1 General

The PM180 provides two user-selectable power quality recording options. This application note outlines specific features provided by the EN 50160:2010 PQ recorder.

The accompanying PAS configuration and data acquisition software provides a user with a means for remote configuring the PQ recorder, monitoring, retrieving and reporting EN 50160:2010 compliance statistics data.

See the PM180 Operation Manual for basic information on configuring and operating EN 50160 PQ recorders and available data logging options.

See Section 2 Configuring the EN 50160:2010 PQ Recorder on how to select and configure the PM180 PQ recorder to get measurements and statistics reports.

1.1 Features

The EN 50160:2010 PQ recorder provides a user with accurate power quality measurements and statistical reports. The recorder also provides detailed time-stamped event, data and waveform information to allow easy diagnosing and resolving power quality incidents.

The EN 50160:2010 PQ recorder features:

Reference documents:

  1. EN 50160:2010 Voltage characteristics of electricity supplied by public electricity networks, July 2010, CENELEC.
  2. CLC/TR 50422:2003 Guide for the application of the European Standard EN 50160, June 2005.
  3. IEC 61000-4-30 Electromagnetic compatibility (EMC) – Part 4-30: Testing and measurement techniques – Power quality measurements, Edition 3.0, 2015-02.
  4. IEC 61000-4-7 Electromagnetic compatibility (EMC) – Part 4-7: Testing and measurement techniques – General guide on harmonics and interharmonics measurements and instrumentation, 2nd edition, 2002-08.
  5. IEC 61000-4-15 Electromagnetic compatibility (EMC) – Part 4-30: Testing and measurement techniques – Flickermeter – Functional and design specifications, Edition 2.0, 2010-08.
  6. IEC/TR 61000-2-8 Electromagnetic compatibility (EMC) – Part 2-8: Environment – Voltage dips and short interruptions on public electric power supply systems with statistical measurement results, 2002-11.
  7. IEC TS 62749 Assessment of power quality – Characteristics of electricity supplied by public networks, Edition 1.0, 2015-04
  8. IEC 62586-1 Power quality measurements in power supply systems – Part 1: Power quality instruments (PQI), Edition 2.0, 2017-03
  9. IEC 62586-2 Power quality measurements in power supply systems – Part 2: Functional tests and uncertainty requirements, Edition 2.0, 2017-03

1.2 Measurement Techniques

1.2.1 Power Quality Monitoring and Recording

The PM180 PQ recorder measures, evaluates and collects power quality information as defined and described in EN 50160:2010. A detailed description of the evaluation techniques used by the PM180 is given in Annex A.

Whenever IEC 61000-4-30 techniques conflict with EN 50160:2010 normative requirements, a user is given an option to choose a preferable method.

Monitoring Thresholds and Compliance Limits

Since PQ monitoring is intended both for network power quality assessment and for troubleshooting of power quality related problems, the PQ recorder provides collecting of power quality compliance statistics and individual recording of all power quality related events based on predefined detection thresholds and limits.

The monitoring thresholds and compliance limits are normally based on power quality indices provided by EN 50160:2010, but can be changed by the user via the EN 50160:2010 PQ Recorder setup to meet his particular installation’s requirements.

For voltage parameters that are characterized by statistical power quality indices like percentiles over a period of time, or for which only indicative statistics is collected, like dips, swells and interruptions, the detection thresholds are defined by high and low normally permissible limits parameters.

For voltage characteristics which compliance with the standard is also characterized by maximum and minimum values over a period of time, like frequency and supply voltage variations, the compliance limits are extended by the high and low maximum permissible limits parameters.

PQ Event Recording

Whenever a monitored parameter exceeds its monitoring/detection threshold, a power quality related event is recorded to the PQ event log file provided with indication of the affected parameter, channel, start and end timestamps and a maximum/minimum magnitude recorded during the event.

For voltage characteristics provided with dual compliance limits, a user can choose which one is to be used as a detection threshold for monitoring PQ related events.

Any monitored parameter can be individually enabled or disabled for event recoding via the EN 50160:2010 PQ Recorder setup, as well as event recording can be globally disabled or enabled in the device. Disabling of PQ event recording, partially or entirely, does not affect evaluation of statistical power quality data collected for EN 50160:2010 compliance reports.

Disturbance Waveforms Recording

Power quality events can be accompanied by voltage and current waveforms recorded at the beginning, during and after the event. The number of pre-event and post-event cycles and the desired sample rate can be configured via the Waveform Recorder setup.

Waveform log files #7 and #8 are used by default for recording power quality related waveforms, but those can be changed to any other log file via the EN 50160:2010 PQ Recorder setup. In presence of the fast transient module, transient waveforms are re-directed to Waveform Log #6 that is automatically re-configured in this case for a higher sample rate.

Waveform recording is enabled by default for voltage dips, swells, interruptions and transients and can be individually enabled for other power quality parameters via the EN 50160:2010 PQ Recorder setup.

Data Trend Recording

For troubleshooting and testing reasons, the PQ recorder provides an additional feature that allows synchronous recording a set of selected measured data, like RMS volts and currents, signaling voltages, harmonics characteristics, and others, before, during and after a power quality event while using different time envelopes dependent on the event duration.

The recorder can start at half-cycle measurements and, as an event continues more time, to automatically move to longer time envelopes of up to 10-min aggregated measurements, and then return to a faster sample rate at the end of the event. The recording duration for each time envelope and the number of cycles to be recorded before and after the event can be configured via the EN 50160:2010 PQ Recorder setup.

Data log file #14 is dedicated for PQ event data trends. By default, no data trending is enabled in the PM180, but can be individually enabled and configured for any parameter using desired time aggregation intervals.

See Annex E for the list of parameters available for data trends synchronized with the PQ recorder.

Compliance Statistics Recording

EN 50160:2010 compliance statistics are automatically collected during weekly/daily evaluation periods unless evaluation is intentionally disabled via the EN 50160:2010 Advanced Setup. At the end of every evaluation period, collected statistical data is recorded to the dedicated log files. For testing reasons, intermediate statistics can be retrieved online and inspected at any time during the current evaluation period without affecting final compliance reports.

