PM130EH PLUS — set CT primary to 250 A Synthetic narration. Welcome to this demonstration on how to change the CT primary current setting on a SATEC PM130EH PLUS meter. Here’s the code key. Match the red code to the meter. The icon and larger name explain its meaning. Smaller PAS and Modbus references provide extra detail. Before we start, here are the controls we will use. Select highlights a window. The Up and Down arrows browse menus or change a value. Energy, Enter confirms a choice or stores an edit. H/ESC is Escape. It backs out or cancels an unsaved edit, depending on the screen. We will not use Max, Min. Check the current-input version. One amp nominal has a continuous range up to two amps. Five amps nominal, up to ten amps. These input ratings and ranges are separate from the CT primary setting. HACS is a dedicated version for compatible SATEC high-accuracy current sensors. This demonstration uses the five-amp version. First, check the product label on your meter. This example is marked for a five-amp CT input. Match the CT secondary to your meter's input rating. For this example, we're using a two-hundred-and-fifty-to-five amp CT with a compatible five-amp meter input. The Ct setting takes the primary current, so we'll enter two hundred and fifty amps. Press and release Select to open the primary menu. Use Select to highlight Change setup, shown as CHG, then briefly press Enter. The PM130 PLUS normally ships with password protection off and the password set to zero, so there is usually no prompt. If protection is enabled and the password is still zero, confirm four zeros with Enter. Otherwise use your configured password. If you don’t know it, ask your administrator or SATEC. Use the arrow buttons to find Basic settings, then press Enter. In Basic settings, use the Up arrow to find CT, the current transformer primary setting. Press Select to highlight its value. For larger changes, hold the Up or Down arrow. Here, the Up arrow stays pressed while the value increases. On the recorded unit, a longer hold makes the number change faster. Release near your target, then use brief presses for precision. Back to our two-hundred-and-forty-five amp example. Our example starts at two hundred and forty-five. Press and release the Up arrow five times to reach two hundred and fifty. Briefly press ENTER to store the new value. Move to another parameter, then return to Ct and check that it still reads two hundred and fifty. Press Escape, the key marked ESC, to return to the main setup menu. Press Select to highlight Escape in the lower window, then briefly press Enter. At the primary menu, press Escape again to return to measurements. For more guidance, use the PM130 PLUS manual. Get in touch with us any time, we're here to help.