PM180 · APPLICATION NOTE
PM180 phasor measurement unit (PMU) application note
High Performance Analyzer PM180 Phasor Measurement Unit Application Note
Transcribed from the SATEC document Phasor Measurement Unit Application Note, BG0637 REV.A4, Oct 2024 (PDF, 17 pages, 382 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.
Revision history
| A1 | May 2021 | Release |
| A2 | Oct 2021 | Added M performance class and unit specifications |
| A3 | June 2022 | Added positive sequence phasors, CFG-3 frame and spontaneous transmission of CFG frames |
| A4 | Oct 2024 | Added configurable channel names and second commanded TCP/UDP and spontaneous UDP data streams. |
1 General
This document describes the operation of the PM180 phasor measurement unit (PMU). For details on setting up the PMU and its communication options, see the product documentation listed below. Use the supplied PAS software tool to configure the PMU options in your device.
The PM180 phasor measurement unit provides synchrophasor and frequency measurements, and real-time cyclic exchange of synchrophasor data with the substation phasor data concentrator (PDC) based on the IEEE C37.118.2 synchrophasor data transfer protocol or via the IEC 61850-9-2 sampled values (SV) service.
PMU features:
- IEEE C37.118.1 three-phase voltage and current phasor measurements synchronized to a common UTC time reference, e.g. GPS
- IEEE C37.118.1 synchronous frequency and rate of change of frequency (ROCOF) measurements
- Clock synchronization to a common UTC time reference using an IRIG-B timecode source or an IEEE 1588 PTPv2 master clock source
- IEEE C37.118.2 commanded client-server UDP and TCP data transmission and spontaneous UDP data transmission over IP protocol
- Optional IEEE C37.118.2 frame extensions with analog data (total active, reactive and apparent power, power factor, and voltage and current THD) and digital status data (up to 32 inputs)
- Streaming of phasor data over Ethernet using the IEC 61850-9-2 multicast sampled value (SV) service with IEEE C37.118.2 mapping of synchrophasor data upon IEC 61850-9-2 and IEC 61850-90-5 guidelines
Reference documents:
- IEEE Std C37.118.1-2011, IEEE Standard for Synchrophasor Measurements for Power Systems
- IEEE Std C37.118.1a-2014, IEEE Standard for Synchrophasor Measurements for Power Systems, Amendment 1: Modification of Selected Performance Requirements
- IEEE Std C37.118.2-2011, IEEE Standard for Synchrophasor Data Transfer for Power Systems
- IEC/IEEE 60255-118-1:2018, Measuring relays and protection equipment – Part 118-1: Synchrophasor for power systems – Measurements
- IEC/TR 61850-90-5:2012, Communication networks and systems for power utility automation – Part 90-5: Use of IEC 61850 to transmit synchrophasor information according to IEEE C37.118
Product documentation:
- BG0521 PM180 Installation Manual
- BG0525 PM180 Operation Manual
- BG0627 PM180 IEEE C37.118.2 Reference Guide
- BG0523 PM180 IEC 61850 Reference Guide
- BG0527 PM180 Modbus Reference Guide
Definitions and acronyms:
- Phasor - a complex equivalent of a sinusoidal wave quantity such that the complex modulus is the cosine wave amplitude, and the complex angle (in polar form) is the cosine wave phase angle
- Synchrophasor - a phasor calculated from data samples using a standard time signal as the reference for the measurement
- APDU - application protocol data unit
- APPID - application identifier
- ASDU - application service data unit
- ASN.1 - Abstract syntax notation number one
- BER - ASN.1 basic encoding rules
- PDC – phasor data concentrator
- PMU – phasor measurement unit
- SV - sampled value
2 PMU Installation
The PMU is implemented as an add-on card integrated in one assembly with the fast transient recorder module.
The PMU module may be located in any of the PM180 expansion slots.
Input voltages must be connected to the module terminals V1, V2, V3 and VN. Current signals are delivered from the common AC inputs via the PM180 backplane. Follow common grounding rules in the PM180 Installation Manual.