Data log files #10 and #11 are automatically configured in the PM180 for a 260-week statistics recording based on weekly evaluation periods, or for 260 days assuming daily statistics evaluation. The file size can be changed via the Log Memory setup dialog in case that data should be stored in the device for a longer time.

A weekly or daily evaluation period for collecting and recording statistical data can be selected, and the week day and time on which a calendar week starts can be configured via the EN 50160:2010 Advanced Setup.

1.2.2 Special Features

Flagging

During a voltage event like a dip, swell or interruption, the measurements for other voltage characteristics might produce unreliable values. The flagging concept avoids counting a single event more than once in different voltage parameters.

If, during a given time interval, a voltage event is detected, all voltage characteristics aggregated during this interval are flagged and are not included into statistical data. If, during a given time interval, any value is flagged, the aggregated value which includes that value is also be flagged.

Flagged data is not included into the EN 50160:2010 compliance statistics and PQ incidents are normally not recorded to the PQ event log file. For testing or troubleshooting reasons, recording flagged data can be enabled via the EN 50160:2010 Advanced Setup.

When enabled, flagged events appear in the PQ event log reports being marked by an asterisk.

Polyphase Aggregation

In a three-phase system, polyphase aggregation is applied to voltage dips and swells. A voltage dip or a swell is counted as one equivalent polyphase event regardless of the shape and number of phases affected and is characterized by a single duration.

The dip/swell magnitude on each affected phase during a polyphase event is individually recorded to the PQ event log file.

Time Aggregation

Reclosing operations can result in multiple voltage dips or interruptions from the same primary event. It can be misleading to count these disturbances as separate events.

To take account of this effect, the concept of time aggregation is applied for statistical analysis of voltage dips, swells and interruptions. Multiple successive events occurring within a limited interval of time may be counted as an equivalent event with equivalent magnitude and duration. For example, all voltage dips within a defined time interval can be counted as one single event whose magnitude and duration are those of the most severe dip observed during this interval.

Time aggregation is normally disabled in the PM180 and can be enabled by specifying a non-zero time aggregation interval from 1 to 180 s via the EN 50160:2010 Advanced Setup.

Regardless of applying time aggregation, each individual voltage event with its magnitude and duration is recorded to the device PQ event log file to allow further troubleshooting power quality related problems.

Data Aggregation

Though the EN 50160:2010 power quality indices require measurement aggregation over well-defined time intervals for each voltage characteristic, the PM180 also provides measurement aggregation over time intervals listed in IEC 61000-4-30, mostly for testing reasons.

10/12–cycle, 150/180-cycle, 10-min and 2-hour aggregated power quality related data, like voltages, currents, frequency, unbalance and total harmonics and interharmonics, are available for monitoring and recording.

The integration interval for harmonic and interharmonic voltages and currents intended for monitoring can be selected via the EN 50160:2010 Advanced Setup. By default, harmonic and interharmonic voltage and current readings represent data measured over non-overlapping 10/12-cycle intervals.

Coincident Currents

Current and current harmonic and interharmonic measurements are not listed by EN 5010:2010 indices and not evaluated for EN 50160:2010 compliance statistics, but provided as a supplement to voltage measurements.

Coincident currents can be recorded in the PQ event log along with the corresponding voltage channels for voltage dips, swells, interruptions and voltage variations with same timing determined by corresponding voltage event. Recording coincident currents is normally disabled and can be enabled via the EN 50160:2010 Advanced Setup.

Time Stamping

For testing reasons, where power quality related data is to be accompanied by a timestamp, the PM180 provides a synchronous polyphase timestamp for latest available 10/12-cycle measurements that can also be applied to all other composite intervals based on these measurements, as well as per channel timestamps for Urms(1/2) related voltage measurements commencing at a fundamental zero crossing. They are available for monitoring and recording via the present online PQ data group of parameters (see Annex D).

Block Numbering

Block numbering of 10/12-cycle and 150/180-cycle measurements within each 10-min interval is provided for IEC 61000-4-30 testing reasons (see Annex D).

The block numbers are updated when new data evaluated over the corresponding aggregation interval is available. Block numbers can be effectively used for synchronous and non-overlapping recording of the related power quality data by taking them as setpoint triggers along with a delta operator that responds to a trigger parameter change.

Flagging Information

Flagging information is given for all aggregation intervals and is indicated by the corresponding parameters in the present PQ data group (see Annex D). It can be used for testing reasons or accompany power quality related data while monitoring and recording.

Each flag holds its status until the corresponding aggregation interval is validated.

2 Configuring the EN 50160:2010 PQ Recorder

See the PM180 Operation Manual for common instructions on configuring your device. The following sections outline specific implementation details for operating the EN 50160:2010 PQ recorder.

2.1 EN 50160:2010 Recording Option

To get measurements and statistics reports, select the EN 50160:2010 PQ option via the General Setup/Device Options setup dialog.

2.2 Clearing EN 50160:2010 Evaluation Counters

The present contents of the EN 50160 evaluation counters may include undesirable statistical data collected during device testing and deployment that can appear in compliance statistics reports. It is recommended to clear PQ counters before starting your EN 50160 evaluation.

To clear the EN 50160 evaluation counters, select Reset from the Monitor menu, click Clear Operation/Event Counters, check the PQ Counters box, and then click OK and confirm your command.

Reference Voltage

As the general approach of EN 50160, all voltage characteristics are referenced to the nominal network voltage that shall be specified by the secondary line-to-line voltage parameter via the Basic setup before running the PQ recorder.

Reference Frequency

The nominal line frequency is used as a reference for evaluation of power frequency and for selecting the appropriate measurement time interval for all power quality related measurements. It also affects characteristics of digital filters used by some evaluation methods like flicker measurements.

2.4 Configuring the EN 50160:2010 PQ Event Recorder

To configure the EN 50160:2010 PQ recorder, select Memory/Log in the Meter Setup Menu and then click on the EN 50160:2010 PQ Recorder tab.

