1 00:00:03,200 --> 00:00:08,614 Welcome to this demonstration on how to change the CT primary current setting 2 00:00:08,614 --> 00:00:10,723 on a SATEC PM130EH PLUS meter. 3 00:00:13,200 --> 00:00:18,797 Here’s the code key. Match the red code to the meter. The icon and larger name 4 00:00:18,797 --> 00:00:24,250 explain its meaning. Smaller PAS and Modbus references provide extra detail. 5 00:00:27,200 --> 00:00:32,579 Before we start, here are the controls we will use. Select highlights a 6 00:00:32,579 --> 00:00:38,337 window. The Up and Down arrows browse menus or change a value. Energy, Enter 7 00:00:38,337 --> 00:00:44,171 confirms a choice or stores an edit. H/ESC is Escape. It backs out or cancels 8 00:00:44,171 --> 00:00:49,247 an unsaved edit, depending on the screen. We will not use Max, Min. 9 00:00:54,200 --> 00:01:00,425 Check the current-input version. One amp nominal has a continuous range up to 10 00:01:00,425 --> 00:01:06,488 two amps. Five amps nominal, up to ten amps. These input ratings and ranges 11 00:01:06,488 --> 00:01:12,389 are separate from the CT primary setting. HACS is a dedicated version for 12 00:01:12,389 --> 00:01:18,452 compatible SATEC high-accuracy current sensors. This demonstration uses the 13 00:01:18,452 --> 00:01:19,826 five-amp version. 14 00:01:24,200 --> 00:01:29,839 First, check the product label on your meter. This example is marked for a 15 00:01:29,839 --> 00:01:35,250 five-amp CT input. Match the CT secondary to your meter's input rating. 16 00:01:39,700 --> 00:01:44,952 For this example, we're using a two-hundred-and-fifty-to-five amp CT with a 17 00:01:44,952 --> 00:01:50,344 compatible five-amp meter input. The Ct setting takes the primary current, so 18 00:01:50,344 --> 00:01:53,075 we'll enter two hundred and fifty amps. 19 00:01:54,700 --> 00:02:00,545 Press and release Select to open the primary menu. Use Select to highlight 20 00:02:00,545 --> 00:02:04,731 Change setup, shown as CHG, then briefly press Enter. 21 00:02:06,700 --> 00:02:12,394 The PM130 PLUS normally ships with password protection off and the password 22 00:02:12,394 --> 00:02:18,164 set to zero, so there is usually no prompt. If protection is enabled and the 23 00:02:18,164 --> 00:02:23,706 password is still zero, confirm four zeros with Enter. Otherwise use your 24 00:02:23,706 --> 00:02:29,400 configured password. If you don’t know it, ask your administrator or SATEC. 25 00:02:30,700 --> 00:02:34,305 Use the arrow buttons to find Basic settings, then press Enter. 26 00:02:36,700 --> 00:02:42,070 In Basic settings, use the Up arrow to find CT, the current transformer 27 00:02:42,070 --> 00:02:46,078 primary setting. Press Select to highlight its value. 28 00:02:48,700 --> 00:02:53,703 For larger changes, hold the Up or Down arrow. Here, the Up arrow stays 29 00:02:53,703 --> 00:02:59,059 pressed while the value increases. On the recorded unit, a longer hold makes 30 00:02:59,059 --> 00:03:00,821 the number change faster. 31 00:03:04,700 --> 00:03:09,460 Release near your target, then use brief presses for precision. Back to our 32 00:03:09,460 --> 00:03:11,936 two-hundred-and-forty-five amp example. 33 00:03:14,700 --> 00:03:18,899 Our example starts at two hundred and forty-five. Press and release the Up 34 00:03:18,899 --> 00:03:21,622 arrow five times to reach two hundred and fifty. 35 00:03:23,700 --> 00:03:26,051 Briefly press ENTER to store the new value. 36 00:03:27,700 --> 00:03:32,412 Move to another parameter, then return to Ct and check that it still reads two 37 00:03:32,412 --> 00:03:33,499 hundred and fifty. 38 00:03:35,700 --> 00:03:40,674 Press Escape, the key marked ESC, to return to the main setup menu. Press 39 00:03:40,674 --> 00:03:45,853 Select to highlight Escape in the lower window, then briefly press Enter. At 40 00:03:45,853 --> 00:03:50,146 the primary menu, press Escape again to return to measurements. 41 00:03:52,700 --> 00:03:58,677 For more guidance, use the PM130 PLUS manual. Get in touch with us any time, 42 00:03:58,677 --> 00:04:00,171 we're here to help.