PM130EH PLUS · FRONT-PANEL KEYPAD GUIDE

How do I set the CT ratio on a PM130EH PLUS?

Open CHG → baSc → Ct, enter the CT primary current in amps, press ENTER to store, read back the setting and return to measurements.

This worked example uses a 250:5 A CT with a compatible 5 A meter input. Enter 250 A; the calculated ratio is 50:1. Use the primary current from your own CT nameplate.

Watch the keypad demonstration

4 minutes 3 seconds · English captions · Synthetic narration · Rendered keypad demonstration. Match the model, input option and actual firmware menus.

Download English captions · Read the text transcript

Jump to a chapter

Check the input version and rating label

The standard input in this film is 5 A nominal with a continuous operating range up to 10 A RMS. The optional 1 A nominal version has a range up to 2 A RMS. These are input ratings/ranges, separate from the programmable CT-primary setting of 1–50,000 A.

HACS is a separate hardware input option. Use compatible SATEC-supplied High-Accuracy Current Sensors; consult SATEC if unsure. Match the CT secondary or sensor to your meter's marked input. The rotation identifies this example's 5 A selection; check the label on your own meter.

Know the buttons and read the code key

  • SELECT highlights a window.
  • Up / Down arrows browse menus or change the selected value.
  • ENERGY / ENTER confirms a choice or stores an edit.
  • H/ESC — Escape backs out or cancels an unsaved edit, depending on the active screen.

A translucent white block shows the physical key being pressed. Separate flashes mean separate brief presses; one continuous block means the key is held. Release when indicated. The MAX/MIN button is not used in this lesson.

In the video key, match the red LED code to the meter. The icon and larger plain-English name explain its meaning. Smaller PAS and Modbus references provide secondary detail.

LED codePlain-English meaning
CHGChange setup
baScBasic settings
CtCT primary current, in amps
ESCEscape / return

Open the illustrated LED-code reference.

Set Ct to 250 A, store and check it

  1. Open Change setup

    From measurements, press and release SELECT to open the primary menu. Use SELECT to highlight CHG — Change setup, then briefly press ENERGY / ENTER.

  2. Follow the applicable password branch

    The PM130 PLUS is shipped with password 0 and protection disabled, so normally there is no prompt. If protection has been enabled and the password is still 0, confirm 0000 with ENTER. Otherwise use the configured password; ask your administrator or SATEC if you do not have it.

  3. Find Basic settings and Ct

    Use the arrows to find baSc — Basic settings, then ENTER. In Basic settings, use Up to find Ct — CT primary current. Press SELECT to highlight the value in the lower window.

  4. Set the primary current

    A brief Up or Down press changes the selected numeric value by one. Holding an arrow makes continuous changes. The separate held-Up example illustrates faster travel seen on the recorded unit; its timing is not a universal firmware acceleration curve. Release near your target and finish with brief presses.

    The film then explicitly returns to its 245 A worked example. Give Up five separate presses to reach 250 A. Enter the primary amps, 250, rather than the calculated 50:1 ratio for the 250:5 A CT.

  5. Store and read back

    Briefly press ENTER to store. Move to another parameter, return to Ct and check that it still reads 250. ESC before storing cancels an unsaved value; it is not the save action.

  6. Return to measurements

    Press H/ESC — Escape to return to the main setup menu. Press SELECT to highlight ESC in the lower window, then briefly press ENTER. At the primary menu, press the physical Escape key again to return to measurements.

PAS and Modbus references

Show secondary configuration references

PAS: Meter Setup → General Setup contains the corresponding CT-primary setting. This video teaches the keypad path.

Modbus: the selected A10 guide places CT primary at Basic Setup base address 2304 + offset 2 = 2306 decimal (0x0902), UINT16, in amps. The equivalent holding-register reference is 42307; it is a different address form. Confirm which notation your software expects. baSc is a menu/group, not one register.

Source: BG0427 A10, page 50 (PDF, new tab); address notation is explained on page 10.

Manuals and source references

Review date: 22 November 2026. Recording firmware was not stated. The phase-to-neutral voltage readings and two energy-pulse flashes are illustrative; they do not establish a real installation's load or correct CT selection. The held example is separate from the five-press 245→250 A worked sequence.

Video transcript

Read the complete narration

Welcome to this demonstration on how to change the CT primary current setting on a SATEC PM130EH PLUS meter.

Here’s the code key. Match the red code to the meter. The icon and larger name explain its meaning. Smaller PAS and Modbus references provide extra detail.

Before we start, here are the controls we will use. Select highlights a window. The Up and Down arrows browse menus or change a value. Energy, Enter confirms a choice or stores an edit. H/ESC is Escape. It backs out or cancels an unsaved edit, depending on the screen. We will not use Max, Min.

Check the current-input version. One amp nominal has a continuous range up to two amps. Five amps nominal, up to ten amps. These input ratings and ranges are separate from the CT primary setting. HACS is a dedicated version for compatible SATEC high-accuracy current sensors. This demonstration uses the five-amp version.

First, check the product label on your meter. This example is marked for a five-amp CT input. Match the CT secondary to your meter's input rating.

For this example, we're using a two-hundred-and-fifty-to-five amp CT with a compatible five-amp meter input. The Ct setting takes the primary current, so we'll enter two hundred and fifty amps.

Press and release Select to open the primary menu. Use Select to highlight Change setup, shown as CHG, then briefly press Enter.

The PM130 PLUS normally ships with password protection off and the password set to zero, so there is usually no prompt. If protection is enabled and the password is still zero, confirm four zeros with Enter. Otherwise use your configured password. If you don’t know it, ask your administrator or SATEC.

Use the arrow buttons to find Basic settings, then press Enter.

In Basic settings, use the Up arrow to find CT, the current transformer primary setting. Press Select to highlight its value.

For larger changes, hold the Up or Down arrow. Here, the Up arrow stays pressed while the value increases. On the recorded unit, a longer hold makes the number change faster.

Release near your target, then use brief presses for precision. Back to our two-hundred-and-forty-five amp example.

Our example starts at two hundred and forty-five. Press and release the Up arrow five times to reach two hundred and fifty.

Briefly press ENTER to store the new value.

Move to another parameter, then return to Ct and check that it still reads two hundred and fifty.

Press Escape, the key marked ESC, to return to the main setup menu. Press Select to highlight Escape in the lower window, then briefly press Enter. At the primary menu, press Escape again to return to measurements.

For more guidance, use the PM130 PLUS manual. Get in touch with us any time, we're here to help.