This setup allows you to adjust the detection thresholds and compliance limits for specific voltage characteristics and to select and configure options for related event, waveform and data trend recording.

The picture below shows the PQ recorder setup dialog with the default factory settings. Use the horizontal scroll bar to move between the two parts of the dialog window.

See Table 2-1 for the available configuration options. See Section 1.2.1 Power Quality Monitoring and Recording for information on how your settings may affect operation of the PQ recorder.

NOTE: When testing the device for compliance with the corresponding standards, some tests may cause generating a large amount of power quality related events that can put an excessive load on the device recorders and thus affect operation of other features in your device. To avoid undesirable effects, you can uncheck the Recorder Enabled box to temporary disable operation of the EN 50160:2010 PQ recorder.

PM180 - Log Setup dialog, EN 50160:2010 PQ Recorder tab with default factory settings, first part (PQ Events and Recording: Thresholds, PQ Log, Waveform Log). Drawing not reproduced on this page. See page 9 of the PDF.

PM180 - Log Setup dialog, EN 50160:2010 PQ Recorder tab with default factory settings, second part (PQ Events and Recording: Waveform Log, Data/RMS Trend - Time Envelopes and Maximum Durations). Drawing not reproduced on this page. See page 9 of the PDF.

Table 2-1 EN 50160:2010 PQ recorder setup options
OptionRangeDescription
Thresholds
Percentile rank, %0-100.0%Defines the percentile rank for evaluation percentiles over a period of time
High norm. perm.-20.00-200.00%High normally permissible limit. Defines the higher detection threshold and a compliance (percentile) limit for parameter evaluation, in percent of the reference value
Low norm. perm.-20.00-200.00%Low normally permissible limit. Defines the lower detection threshold and a compliance (percentile) limit for parameter evaluation, in percent of the reference value
High max. perm.-20.00-200.00%High maximum permissible limit. Defines the maximum allowed compliance limit for parameter evaluation, in percent of the reference value
Low max. perm.-20.00-200.00%Low maximum permissible limit. Defines the minimum allowed compliance limit for parameter evaluation, in percent of the reference value
Hysteresis, %0-50.0%Defines the hysteresis for a PQ parameter, in percent of the reference value or threshold
PQ Log
On norm. perm.Checked UncheckedEnables recording power quality related events for a specific voltage characteristic on exceeding the normally permissible limit
On max. perm.Checked UncheckedEnables recording power quality related events for a specific voltage characteristic on exceeding the maximum permissible limit
Waveform Log
On startChecked UncheckedEnables coincident waveform recording on detection of a power quality event
On endChecked UncheckedEnables triggering waveform recording after a power quality event ends
Log No.1-8Specifies a waveform log file for waveform recording
Data/RMS trend – Time envelopes and Maximum Durations
EnableChecked UncheckedEnables recording of a coincident data trend during power quality related events
1/2-cyc, cycles0-1000 cyclesMaximum duration of data recording at a half-cycle rate
0.2-s, seconds0-1000 sMaximum duration of data recording at a 0.2-second rate
3-s, minutes0-1000 minutesMaximum duration of data recording at a 3-second rate
10-min, hours0-1000 hoursMaximum duration of data recording at a 10-minute rate
Before, Cycles0-20 cyclesThe number of cycles to be recorded prior to the event at a half-cycle rate
After, Cycles0-20 cyclesThe number of cycles to be recorded after the event at a half-cycle rate
Log No.14Indicates a data log file for coincident data recording

2.5 Configuring EN 50160:2010 Advanced Options

To configure the EN 50160:2010 recording options or enable additional recording features, select Memory/Log in the Meter Setup Menu and then click on the EN 50160:2010 Advanced Options tab.

The picture below shows a setup dialog screen with the default factory settings. See Table 2-2 for the available options and their limits.

See Section 1.2 Measurement Techniques for information on the advanced recording options and operation of the PQ recorder.

PM180 - Log Setup dialog, EN 50160:2010 Advanced Setup tab with default factory settings. Drawing not reproduced on this page. See page 11 of the PDF.

Table 2-2 EN 50160:2010 advanced setup options
OptionRangeDefaultDescription
Compliance Statistics
EvaluationDisabled, EnabledEnabledEnables the EN 50160:2010 statistics evaluation
Evaluation PeriodDaily, WeeklyWeeklyDefines the EN 50160:2010 statistics evaluation period
First Day of the WeekSunday-SaturdaySundayDefines the first day of the week for statistics evaluated on a weekly basis
Start Time00:00-23:0000:00Defines the start time of the evaluation period
Recording Options
Record Flagged DataDisabled, EnabledDisabledEnables recording flagged events to the PQ event log. Fagged data is marked by an asterisk in the PQ log reports.
Record Coincident CurrentsDisabled, EnabledDisabledEnables recording coincident currents. If enabled, the corresponding currents with same timing will be recorded to the PQ event log along with the corresponding voltage channels in case of a voltage dip, swell or voltage variation event.
Rapid Voltage Changes
Minimum Steady State Time3 s, 1 s, 100/120 1/2-cyc.100/120 1/2-cyc.Defines the minimum time interval for voltages to stay within the detection threshold to be considered a steady-state condition, and the corresponding voltage change detection method
Max. Repetition Rate0=any, 1-100 (any)Defines the maximum repetition rate in variations per evaluation interval (equal or less than) for rapid voltage changes. Voltage changes at higher rates will not be classified since they would be subject for flicker evaluation
Evaluation Interval1-60 min60Defines the time interval for periodic evaluation of rapid voltage changes. If the maximum repetition rate is set to a non-zero value, the evaluation and recording of the rapid voltage changes will be done at the end of each evaluation interval.
Flicker
Pst Period1-10 min10 minDefines the period of time for the short-term flicker evaluation. The standard setting of 10 minutes can be temporarily changed in the device for testing purposes
Harmonic Voltage
THD, up to order25-5040Defines the highest harmonic order included in the THD evaluation
Harmonics, up to order25-5025Defines the highest harmonic order for evaluation of the harmonic voltages
Interharmonic Voltage
EvaluationDisabled, EnabledDisabledEnables the evaluation of interharmonic voltages
THD, up to order25-5040Defines the highest interharmonic order included in the interharmonic THD evaluation
Interharmonics, up to order25-5025Defines the highest interharmonic order for evaluation of the interharmonic voltages
Mains Signaling Voltage
EvaluationDisabled, EnabledDisabledEnables the evaluation of the mains signaling voltages
1st Signaling Frequency110-3000 Hz183.0 HzSpecifies the mains signaling frequency for the compliance evaluation
2nd Signaling Frequency110-3000 Hz191.0 HzSpecifies the mains signaling frequency for the compliance evaluation
3rd Signaling Frequency110-3000 Hz217.0 HzSpecifies the mains signaling frequency for the compliance evaluation
4th Signaling Frequency110-3000 Hz317.0 HzSpecifies the mains signaling frequency for the compliance evaluation
Aggregation Interval3 s (150/180 cyc.), 0.2 s (10/12 cyc.)3 s (150/180 cyc.)Defines the aggregation time for interharmonic bins used in mains signaling voltage measurements
Voltage Events
Time Aggregation Interval0-180 s0Defines the aggregation time for time-aggregated voltage events: voltage interruptions, dips and swells. Time aggregation does not apply with a zero interval.
Data Monitoring Options
Harmonics Aggregation Interval0.2 s (10/12 cyc.) 3 s (150/180 cyc.) 10 min 2 h0.2 s (10/12 cyc.)Defines the aggregation interval for monitoring voltage and current harmonics and interharmonics. The default 10/12-cycle interval can be changed to higher values for testing purposes. The setting only applies to direct harmonic and interharmonic readings and does not affect EN 50160 evaluation statistics.