If an IRIG-B time source is used for UTC time synchronization, connect the IRIG-B signal wires to the 1pps/CM terminals on the PM180 CPU module.
In case the IEEE 1588 master clock is used as UTC source, connect the network cable directly to the PMU IEEE 1588 Ethernet port.
PMU operation is indicated by the “PMU OK” LED on the front of the PMU, which flashes yellow ones a second when the PMU clock is not in sync with the UTC/IRIG-B clock, and flashes green when synchronized.
3 Measuring Techniques
3.1 Synchrophasor Estimation
The PMU calculates and reports synchrophasor estimates as defined and described in IEEE C37.118.1 Clause 4.
The estimates include three-phase voltage and current synchrophasors calculated from the input signal waveforms synchronized to an absolute time reference, followed by complex multiplication with the nominal frequency carrier, i.e., multiplication of the input by the quadrature oscillator (sine and cosine).
All measurements are made on a common time base and related to the system nominal frequency, so the phase angle measurements are directly comparable. Differences in the actual frequency are included in the phase angle estimation. A precise time reference clock is used to provide the UTC time to determine the phase angle.
3.2 Frequency and ROCOF Estimation
The frequency is computed as the first derivative of the synchrophasor phase angle, and ROCOF is computed as the second derivative of the same phase angle.
The frequency and ROCOF estimates are based on positive sequence synchrophasors calculated using the symmetrical components transformation. Since phase angle changes relative to the difference between the actual frequency and the nominal frequency, this approach yields the offset from nominal.
3.3 Reporting Rates
The PMU supports data reporting at submultiples of the nominal system frequency. The actual reporting rate is user selectable.
The available rates are listed in the following table.
| System frequency | 50 Hz | 60 Hz |
|---|---|---|
| Reporting rates (frames/s) | 1, 2, 5, 10, 25, 50 | 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 |
4 Time Synchronization
The PMU must be connected to a reliable and accurate GPS time source, that can provide time traceable to UTC so all measurements are synchronized to UTC time with accuracy sufficient to meet the requirements of IEEE C37.118.1.
The PMU clock can be synchronized to UTC using an IRIG-B timecode source or an IEEE 1588 PTPv2 master clock source.
4.1 IRIG-B Time Synchronization
When using an external IRIG-B time source, connect the IRIG-B signal wires to the 1pps/CM terminals on the PM180 CPU module.
The PM180 IRIG-B port uses an unmodulated (pulse-width coded) timecode signal (unbalanced 5V level) according to the IRIG 200-04 standard. It supports B000/B001 and B004/B005 timecode formats with time code extentions specified for the IRIG-B profle in Annex D of IEEE Std C37.118.1-2011.
The PMU IRIG-B port can synchronize to the IRIG-B timecode source with sub-microsecond accuracy.
To enable the IRIG-B port as a UTC source, select the IRIG-B time synchronization option in the IEEE C37.118.2 setup (see the PM180 IEEE C37.118.2 Reference Guide for details).
4.2 PTPv2 Time Synchronization
To use the IEEE 1588 master clock as UTC source, your PMU must be provided with the IEEE 1588 Ethernet port.
The IEEE 1588 PMU port must be connected to an IEEE 1588 grandmaster clock through a PTPv2 peer-to-peer transparent clock switch compliant with IEEE Std 1588-2008.
The IEEE 1588 PMU port implements an ordinary PTPv2 clock and uses the IEEE C37.238 power profile per IEEE C37.238-2011 and IEC/IEEE 61850-9-3 as follows:
- PTP version 2.
- PTP transport over Layer 2 Ethernet (IEEE 802.3), IEEE 1588-2008, Annex F.
- Multicast addressing.
- Peer-to-peer (P2P) path delay measurement mechanism.
- Announce interval = 1 s
- Sync interval = 1 s
- Capable of working with one-step and two-step master clocks.
