Each has a setup code and a figure, Figures 2-11 to 2-18. The PM335 typical installation drawing is Figure 2-8a on page 24.

SATEC Australia's advice:

  • Pick the Table 3 row that matches your circuit, whether potential transformers (PTs) are used, and the number of CTs.
  • Set the same wiring mode in Basic Setup.
  • Go by the table. Some of the text before Table 3 gives figure numbers that don't match it.

Applies to

This page covers the standard PM335 PRO, the panel-mounted model with a 3.5-inch colour display.

The manual's wiring figures are shared between the EM235 PRO and PM335 PRO. Figure 2-8a is the PM335 typical installation drawing.

The page doesn't cover the display-less transducer version, FCAS variants, medium-voltage sensor interfaces or DC metering set-ups.

Before you choose: check the label

The manual says: "Before connecting the instrument to the power source, check the labels at the front of the instrument to ensure that your instrument is equipped with the appropriate rating input voltages and currents."

The quick start gives separate instructions for standard CTs and HACS CTs:

  • Standard external CTs: "connect the CT's (14 AWG minimum) "+" pole to the device's I1+ current input ... and the "-" pole to the adjacent I1- current input. Repeat this for the following two phases, I2 and I3. Verify proper polarity in your connections in accordance with the arrow printed on the external CTs."
  • "HACS" CTs: "connect the red/white wire to the "+" terminal and the black/orange (colors vary according to the CT model) wire to the "-" terminal."

The manual covers the medium-voltage sensor interfaces (GWP and Lindsey) and the PTS installation on pages 16, 26–27 and 36–37. The order string also lists FLEX ("3V AC inputs for Rogowski current clamps") and LPCT current-input options.

SATEC Australia's advice: for FLEX or LPCT inputs, contact technical support for the wiring.

The manual describes "3 input currents for 3P system monitoring (optional 4th channel)".

Table 3: Wiring Configurations

Wiring ConfigurationSetup CodeFigure
3-wire 2-element Delta direct connection using 2 CTs3dir22-11
4-wire 3-element Wye direct connection using 3 CTs4LN32-12
4-wire 3-element Wye connection using 3 PTs, 3 CTs4Ln3 or 4LL32-13
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs3OP22-14
4-wire 2½-element Wye connection using 2 PTs, 3 CTs3Ln3 or 3LL32-15
3-wire 2½-element Open Delta connection using 2 PTs, 3 CTs3OP32-16
4-wire 3-element Delta direct connection using 3 CTs4LL32-17
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs3bLn3 or 3bLL32-18

Source: BG0612 Rev. A8, Table 3, page 31. Figures 2-11 to 2-18 are on pages 32–35.

Points from the manual:

  • Table 9 describes 4LN3 as "4-wire Wye using 3 PTs (3 element), line-to-neutral voltage readings" and 4LL3 as "4-wire Wye using 3 PTs (3 element), line-to-line voltage readings".
  • The note to Table 9 says: "In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltage readings for min/max volts and volt demands represent line-to-neutral voltages; otherwise, they will be line-to-line voltages."
  • Figure 2-15 says: "This configuration provides accurate power measurements only if the voltages are balanced."
  • 4LL3 appears against both Figure 2-13 (wye with PTs) and Figure 2-17 (4-wire delta direct connection). The caption of Figure 2-17 reads "(Wiring Mode = 4LL3 or 4Ln3)".

SATEC Australia's advice: if your installation is a 4-wire delta, contact technical support before you set the mode.

The PM335 typical installation

Figure 2-8a on page 24 shows:

  • the supply through a 2 A switch (SW1);
  • the voltage inputs through a 2 A switch (SW2);
  • the I1, I2 and I3 CTs through a shorting-switch block;
  • a fourth CT, on the neutral, wired straight to a separate I4+/I4− terminal block, drawn without a shorting switch;
  • RS-485 to a PC, marked "Up to 31 devices";
  • the built-in digital input, analogue input and relay output connections.

The PM335 quick start places the terminals as follows:

  • power supply: "bottom-left of back panel";
  • CT inputs: "bottom right of rear end";
  • voltage inputs: "bottom-center of rear end";
  • COM1 (RS-485): "top-left of rear-end".

Figure 2-9b on page 25 is the EM235 typical installation drawing.

The supply range printed on the typical drawings differs from the datasheet's figures. SATEC Australia's advice: take the supply rating from your meter's label.

Safety points from the manual

  • The quick start says: "Make sure all power sources are disconnected."
  • The external current transformer secondary "must never be allowed to be open circuit when the primary is energized". The typical installation drawing shows shorting switches for I1–I3 only; its I4 CT is drawn without one. The manual's note about the open-circuit CT secondary applies to every external CT, I4 included.
  • "It is required to use a 2A Low-Voltage Circuit Breaker before connecting to Mains (voltage inputs)".
  • "Only qualified personnel familiar with the instrument and its associated electrical equipment must perform setup procedures."
  • The quick start says: "Only a licensed electrician may perform installations and wiring of the PM335."

Set the wiring mode to match

Basic Setup includes Wiring Mode, with the options in Table 9. The default is 4Ln3. The manual's paths are:

  • front display: the General Setup menu, then Basic Setup;
  • PAS: General Setup from the Meter Setup menu, then the Basic Setup tab.

The manual says: "Always specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs."

SATEC Australia's advice: if the meter is already in service, save its current setup before changing anything. The PAS lesson Upload the setups, then duplicate the backup shows how.

DC measurement

DC voltage and current measurement is on pages 37–42. The manual notes: "DC option will appear in the menu for HACS input meters only".

SATEC Australia's advice: check the order code and those pages before wiring a DC installation.

What to send technical support

Contact SATEC Australia technical support through our contact form.

SATEC Australia's advice is to include:

  • the full order code from the label;
  • the circuit type;
  • the PT and CT ratios, and how many of each are fitted;
  • the figure and setup code you think applies;
  • a photo of the terminals, if the meter is installed.

Manuals and source pages

  • EM235/PM335 PRO Installation and Operation Manual, BG0612 Rev. A8, December 2024 (PDF on our site). Printed page numbers match the PDF pages:
  • PRO PM335 Quick Start, BG0635 Rev. A2, pages 1–2 (PDF on our site).
  • Evidence checked 22 November 2026.

Source review: 22 November 2026.