2.6 Configuring EN 50160:2010 Harmonics Limits

To configure the EN 50160:2010 harmonics and interharmonics compliance limits, select Memory/Log in the Meter Setup Menu and then click on the EN 50160:2010 Harmonics Setup tab.

This setup allows you to define or change detection thresholds and standard compliance limits for individual voltage harmonics and interharmonics.

Since compliance indices for interharmonics are not defined in EN 50160:2010, the interharmonic compliance limits are not provided and interharmonics evaluation in your device is disabled by default. To allow collecting interharmonics compliance statistics, define the compliance limits for individual interharmonics using your local power quality indices and enable interharmonics evaluation via the EN 50160:2010 Advanced Setup.

The picture below shows factory pre-configured settings.

PM180 - Log Setup dialog, EN 50160:2010 Harmonics Setup tab (Harmonic Voltage Limits, % and Interharmonic Voltage Limits, %). Drawing not reproduced on this page. See page 13 of the PDF.

The default settings contain values of individual harmonic voltages specified by the standard for low-voltage networks. To automatically pre-set compliance limits for a medium-voltage or high-voltage network, ensure that the nominal voltage and PT ratio settings in your device’s Basic Setup match the actual network characteristics, and then click on the Default button.

3 Operating the EN 50160:2010 PQ Recorder

3.1.1 Retrieving EN 50160:2010 Event and Statistics Files

See the PM180 Operation Manual for information on retrieving EN 50160:2010 PQ event log, compliance statistics and online statistics files.

3.1.2 Getting EN 50160:2010 PQ Event Reports

See the PM180 Operation Manual for detailed information on how to get PQ event reports and on available viewing and printing options.

Annex F provides an example of the EN 50160:2010 PQ event report.

3.1.3 Getting EN 50160:2010 Compliance Reports

See the PM180 Operation Manual for information on viewing, editing and printing options for EN 50160:2010 compliance statistics and online statistics reports.

An example of the EN 50160:2010 compliance report is given in Annex G.

Annex A EN 50160:2010 Evaluation and Recording

A.1 EN 50160:2010 Background

Scope of EN 50160:2010

EN 50160:2010 defines main characteristics of the voltage in public low, medium and high voltage electricity networks, which can be expected to remain within limits or values specified by the standard. The different aspects covered by the standard are exclusively related to the following voltage characteristics: frequency, magnitude, waveform and symmetry of the line voltages

The standard is applicable only under normal operating conditions including correct operation of the protection devices in the case of a fault in the network (blowing of a fuse, operation of a circuit-breaker etc.) or changes in network configuration. The standard does not apply under abnormal conditions like maintenance and construction works or other exceptional situations, in particular exceptional weather conditions, power shortages, third party interference or industrial actions.

The voltage characteristics are evaluated using a statistical approach. The standard and its referenced publications specify for each voltage characteristic:

The voltage characteristics covered by the standard are divided into two groups:

  1. Characteristics for which limit values are specified.
  2. Characteristics for which only indicative values are given.

Measurement methods to be applied in the standard are described in IEC 61000-4-30, IEC 61000-4-7 and IEC 61000-4-15. Some indicative values for voltage dips and short interruptions are given in IEC/TR 61000-2-8.

Voltage Characteristics

For the following voltage characteristics, the standard provides definite limits that can be complied with for most of the time considering the possibility of relatively rare excursions beyond limits:

  1. Power frequency
  2. Supply voltage variations
  3. Single rapid voltage changes
  4. Flicker
  5. Supply voltage unbalance
  6. Harmonic voltages
  7. Interharmonic voltages
  8. Mains signaling voltages

Table A-1 indicates the time aggregation intervals applied to different voltage parameters and reference compliance limits specified by the standard for the characteristics with definite limits. Limits are set with a view to compliance for a percentage of the observation time.