- Responds to peer path delay requests with two-step peer delay responses (Pdelay_Resp, Pdelay_Resp_Follow_Up messages).
The IEEE 1588 PMU port can synchronize to the PTP grandmaster clock with sub-microsecond accuracy, which can be degraded by network topology, PTP switch accuracy, or transmission media asymmetry.
To enable the IEEE 1588 port as UTC source, select the IEEE 1588 time synchronization option in the IEEE C37.118.2 setup, and configure the port network addresses (see the PM180 IEEE C37.118.2 Reference Guide for details).
The PMU comes with a Telnet server that can be used to check the PMU clock status and time accuracy. Connect with a Windows Telnet client to the PMU using the IP address of the IEEE 1588 PMU port, login with the password shown in the PDF and enter "ptp". Figure 4-1 shows an example of the PMU clock status printout.
Figure 4-1 PMU PTP clock status information. Drawing not reproduced on this page. See page 9 of the PDF.
5 PMU Communications
5.1 IEEE C37.118.2 Communications
The PMU IEEE C37.118.2 protocol implementation is user configurable, making it easy to adapt for use in different installations. See the PM180 IEEE C37.118.2 Reference Guide for more details on operating and configuring IEEE C37.118.2.
To keep maximum interoperability with phasor data concentrators (PDC) and controlling stations, the PM180 supports all standard frame types for synchrophasor data interrogation and streaming.
The PM180 PMU provides commanded unicast client-server UDP and TCP data transmission and spontaneous multicast or unicast UDP data transmission using two data streams with programmable data rates. The data stream ID number uniquely identifies each data stream.
The synchrophasor measurement data reporting rate can be configured in submultiples of the nominal power line frequency from 1 to 60 frames per second.
Each data stream can be individually configured to any data rate that is submultiple of the PMU reporting rate.
5.1.1 Commanded Unicast UDP and TCP Data Transmission
Commanded unicast data transfer is controlled by commands sent by the client over a unicast TCP or UDP connection to the PMU's local TCP or UDP port, respectively.
Configuration and header frames are always sent to the IP address and port from which the corresponding command was received, while data frames are sent to the IP address and port from which the start command was sent. This does not necessarily have to be the same port.
The PMU provides up to 5 simultaneous unicast TCP and/or UDP connections for streaming synchrophasor data at a user-programmable data rate using one of two commanded data streams. The transmission start command should indicate the selected stream identifier.
5.1.2 Spontaneous UDP Data Transmission
Unlike commanded data transfer, spontaneous data frames are sent to a user-configured IP address and destination port. The PMU provides two data streams for simultaneous transmission of synchrophasor data frames to two different destinations at user-programmable data rates.
Spontaneous data transfer must be enabled or disabled explicitly by the user through the IEEE C37.118.2 settings or over an alternate client-server TCP or UDP connection to a local PMU TCP or UDP port, respectively, by referring to the appropriate spontaneous data stream identifier. Regardless of how the data stream is enabled, its state is stored in non-volatile memory, so that if it is enabled, data transfer is automatically started after the device reboots.
Configuration and header frames can be requested and received over an alternative TCP or UDP connection by referencing the appropriate data stream identifier, as in a regular client-server connection. Configuration frames can also be sent spontaneously to a user-configured destination port without an explicit command, like spontaneous data frames are sent (see Configuration Frames below).
Spontaneous UDP data transmission can operate in unicast, multicast or broadcast mode depending on the destination IP address the user specified.
5.1.3 IEEE C37.118.2 Message Frames
Data Frames
Synchrophasor data frames transmit a time stamped set of measurements that include phasor estimates, frequency deviation from the nominal power line frequency and the rate of change of frequency. In addition, the data frame can be expanded to contain analog data (total active, reactive and apparent power, power factor, voltage and current THD) and digital input status information (up to 32 inputs can be included).
The phasor data can represent single phase phasors (tree phase voltage and tree phase currents) or 3-phase positive sequence voltage and current, or both in a single frame.
