PM135 · IDENTIFY

Identifying your PM135: model, options, clock and wiring drawing

PM135 and its TOU add-on module, from its manufacturer manual
PM135 and TOU add-on module, manufacturer manual page 35. Identification illustration only.

Before changing a PM135's setup, replacing it or asking for support, it helps to know exactly which PM135 it is. This page shows where to read the model and its settings, what the ordering options mean, how the clock arrangement differs between versions, and how to find the wiring drawing that matches the meter. It is based on the PM135 Installation and Operation Manual, BG0518 Rev. A4, and SATEC Australia's PM135 datasheet.

The three models

The PM135 comes as three models:

ModelWhat it adds
PM135PThe basic model: voltage, current, power and frequency measurements, and control capabilities. A special amp-demand version can be ordered with a simplified display.
PM135EEverything in the PM135P, plus energy measurements and data logging.
PM135EHEverything in the PM135E, plus harmonic analysis.

The PM135E and PM135EH also have a red Energy Pulse LED on the front. The manual lists billing and time-of-use energy registers, and event and data recording, as PM135E and PM135EH features.

Reading the model from the front display

The Device Info display shows the meter's model, serial number, firmware version, bootloader version, communication module version and I/O module type. Scroll through it with the UP and DOWN buttons.

The Basic Settings display shows the wiring mode, PT ratio, PT ratio multiplier, CT primary current, demand periods and nominal frequency.

Ordering options and the rear labels

The manual asks installers to check the labels on the back of the instrument for the power supply voltage, input voltages and currents before connecting it. It does not show what else those labels carry.

SATEC Australia's datasheet builds a PM135 order code from these choices:

  • Model: PM135P, PM135E or PM135EH.
  • Current inputs: 5 A, 1 A, a 5 A split-core remote HACS (RS5), or High Accuracy Current Sensors (HACS). Both HACS options are 50/60 Hz only.
  • Calibration frequency: 25, 50, 60 or 400 Hz. 25 Hz and 400 Hz are for the 1 A and 5 A models only.
  • Display resolution: low (1 A, 1 V) or high (0.01 A, 0.1 V).
  • Power supply: 85–265 V AC and 85–290 V DC; 9.5–18 V DC; or 18.5–58 V DC.
  • Protocol: Modbus and DNP3.0, or Modbus and IEC 60870-5-101/104. IEC 60870-5-104 requires Ethernet.
  • Mounting: panel (standard) or DIN rail.
  • Testing: full functional test with a detailed test report, or that plus an ISO 17025 and ILAC certified calibration certificate.

SATEC Australia's datasheet allows at most one expansion module per instrument, and says modules can be ordered separately. Its ordering table lists analogue outputs, a second communication port (Ethernet, PROFIBUS or RS-232/422/485), and digital inputs and outputs. The manual's list of available options also includes a TOU battery-operated clock unit and a GPRS communication port, and the manual describes a 120 V voltage input option ("Option U"), which it says usually implies use of a potential transformer. None of these three appears in the datasheet's ordering table.

The clock arrangement

The PM135's clock is backed differently depending on the version and on whether a TOU module is fitted. The regular version uses a super-capacitor, the V2 version a battery, and the optional TOU module a battery-backed clock. The manual does not say how to tell a regular PM135 from a V2. For the retention times and the TOU module battery, see PM135 clock backup and the TOU module battery.

SATEC Australia's advice: to find out which clock version a meter has, contact SATEC Australia with its serial number from the Device Info display.

Choosing the right wiring drawing

The wiring drawings are on pages 26–29 of the manual, and each drawing's caption names its wiring mode code. SATEC Australia's advice: use the wiring mode code shown on the Basic Settings display, and find the drawing whose caption names that code.

Wiring mode codeConnectionFigure (caption)Manual page
3dir23-wire 2-element Delta, direct connection, 2 CTs2-926
4LL3 or 4Ln34-wire Wye 3-element, direct connection, 3 CTs2-1026
4LL3 or 4Ln34-wire Wye 3-element, 3 PTs, 3 CTs2-1127
3OP23-wire 2-element Open Delta, 2 PTs, 2 CTs2-1227
3LL3 or 3Ln34-wire Wye 2½-element, 2 PTs, 3 CTs2-1328
3OP33-wire 2½-element Open Delta, 2 PTs, 3 CTs2-1428
4LL3 or 4Ln34-wire 3-element Delta, direct connection, 3 CTs2-1529
3bLn3 or 3bLL33-wire 2½-element Broken Delta, 2 PTs, 3 CTs2-1629

Three drawings share the 4LL3/4Ln3 codes. Their captions differ in whether potential transformers are used, and in whether the system is Wye or Delta. SATEC Australia's advice: choose between those three drawings on those two points.

The figure numbers in the manual's wiring table (Table 2, page 25) are one lower than the figure captions. For example, the table gives Figure 2-8 for 3dir2, but the 3dir2 drawing is captioned Figure 2-9, and Figure 2-8 is the current input connection drawing. SATEC Australia's advice: go by the caption, not the table.

The manual can be downloaded from SATEC Australia's manuals page, or opened directly at the wiring drawings.

Keeping the as-found setup

PAS can read the meter's present setups and save them to the meter's site database, either one setup at a time or all at once with Upload Setups from the Meter Setup menu. PAS shows the general method in Upload the setups, then duplicate the backup; start with Start with PAS if PAS is new to you.

SATEC Australia's advice: upload and keep a copy of the meter's setups before changing any setting, replacing a module or replacing the meter.

What to record before contacting support

The Device Control display has a Diagnostics list of messages from the meter's self-test. The green diagnostic LED flashes until the diagnostics are cleared.

SATEC Australia's advice: before contacting SATEC Australia, record the following, and do not clear the diagnostics first:

  • the Device Info values: model, serial number, firmware, bootloader, communication module version and I/O module type;
  • the Basic Settings values, especially the wiring mode, PT ratio and CT primary current;
  • any messages in the Diagnostics list;
  • a copy of the uploaded PAS setups, if you have PAS;
  • a photograph of the rear labels, but only if they can be seen without opening an energised panel.

Contact SATEC Australia technical support through our contact form.

Source review: 22 November 2026.

Contact SATEC technical support

Back to Knowledge Base home