Table A-1 Reference compliance limits for voltage characteristics
Voltage characteristicAggregation intervalCompliance, % of the timeObservation period
Power frequency10 sSynchronous connection: ±1% for 99.5% of a year +4/-6% for 100% of the time Asynchronous connection: ±2% for 95% of a week ±15% for 100% of the timeWeek, year
Supply voltage variations10 minLow voltage: ±10% Un for 95% of the time +10%/-15% Un for 100% of the time Medium voltage: ±10% Un for 99% of the time ±15% Un for 100% of the time High voltage: Subject to individual contractsWeek
Single rapid voltage changes≤4-5% Un (up to 10% Un), only indicative values are givenDay
Flicker10 minPlt ≤ 1 for 95% of the timeWeek
Voltage unbalance10 min≤2-3% for 95% of the timeWeek
THD10 minLow and medium voltage: ≤ 8 for 95% of the time High voltage: Under considerationWeek
Harmonic voltages10 minEN 50160:2010, Tables 1, 4, 7 depending on the supply network voltageWeek
Interharmonic voltages10 minUnder considerationWeek
Mains signaling voltage3 sWithin “Meister-curve” for 99% of the time, EN 50160:2010, Figures 1, 2Day

Generally, an observation period of one week is chosen because it is the shortest interval to obtain reproducible measurement results. Limits are set with a view to compliance for a percentage of the observation time, e.g. 95% of the observations in any period of one week.

In the case of supply voltage and power frequency variations, further limits are specified within which the average measurements shall remain for 100% of the time.

Compliance limits for supply voltage variations, single rapid voltage changes and signaling voltages are given in percentage of the network nominal voltage. Compliance limits for power frequency are given in percentage of the nominal network frequency.

NOTES:

  1. For single rapid voltage changes, only indicative values are given for the time being.
  2. For some specific parameters, national regulations may define stricter limits.
  3. Compliance limits given in the standard may be superseded in total or in part by the terms of a contract between the user and the network operator.

Voltage Events

For the remaining characteristics of the voltage, by their unpredictable nature, the standard gives only indicative values, which are intended to provide users with information on the range of magnitude which can be expected. Those are called voltage events and comprise:

  1. Short and long voltage interruptions
  2. Voltage dips
  3. Voltage swells
  4. Transient overvoltages

Table A-2 shows typical detection thresholds and durations for the voltage events specified by the standard.

Table A-2 Reference thresholds and durations for voltage events
Voltage eventThreshold and durationObservation period
Short voltage interruptions<5% Un on all phases, <= 3 minYear
Long voltage interruptions<5% Un on all phases, > 3 minYear
Voltage dips<90% Un on any phase, <= 1 minYear
Voltage swells>110% Un, <= 1 minYear
Transient overvoltages>20% Un, peak, <= 10 msYear

The basic measurement for detecting voltage interruptions, dips and swells is Urms(1/2) – a value of the RMS voltage measured over 1 cycle, commencing at a fundamental zero crossing and refreshed each half-cycle. Typical hysteresis for voltage events is 2% Un.

Voltage events are classified by their duration and magnitude in percentage of the nominal network voltage. Collected voltage dips and swells event statistics are classified and represented according to the tables 2, 3, 5, 6, 8, and 9 given in EN 50160:2010.

A.2 EN 50160:2010 Evaluation Techniques

This section describes methods used for evaluating voltage characteristics.

Power Frequency

Method of Evaluation

The basic frequency measurement is the mean value of the frequency over fixed time intervals of 10 seconds under normal operating conditions.

A frequency variation is not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

Target Values

The compliance limits for frequency variations given in the EN 50160:2010 are as follows:

For synchronous connections:

50Hz ±1% for 99.5% of a year

50Hz +4/-6% for 100% of the time

For asynchronous connections:

50Hz ±2% for 95% of a week

50Hz ±15% for 100% of the time

The same limits are used for 60Hz systems.

Supply Voltage Variations

This characteristic defines slow variations of steady state supply voltage magnitude.

Method of Evaluation

The basic supply voltage magnitude measurement is the RMS value of the steady state voltage over a period of 10 minutes under normal operating conditions.

A voltage variation is not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

Target Values

The compliance limits for voltage variations given in the EN 50160:2010 are as follows:

Low voltage networks:

±10% Un for 95% of a week

+10%/-15% Un for 100% of the time

Medium voltage networks:

±10% Un for 99% of a week

±15% Un for 100% of the time

High voltage networks:

Subject to individual contracts

Single Rapid Voltage Changes

Rapid voltage changes are sudden but relatively weak voltage variations between two steady state voltage levels. The maximum rate of rapid voltage changes in normally once per hour or less. Voltage variations repeating more than once an hour are usually accounted by flicker. To avoid counting excessive flicker by rapid voltage changes, the maximum rate of voltage changes in variations (1 to 10) per an evaluation interval (from 1 min to an hour) can be limited and configured in the meter via the EN 50160:2010 Advanced Setup.

Method of Evaluation

The PQ recorder provides two methods for evaluation of rapid voltage changes based either on RMS value of voltage over a period of 1 or 3 seconds, or on the arithmetic mean of 100/120 consecutive Urms(1/2) values. The desired method can be selected via the EN 50160:2010 Advanced Setup by defining the minimum steady-state measurement time for detecting a voltage change.

Option 1: The recorder establishes the maximum difference of the RMS voltage between two intervals selected from three consecutive 3-second or 1-second intervals and compares it with the target compliance limit.

Option 2: The voltage change is detected as guided in IEC 61000-4-30 Clause 5.11.2 by establishing a difference between every Urms(1/2) measurement and the arithmetic mean of the preceding 100/120 Urms(1/2) values and comparing it with the target compliance limit (detection threshold). Along with the steady-state voltage change included into statistics, the recorder provides also an indication of the maximum difference between any of the Urms(1/2) values during the event and the final steady-state voltage level.

The rate of rapid voltage changes is not limited by default. To limit evaluation of voltage changes caused by flicker, define a non-zero maximum allowed repetition rate and a time period for counting a rate of changes.

A rapid voltage change is not classified if the rate of changes exceeds the predefined value (if defined), or crosses a dip or swell threshold, as it would be considered a voltage dip or a voltage swell.

Target Values

Under normal operating conditions the magnitude of rapid voltage changes (once per hour or less) should generally not exceed 5% of nominal voltage in LV networks, and 4% in MV networks. In some circumstances, like in systems where equipment switching must be carried out to meet supply system or load requirements, it can reach 10%Un in LV networks, and 6%Un in MV networks.