The complex phasor values can be sent in a rectangular coordinates format (real and imaginary) or in polar coordinates (magnitude and angle). The phasor and frequency data can be represented in 32-bit IEEE floating-point format or as 16-bit scaled integer numbers. In case of using integer format, the data conversion factors are provided via the IEEE C37.118.2 configuration frames.
Configuration Frames
IEEE C37.118.2 configuration frames provide information about the synchrophasor data stream in binary format. The PM180 PMU supports CFG-1, CFG-2 and CFG3 configuration frames. The configuration frame contents correspond to the specification given by IEEE C37.118.2.
In spontaneous UDP data transmission mode, configuration frames CFG-2 or CFG-3 can be sent spontaneously without the explicit user command. If enabled, the configuration frame is sent periodically every 30 seconds.
The names of the phasor, analog data and digital status channels are user configurable. The default channel names are listed in Table 5-1.
| Channel name | Description |
|---|---|
| VA | V1 phase phasor |
| VB | V2 phase phasor |
| VC | V3 phase phasor |
| IA | I1 phase phasor |
| IB | I2 phase phasor |
| IC | I3 phase phasor |
| V1 | Positive sequence voltage phasor |
| I1 | Positive sequence current phasor |
| P | Active power analog channel |
| Q | Reactive power analog channel |
| S | Apparent power analog channel |
| PF | Power factor analog channel |
| VTHDA | V1 phase THD analog channel |
| VTHDB | V2 phase THD analog channel |
| VTHDC | V3 phase THD analog channel |
| ITHDA | I1 phase THD analog channel |
| ITHDB | I2 phase THD analog channel |
| ITHDC | I3 phase THD analog channel |
| DI1 | Digital status channel 1 |
| DI2 | Digital status channel 2 |
| … | |
| DI32 | Digital status channel 32 |
Header Frame
A header frame gives information about the synchrophasor data stream in human-readable format.
5.2 IEC 61850 Communications
5.2.1 PMU Data Model
Synchrophasor data transfer in the context of IEC 61850 uses IEEE C37.118 to IEC 61850 mapping mechanism defined in IEC 61850-90-5.
PMU is modeled as a dedicated logical device within the PM180 IED. The detailed PMU data model is shown as a part of the ICD definition file provided with your device.
The PMU logical device is responsible for the publishing of the synchrophasor measurements as defined in IEEE C37.118.2. It includes:
- a) MMXU measurement logical node that represents voltage and current synchrophasor data, frequency and ROCOF measurements; the new data object of HzRte is added to the MMXU logical node to accommodate the ROCOF data.
- b) LTIM time management logical node that gives indication of the local time configuration and status, like offset of local time from UTC and the flag indicating if daylight saving time is in effect.
- c) LTMS time master supervision logical node that is used for supervision of the time synchronization function; it indicates the current time source and time synchronization status according to IEC 61850-9-2.
5.2.2 Encoding Phasor Data in Multicast SV APDU
IEEE C37.118.2 synchrophasor data stream is mapped to IEC 61850-9-2 sampled values APDU (application protocol data unit). The sampled values dataset is user configurable.
Encoding of the sampled values APDU frame is shown in Figure 5-1.
Figure 5-1 Encoding of the SV APDU frame and synchrophasor data. Drawing not reproduced on this page. See page 12 of the PDF.
The APDU contains a single ASDU (application service data unit), which is encoded using ISO/IEC 8825-1 ASN.1 basic encoding rules (BER) with context-specific field tag octets listed in IEC 61850-9-2, Table 14.
Unlike other APDU attributes, a sequence of sampled phasor data is encoded as a compact block without ASN.1 tag triplets. The dataset members are encoded in their basic forms using fixed-length basic data type encoding rules listed in IEC 61850-9-2 Table 15.
The following picture shows an example of the multicast sampled values frame that carries a synchrophasor data stream over an Ethernet LAN.
