ETC II · ROUTING

How does the ETC II decide which port a meter request goes to?

ETC II manufacturer product photograph
ETC II manufacturer product photograph

Quick Answer

Every request to the ETC II carries a device address. The manual gives the programmable range as 1 to 247, which may be restricted by specific protocol limitations. One address is kept for the ETC II's own settings and data. It is 99 when shipped and can be moved.

The ETC II routes every other address to a downstream network in one of two ways:

  • Fixed rules. Each address band goes to COM4 or COM5, depending on how those two ports are being used.
  • The device routing table. Available from firmware V21.5.4, the table names the port or Ethernet IP address for each device. It only takes effect once it is enabled.

For the setup steps in PAS, see How do I connect and configure a SATEC ETC gateway?. This page explains what those settings mean.

The ETC II's Own Address

The manual reserves the ETC II's own address for accessing its configuration and data registers. The factory setting is 99. The manual says it can be moved in the Gateway Options setup if you want to use 99 for a meter.

The manual does not say what happens if the ETC II's own address is also inside a downstream address band. SATEC Australia's advice is to give every meter an address that differs from the ETC II's own address.

Fixed Routing Rules

When the routing table is not in use, the manual gives these fixed bands:

How the ports are usedAddresses sent to COM4Addresses sent to COM5
COM5 not used1–247none
COM4 master, COM5 serial1–3233–247
COM4 master, COM5 IP-Link wireless216–2471–215
COM4 slavenone1–247

The manual adds that with non-standard communication protocols, all messages go to COM4.

The manual says COM4 should be set to master mode to operate as a gateway port. COM5 is set to master at the factory.

The Configured Address Range

Gateway Options also holds a device address range, with a default start of 1 and end of 215. The manual does not explain how this range combines with the fixed bands above. It also does not say what happens to a request for an address outside the range.

For example, in the COM4 master and IP-Link arrangement, the fixed band sends 216–247 to COM4, while the default range ends at 215. The manual does not say whether those addresses are reached.

SATEC Australia's advice: do not assume addresses outside the configured range will be reached. Read the actual range, and confirm one meter at each end of the band before relying on it.

The Device Routing Table

From firmware V21.5.4, the device routing table names the target for each device address:

  • a serial port (COM4 or COM5) for serial and wireless devices;
  • an IP address for a device on the Ethernet network.

Ethernet devices can only be reached through the routing table. The table has no effect until Routing Table is enabled in Gateway Options, and it is disabled by default. Each table entry can also carry a shared-access rule for some SATEC meter families.

The manual says the table is available starting with V21.5.4. SATEC Australia's advice: check the installed firmware before planning to use the table.

Addresses Are Not Device Counts

The manual allows up to 32 devices on each serial network. The address bands above say where requests are routed; the manual does not present them as a count of connectable meters.

What To Record

SATEC Australia's advice: before anyone changes a setting, record:

  1. The ETC II's own address, the address range start and end, and whether the routing table and shared access are enabled.
  2. How COM4 and COM5 are set (master or slave, serial or IP-Link).
  3. For each meter, its address and the port or IP it is meant to use.
  4. The ETC II firmware version.

SATEC Australia's advice: save a copy of the existing setup before any authorised change, as described in the ETC gateway guide.

If A Meter Is Not Reached

SATEC Australia's advice: contact SATEC Australia technical support through our contact form. Include the details above, the address you requested, the exact error or timeout, and a photograph of the gateway label and wiring.

Manuals And Source Pages

Source review: 22 November 2026.

Contact SATEC technical support

Back to Knowledge Base home