Flicker

Flicker expresses the visual discomfort caused by repetitive changes of brightness in lightning subjected to fluctuations of the supply voltage. Flicker is indicated by the long-term flicker severity parameter Plt, which is evaluated every 2 hours.

Method of Evaluation

The basic measurement is the short-term flicker severity indicator Pst, evaluated each 10 minutes. The indicative long-term flicker severity Plt is evaluated from 12 consecutive Pst values commencing at even-numbered 2-hour intervals. For testing purposes, the Pst period can be temporarily changed in the meter in the range of 1 to 10 minutes via the EN 50160:2010 Advanced Setup.

Pst values are not classified during intervals when the supply voltage magnitude exceeds a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

Plt is not evaluated if any of the included Pst intervals is flagged.

Target Values

The flicker compliance limit given in the EN 50160:2010 is:

Plt ≤ 1 for 95% of a week

The Plt compliance limit can be changed in the meter via the EN50160 PQ Recorder setup.

Voltage Unbalance

This characteristic defines the magnitude and/or phase asymmetries of three-phase steady state supply voltage.

Method of Evaluation

The basic measurement is the RMS value of the steady state voltage unbalance over a period of 10 minutes under normal operating conditions. It is defined via symmetrical components as the negative sequence component expressed in percent of the positive sequence component.

Voltage unbalance is not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

Target Values

The compliance limit for voltage unbalance given in the EN 50160:2010 is:

≤ 2% (≤ 3% in some areas) for 95% of a week

Harmonic Voltages

Method of Evaluation

The basic measurements are individual harmonic voltages expressed in percent of the fundamental voltage and the total harmonic distortion factor (THD) aggregated over a period of 10 minutes.

Harmonic voltages are evaluated based on 10/12-cycle gapless subgroup measurements. The THD is calculated as the subgroup total harmonic distortion.

Individual harmonic voltages are normally evaluated up to order 25 and the THD is calculated including all harmonics up to order 40 as required by EN 50160:2010. The order of the highest harmonic for both can be configured from 25 to 50 via the EN 50160:2010 Advanced Setup.

Harmonic voltages are not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

Target Values

The ranges of harmonic voltages given in the EN50160 are:

Low voltage networks:

THD ≤ 8 for 95% of a week

Individual harmonic voltages shall be less than or equal to the values given in Table 1 EN 50160:2010 for 95% of a week.

Medium voltage networks:

THD ≤ 8 for 95% of a week

Individual harmonic voltages shall be less than or equal to the values given in Table 4 EN 50160:2010 for 95% of a week.

High voltage networks:

THD limit is under consideration

Individual harmonic voltages shall be less than or equal to the indicative values given in Table 7 EN 50160:2010 for 95% of a week.

Compliance limits for the THD and individual harmonics can be changed in the meter via the EN 50160:2010 PQ Recorder setup and via the EN 50160:2010 Harmonics setup.

Interharmonic Voltages

Method of Evaluation

This feature is normally disabled in the meter and may be enabled via the EN 50160:2010 Advanced Setup.

The basic measurements are individual interharmonic voltages expressed in percent of the fundamental voltage aggregated over a period of 10 minutes.

Interharmonic voltages are evaluated based on 10/12-cycle gapless interharmonic centered subgroup measurements. The total interharmonic distortion is calculated as the subgroup total interharmonic distortion.

The highest interharmonic order for evaluating individual interharmonic voltages and total interharmonic distortion can be selected in the meter via the EN50160 Advanced setup.

Interharmonic voltages are not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

Target Values

EN 50160:2010 compliance limits for interharmonic voltages are still under consideration. User assigned levels can be configured via the EN 50160:2010 Harmonics setup.

Mains Signaling Voltage

This characteristic defines the magnitude of the signal voltages used in some countries for signal transmission over public supply networks. The meter can evaluate ripple control signaling voltages in a frequency range from 100 Hz to 3 kHz.

Method of Evaluation

This feature is normally disabled in the meter since it is not commonly used. It can be enabled and up to 4 signaling frequencies can be selected for monitoring via the EN 50160:2010 Advanced Setup.

The basic measurements for mains signaling voltage can be selected by the aggregation interval setting via the EN 50160:2010 Advanced Setup:

Option 1: 3-second (150/180-cycle) mean value of signal voltages.

Option 2: 10/12-cycle value of signal voltages.

In both cases, the measurement method is based on the root of the sum of the squares of the 4 nearest 10/12-cycle RMS value interharmonic bins.

The EN 50160:2010 detection thresholds and compliance levels for signaling voltages are given by the so-called “Meister-curve” which defines the maximum permissible ripple control voltages in LV and MV networks.

Set to zero the detection threshold for signaling voltages in the EN 50160:2010 PQ recorder setup (factory default) to force using the Meister-curve compliance levels.

For IEC 61000-4-30 testing reasons, the detection threshold can be set to a constant level by defining a non-zero threshold value in percent of the nominal voltage.

Signaling voltages are not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

Target Values

The 3-second mean value of the signal voltages shall be less or equal to the specified limits for 99% of a day.

For HV networks, no values are given for mains signaling voltages.

Voltage Interruptions

Voltage interruptions correspond to temporary loss of supply voltage on all phases lasting less than or equal to 3 minutes in the event of short interruptions, and more than 3 minutes for long interruptions.

Method of Evaluation

The voltage interruption is detected when the voltages on all phases fall below the interruption threshold (IEC 61000-4-30) that is specified by the EN 50160:2010 at a level of 5%Un. The interruption threshold can be changed in the meter via the EN 50160:2010 PQ Recorder setup.

Time aggregation of multiple successive interruptions can be applied.

The basic voltage measurement for voltage interruptions is Urms(1/2).

Statistical Survey

Statistical data is classified by interruption duration. EN 50160:2010 does not provide a classification method for voltage interruptions. Some indicative data can be found in IEC/TR 61000-2-8. The PM180 EN 50160:2010 PQ recorder classifies interruptions according to Table A-3.