Figure 5-2 Captured synchrophasor multicast sampled values frame. Drawing not reproduced on this page. See page 13 of the PDF.
5.2.3 IEC 61850 SV Publisher
The PM180 multicast SV publisher is responsible for publishing of the synchrophasor data over Ethernet. The SV publisher options and the sampled values dataset can be configured using the supplied PAS configuration software tool as described in the PM180 IEC 61850 Reference Guide.
5.3 Modbus Communications
Modbus communications is used to configure PMU parameters and monitor synchrophasor data measurements using the PAS configuration software tool or client software application.
The PM180 provides a dedicated synchrophasor data set listed in Table 5-2. For convenience of monitoring and verification, synchrophasor data is given in both polar format (magnitude and angle in arc-degree) and rectangular format (real and imaginary parts of a complex magnitude).
The bitmapped PMU time quality and frame status attributes are detailed in Table 5-3 and Table 5-4.
| Label | Description |
|---|---|
| FrmNo | Frame number |
| Tm | Frame timestamp, UTC seconds since 1/1/1970 |
| Tmmcs | Frame timestamp, fractional second |
| TmQual | Time quality, bitmap |
| IDCode | Data source/stream ID number |
| Stat | Frame status, bitmap |
| FREQ | Actual frequency or frequency deviation from nominal, Hz |
| DFREQ | Rate of change of frequency (ROCOF), Hz/s |
| V1 mag | V1 phasor magnitude |
| V1 ang | V1 phasor angle |
| V2 mag | V2 phasor magnitude |
| V2 ang | V2 phasor angle |
| V3 mag | V3 phasor magnitude |
| V3 ang | V3 phasor angle |
| I1 mag | I1 phasor magnitude |
| I1 ang | I1 phasor angle |
| I2 mag | I2 phasor magnitude |
| I2 ang | I2 phasor angle |
| I3 mag | I3 phasor magnitude |
| I3 ang | I3 phasor angle |
| V1 Re | V1 phasor, Real |
| V1 Im | V1 phasor, Imaginary |
| V2 Re | V2 phasor, Real |
| V2 Im | V2 phasor, Imaginary |
| V3 Re | V3 phasor, Real |
| V3 Im | V3 phasor, Imaginary |
| I1 Re | I1 phasor, Real |
| I1 Im | I1 phasor, Imaginary |
| I2 Re | I2 phasor, Real |
| I2 Im | I2 phasor, Imaginary |
| I3 Re | I3 phasor, Real |
| I3 Im | I3 phasor, Imaginary |
| V1seq mag | Positive sequence voltage phasor magnitude |
| V1seq ang | Positive sequence voltage phasor angle |
| I1seq mag | Positive sequence current phasor magnitude |
| I1seq ang | Positive sequence current phasor angle |
| V1seq Re | Positive sequence voltage phasor, Real |
| V1seq Im | Positive sequence voltage phasor, Imaginary |
| I1seq Re | Positive sequence current phasor, Real |
| I1seq Im | Positive sequence current phasor, Imaginary |
| Bits | Description |
|---|---|
| 0:3 | 0xF = clock failure, time not reliable |
| 0xB = time within 10 s | |
| 0xA = time within 1 s | |
| 0x9 = time within 100 ms | |
| 0x8 = time within 10 ms | |
| 0x7 = time within 1 ms | |
| 0x6 = time within 100 µs | |
| 0x5 = time within 10 µs | |
| 0x4 = time within 1 µs | |
| 0x3 = time within 100 ns | |
| 0x2 = time within 10 ns | |
| 0x1 = time within 1 ns | |
| 0x0 = locked to UTC traceable source | |
| 4 | Leap second pending |
| 5 | Leap second occurred |
| 6 | Leap second direction, 0 = add, 1=delete |
| Bits | Description |
|---|---|
| 0:3 | Trigger reason |
| 4:5 | Unlocked time: |
| 0 = sync locked or unlocked time < 10 s (best quality) | |
| 1 = unlocked time < 100 s | |
| 2 = unlocked time <= 1000 s | |
| 3 = unlocked time > 1000 s | |
| 6:8 | PMU time quality (see F39) |
| 9 | 1 = data modified by post processing, 0 = otherwise |
| 10 | Configuration change, set to 1 for 1 min to advise configuration will change, and cleared to 0 when change effected |
| 11 | 1 = PMU trigger detected, 0 = no trigger |
| 12 | Data sorting, 0 = by timestamp, 1 = by arrival |
| 13 | 0 = PMU in sync with a UTC traceable time source |
| 14-15 | Data error: |
| 0 = good measurement data | |
| 1 = PMU error (no information about data) | |
| 2 = PMU in test mode or absent data tags inserted (do not use values) | |
| 3 = PMU error (do not use values) |
See the PM180 Modbus Reference Guide for the location of the synchrophasor data registers. Refer to the PM180 Operation Manual for more information on configuring datasets for monitoring with the PAS configuration tool.
