ETC2002 · IDENTIFY

How do I identify an ETC2002 and find its own instructions?

Quick Answer

The ETC2002 Network Communicator and the ETC II are different SATEC products, each with its own manual. The front panel names the model. SATEC Australia's advice: check the model name before you use any instructions. Use the ETC2002 Installation and Operation Manual, BG0328 Rev. A7, and the ETC2002 Modbus guide, BG0367 Rev. A2. Our ETC gateway setup guide covers the ETC II and ETC ONE PLUS, not the ETC2002.

SATEC Australia's advice: if you are not sure which model you have, or the unit is showing a fault, leave the settings, the RUN/PROG switch and the power as they are, and contact us with the details listed below.

Check The Model Name On The Front Panel

The ETC2002 panel reads ETC2002 NETWORK COMMUNICATOR. The ETC II panel reads ETC II NETWORK COMMUNICATOR. Their battery holders look alike. SATEC Australia's advice: go by the model name and the ports, not the battery holder.

What to look forETC2002ETC II
Model name on the panelETC2002 NETWORK COMMUNICATORETC II NETWORK COMMUNICATOR
Top-right socketsIRIG-B, ETHERNET (COM1) and TEL.LINE (COM2)ETH/USB, and COM2 CELLULAR with an antenna socket and SIM slot
Port light rowsACTIVITY and LINK/DCD rows over COM 1 and 2; TX and RX rows over COM 3 to 5TX and RX rows only; no ACTIVITY or LINK/DCD row
Lower rightDIGITAL INPUTS terminal, inputs 1 to 4OPT block
Battery-backed memory1.5 Mbyte4 Mbyte
ManualBG0328 Rev. A7BG0594 Rev. A5

Sources: ETC2002 manual pp. 5, 6, 12 and 57; ETC II manual pp. 6, 13 and 58.

The manual lists some ports as options, such as the dial-up modem port. SATEC Australia's advice: if a port in the table is missing, rely on the model name.

Line drawing of the ETC2002 front panel: a round BATTERY holder, CPU and BATTERY LOW lights, the legend ETC2002 NETWORK COMMUNICATOR, ACTIVITY and LINK/DCD light rows over COM 1 and 2 and TX and RX rows over COM 3 to 5, a RUN/PROG switch, an IRIG-B socket, ETHERNET and TEL.LINE sockets, and below them the POWER SUPPLY, COM 3 RS-232, COM 4 and COM 5 RS-422/485 and DIGITAL INPUTS terminals.
Figure 1. ETC2002 front panel. From Figure 2-1, ETC2002 Installation and Operation Manual BG0328 Rev. A7, p. 6. Open figure in a new tab.
Photograph of the left end of the ETC2002 front panel: the SATEC logo, the round BATTERY holder, CPU and BATTERY LOW lights, and the ETC2002 model legend beside the ACTIVITY and LINK/DCD rows.
Figure 2. ETC2002 status lights. From Figure 3-1, ETC2002 Installation and Operation Manual BG0328 Rev. A7, p. 12. Open figure in a new tab.

Read The Lights

The ETC2002 has two yellow status lights, CPU and BATTERY LOW, and ten green port lights.

LightWhat the ETC2002 manual says
CPU "flashing for one second with a one-second pause""the device is in the operational state and is functioning normally"
CPU "flashing briefly 2 times with a one-second pause""the device is in service mode and is not operational"
CPU "flashing briefly 3 times with a one-second pause""a critical error has occurred and the device is not operational. Contact your local distributor for servicing."
BATTERY LOW "lights up""the backup battery is near the end of its operational life and should be replaced"
COM1 LINK onThe Ethernet port is connected to the local network
COM1 ACTIVITY flashingData is passing through the Ethernet port
COM2 DCD onA connection to a remote modem is established
COM2 ACTIVITY flashingData is passing through the modem port
COM3, COM4, COM5 RX and TX flashingThe port is receiving or transmitting data

If BATTERY LOW is on, read What does the BATTERY LOW light on an ETC2002 mean?.

The RUN/PROG Switch

The RUN/PROG switch must be in RUN for normal operation. In PROG, the COM3 port operates as a service port, the device "still services the Internet to serial gateway connections", and "serial-to-serial master connections through the COM3 port are not available". If the unit is powered up with the switch in PROG, it starts in service mode and the gateway does not operate.

The manual describes two terminal routes that list a version command, ver. A local session through COM3 is opened with the switch in PROG. A Telnet session over the network uses port 5023 and needs a login name and password, which the manual says to get from your local representative. SATEC Australia's advice: do not move the switch, restart the unit or start a terminal session just to read its version; tell us what you can see, and we will say whether anything else is needed.

Use The ETC2002's Own Documents

The links on our ETC II product page labelled "ETC 2002 / ETC II" open the ETC II documents, not these. The ETC gateway setup guide covers the ETC II and ETC ONE PLUS only, and states that the ETC2002 needs its own documentation.

SATEC Australia's advice: do not apply ETC II instructions to an ETC2002, or the reverse.

What To Send Us

SATEC Australia's advice: before you contact us, collect these photographs and notes. None of them needs any change to the unit.

  1. A photograph of the whole front panel, showing the model name, the lights and the RUN/PROG switch position.
  2. A photograph of the labels on the back. The manual says these show the power supply the unit is equipped with.
  3. What the CPU light is doing, using the table above, and whether BATTERY LOW is on.
  4. Which ports are in use and what each connects to: Ethernet, telephone line, the serial ports, an IRIG-B time source and the digital inputs.
  5. The firmware version, only if you already have it from PAS or an earlier record.
  6. A copy of the PAS site database for this ETC2002, if one exists. PAS keeps the ETC2002 setup in that database, and Upload Setups reads the setup from the device into it. SATEC Australia's advice: keep a copy of any existing database before you upload; see Upload the setups, then duplicate the backup.
  7. When the problem started, and any recent power, wiring, network or setting changes.

SATEC Australia's advice: send these through our contact form.

Manuals And Page References

  • ETC2002 Installation and Operation Manual, BG0328 Rev. A7: features p. 5; front panel drawing p. 6; back label p. 7; lights and RUN/PROG switch p. 12; modes p. 13; terminal and Telnet sessions pp. 20–24; PAS setups pp. 30–31; specifications p. 57.
  • ETC II Installation and Operation Manual, BG0594 Rev. A5, for comparison only: features p. 6; front panel and lights p. 13; specifications p. 58.

Source review: 22 November 2026.