Table A-3 Classification of voltage interruptions according to durations
Residual voltage u, %UnDuration t, s
t <= 0.50.5 < t <= 11 < t <= 55 < t <= 2020 < t <=6060 < t <= 180180 < t
5 > u

Voltage Dips

A voltage dip is a sudden reduction of the RMS voltage below 90% of the nominal value, followed by a return to a value higher than 90% of the nominal in a time varying from 10 ms to 60 s.

Method of Evaluation

A voltage dip is counted as one polyphase event regardless of the shape and of the number of phases affected (IEC 61000-4-30). An event can begin on one phase and end on another phase. The fault magnitude is recorded separately for each phase involved. The event duration is measured from the instant at which the voltage falls below the start threshold on one of the phases to that at which it becomes greater than the end threshold on all affected phases including a threshold hysteresis.

Time aggregation of multiple successive voltage dips can be applied.

The basic voltage dip measurement is Urms(1/2).

Statistical Survey

The PM180 provides statistical evaluation of voltage dips using the classification recommended by EN 50160:2010. Dips are classified by residual voltage magnitude and duration according to Table A-4.

Table A-4 Classification of dips according to residual voltage and duration
Residual voltage, u %UnDuration t, s
0.01 <= t <= 0.20.2 < t <= 0.50.5 < t <= 11 < t <= 55 < t <= 60
90 > u >= 80
80 > u >= 70
70 > u >= 40
40 > u >= 5
5 > u

Voltage Swells

Voltage swells are sudden rises of the voltage RMS value of more than 110% of nominal voltage. Voltage swells may last between 10 milliseconds and one minute.

Method of Evaluation

A swell is counted as one polyphase event regardless of the shape and of the number of phases affected (IEC 61000-4-30). An event can begin on one phase and end on another phase. The fault magnitude is recorded separately for each phase involved. The event duration is measured from the instant at which the voltage rises above the start threshold on one of the phases to that at which it becomes lower than the end threshold on all affected phases including a threshold hysteresis.

Time aggregation of multiple successive voltage swells can be applied.

The basic voltage measurement is Urms(1/2).

Statistical Survey

The PM180 provides statistical evaluation of voltage swells using the classification recommended by EN 50160:2010. Swells are classified by voltage magnitude and duration according to Table A-5.

Table A-5 Classification of swells according to maximum voltage and duration
Swell voltage, u %UnDuration t, s
0.01 <= t <= 0.50.5 < t <= 55 < t <= 60
u >= 120
120 > u > 110

Transient Overvoltages

Transient overvoltages correspond to disturbances of very short duration, lasting typically less than one half-cycle, i.e. a few microseconds to several milliseconds.

Method of Evaluation

Transient overvoltages are detected as impulsive or low frequency oscillatory transients with a rise time less than 0.5 ms and duration from 20 us with the fast transient module option and from 75 us without it, and up to a half cycle. The impulse magnitude is referenced to the nominal voltage amplitude (1.414 Un). The meter can detect transient overvoltages with a magnitude of up to 2 kV with the fast transient module option or up to 700V without it.

Statistical Survey

Statistical data is classified by transient magnitude and duration. EN 50160:2010 does not provide a classification method for transient overvoltages. The PM180 EN 50160:2010 PQ classifies transient overvoltages according to Table A-6.

Table A-6 Classification of transient overvoltages according to magnitude and duration
Transient voltage, u %Un peakDuration t, ms
t <= 0.10.1 < t <= 0.20.2 < t <= 0.50.5 < t <= 11 < t <= 55 < t <= 10
u > 800
800 >= u > 400
400 >= u > 200
200 >= u > 100
100 >= u > 20