6 Measurement Specifications
| Inputs | Parameter | Value |
|---|---|---|
| Voltage | Rated voltage | 100-120 V phase-to-phase/57.7-69.3 V phase-to-neutral |
| Measurement range | 1-480 V phase-to-neutral | |
| Current | Rated current | 1 A or 5 A (upon order) |
| Measurement range | 0.1-400 % (4x) rated current |
| Performance class | Nominal frequency | Data reporting rate (Fs), frames/s | Frequency range |
|---|---|---|---|
| P | 50 Hz | 1, 2, 5, 10, 25, 50 | 50 +/-2 Hz |
| 60 Hz | 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 | 60 +/-2 Hz | |
| M | 50 Hz | 1, 2, 5, 10 | 50 +/-2 Hz |
| 25, 50 | 50 +/-5 Hz | ||
| 60 Hz | 1, 2, 3, 4, 5, 6, 10 | 60 +/-2 Hz | |
| 12 | 60 +/-2.4 Hz | ||
| 15 | 60 +/-3 Hz | ||
| 20 | 60 +/-4 Hz | ||
| 30, 60 | 60 +/-5 Hz |
| Parameter | Conditions | Value |
|---|---|---|
| Frequency | Over frequency range | < 0.0005 Hz |
| Over temperature range 0-50 °C | 0.001 Hz | |
| TVE, voltage | At nominal frequency | 0.05% |
| Over frequency range | 0.1% | |
| Over temperature range 0-50 °C | 0.2% | |
| TVE, current | At nominal frequency, > 40% rated current | 0.05% |
| Over frequency range | 0.1% | |
| Over temperature range 0-50 °C | 0.2% | |
| Phase | At nominal frequency | 0.025 degree |
| Over frequency range | 0.05 degree | |
| Over temperature range 0-50 °C | 0.1 degree |
| Parameter | Conditions | Value |
|---|---|---|
| Frequency | At nominal frequency, > 40% rated voltage | < 0.0005 Hz |
| Over frequency range | 0.001 Hz | |
| Over temperature range 0-50 °C | 0.001 Hz | |
| TVE, voltage | At nominal frequency, > 60%/50Hz, > 40%/60Hz rated voltage | 0.05% |
| Over frequency range | 0.1% | |
| Over temperature range 0-50 °C | 0.2% | |
| TVE, current | At nominal frequency, > 40% rated current | 0.05% |
| Over frequency range | 0.1% | |
| Over temperature range 0-50 °C | 0.2% | |
| Phase | At nominal frequency | 0.025 degree |
| Over frequency range | 0.05 degree | |
| Over temperature range 0-50 °C | 0.1 degree |
Downloads and related
- Download the PDF (BG0637 REV.A4, 382 KB)
- Read the PDF in the document library
- Product support: answers, documents and videos
- All application notes as web pages
- How do I replace the backup battery in a PM180?
- Which PM180 display and options are fitted or required?
- What information and records should I preserve before a PM180 service or change?
Questions about this document? Use the contact form.