Annex B EN 50160:2010 Compliance Statistics Log

Annex B EN 50160:2010 Compliance Statistics Log
Field No.Field LabelDescription
Section 0 - Frequency Variation
1NnvNumber of non-valid 10-sec intervals
2NNumber of valid 10-sec intervals
3N1Number of values exceeded percentile limit
4N2Number of values exceeded maximum permissible limit
5df min1Low percentile of frequency variation, +/-%Fn
6df max1High percentile of frequency variation, +/-%Fn
7df min2Minimum frequency variation, +/-%Fn
8df max2Maximum frequency variation, +/-%Fn
9df lim1 lowLow percentile limit of frequency variation, %Fn
10df lim1 highHigh percentile limit of frequency variation, %Fn
11df lim2 lowLow maximum limit of frequency variation, %Fn
12df lim2 highHigh maximum limit of frequency variation, %Fn
13PercRankCompliance percentile rank, %
Section 1 - Voltage Variations
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3V1 N1Number of values exceeded percentile limit on phase A/AB
4V1 N2Number of values exceeded maximum limit on phase A/AB
5V1 dU min1Low percentile of voltage variation on phase A/AB, +/-%Un
6V1 dU max1High percentile of voltage variation on phase A/AB, +/-%Un
7V1 dU min2Minimum voltage variation on phase A/AB, +/-%Un
8V1 dU max2Maximum voltage variation on phase A/AB, +/-%Un
9V2 N1Number of values exceeded percentile limit on phase B/BC
10V2 N2Number of values exceeded maximum limit on phase B/BC
11V2 dU min1Low percentile of voltage variation on phase B/BC, +/-%Un
12V2 dU max1High percentile of voltage variation on phase B/BC, +/-%Un
13V2 dU min2Minimum voltage variation on phase B/BC, +/-%Un
14V2 dU max2Maximum voltage variation on phase B/BC, +/-%Un
15V3 N1Number of values exceeded percentile limit on phase C/CA
16V3 N2Number of values exceeded maximum limit on phase C/CA
17V3 dU min1Low percentile of voltage variation on phase C/CA, +/-%Un
18V3 dU max1High percentile of voltage variation on phase C/CA, +/-%Un
19V3 dU min2Minimum voltage variation on phase C/CA, +/-%Un
20V3 dU max2Maximum voltage variation on phase C/CA, +/-%Un
21dU lim1 lowLow percentile limit of voltage variation, %Un
22dU lim1 highHigh percentile limit of voltage variation, %Un
23dU lim2 lowLow maximum limit of voltage variation, %Un
24dU lim2 highHigh maximum limit of voltage variation, %Un
25PercRankCompliance percentile rank, %
Section 2 - Rapid Voltage Changes
1N1Number of polyphase incidents
2V1 N1Number of incidents on phase A/AB
3V1 dUMaximum voltage change on phase A/AB, %Un
4V2 N1Number of incidents on phase B/BC
5V2 dUMaximum voltage change on phase B/BC, %Un
6V3 N1Number of incidents on phase C/CA
7V3 dUMaximum voltage change on phase C/CA, %Un
8dU limMaximum permissible limit of voltage changes, Un%
Section 3 - Flicker
1NnvNumber of non-valid 2-hour intervals
2NNumber of valid 2-hour intervals
3V1 Plt N1Number of Plt values exceeded percentile limit on phase A/AB
4V1 Plt max1High percentile of Plt on phase A/AB
5V1 Plt max2Maximum Plt on phase A/AB
6V2 Plt N1Number of Plt values exceeded percentile limit on phase B/BC
7V2 Plt max1High percentile of Plt on phase B/BC
8V2 Plt max2Maximum Plt on phase B/BC
9V3 Plt N1Number of Plt values exceeded percentile limit on phase C/CA
10V3 Plt max1High percentile of Plt on phase C/CA
11V3 Plt max2Maximum Plt on phase C/CA
12Plt limHigh percentile limit of Plt
13PercRankCompliance percentile rank, %
Section 4 - Voltage Unbalance
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3Vunb N1Number of voltage unbalance values exceeded percentile limit
4Vunb max1High percentile of voltage unbalance, %
5Vunb max2Maximum voltage unbalance, %
6Vunb limHigh percentile limit of voltage unbalance, %
7PercRankCompliance percentile rank, %
Section 5 - Voltage THD
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3V1 N1Number of THD values exceeded percentile limit on phase A/AB
4V1 THD max1High percentile of THD on phase A/AB, %
5V1 THD max2Maximum THD on phase A/AB, %
6V2 N1Number of THD values exceeded percentile limit on phase B/BC
7V2 THD max1High percentile of THD on phase B/BC, %
8V2 THD max2Maximum THD on phase B/BC, %
9V3 N1Number of THD values exceeded percentile limit on phase C/CA
10V3 THD max1High percentile of THD on phase C/CA, %
11V3 THD max2Maximum THD on phase C/CA, %
12THD limHigh percentile limit of THD, %
13PercRankCompliance percentile rank, %
Section 6 - Signaling Voltage
1NnvNumber of non-valid intervals
2NNumber of valid intervals
3V1 Sig1 N1Number of 1st signaling voltage incidents on phase A/AB
4V1 Sig1Maximum 1st signaling voltage magnitude on phase A/AB, %Un
5V1 Sig2 N1Number of 2nd signaling voltage incidents on phase A/AB
6V1 Sig2Maximum 2nd signaling voltage magnitude on phase A/AB, %Un
7V1 Sig3 N1Number of 3rd signaling voltage incidents on phase A/AB
8V1 Sig3Maximum 3rd signaling voltage magnitude on phase A/AB, %Un
9V1 Sig4 N1Number of 4th signaling voltage incidents on phase A/AB
10V1 Sig4Maximum 4th signaling voltage magnitude on phase A/AB, %Un
11V2 Sig1 N1Number of 1st signaling voltage incidents on phase B/BC
12V2 Sig1Maximum 1st signaling voltage magnitude on phase B/BC, %Un
13V2 Sig2 N1Number of 2nd signaling voltage incidents on phase B/BC
14V2 Sig2Maximum 2nd signaling voltage magnitude on phase B/BC, %Un
15V2 Sig3 N1Number of 3rd signaling voltage incidents on phase B/BC
16V2 Sig3Maximum 3rd signaling voltage magnitude on phase B/BC, %Un
17V2 Sig4 N1Number of 4th signaling voltage incidents on phase B/BC
18V2 Sig4Maximum 4th signaling voltage magnitude on phase B/BC, %Un
19V3 Sig1 N1Number of 1st signaling voltage incidents on phase C/CA
20V3 Sig1Maximum 1st signaling voltage magnitude on phase C/CA, %Un
21V3 Sig2 N1Number of 2nd signaling voltage incidents on phase C/CA
22V3 Sig2Maximum 2nd signaling voltage magnitude on phase C/CA, %Un
23V3 Sig3 N1Number of 3rd signaling voltage incidents on phase C/CA
24V3 Sig3Maximum 3rd signaling voltage magnitude on phase C/CA, %Un
25V3 Sig4 N1Number of 4th signaling voltage incidents on phase C/CA
26V3 Sig4Maximum 4th signaling voltage magnitude on phase C/CA, %Un
27Sig1 frq1st signaling frequency
28Sig2 frq2nd signaling frequency
29Sig3 frq3rd signaling frequency
30Sig4 frq4th signaling frequency
31V Sig1 limMaximum permissible 1st signaling voltage magnitude, %Un
32V Sig2 limMaximum permissible 2nd signaling voltage magnitude, %Un
33V Sig3 limMaximum permissible 3rd signaling voltage magnitude, %Un
34V Sig4 limMaximum permissible 4th signaling voltage magnitude, %Un
35PercRankCompliance percentile rank, %
Section 7 - Voltage Interruptions (indicative statistics)
1N1 0,5sNumber of short polyphase interruptions <=500ms
2N2 1sNumber of short polyphase interruptions <=1s
3N3 5sNumber of short polyphase interruptions <=5s
4N4 20sNumber of short polyphase interruptions <=20s
5N5 60sNumber of short polyphase interruptions <=60s
6N6 180sNumber of short polyphase interruptions <=180s
7N7 >180sNumber of long polyphase interruptions >180s
8V minMinimum residual voltage, %Un
9dt maxMaximum duration of a short polyphase interruption
10dt totTotal duration of short polyphase interruptions
Section 8 - Voltage Dips (indicative statistics)
1N11 90%/0,2sNumber of polyphase dips <90% and duration <=0.2 s
2N12 90%/0,5sNumber of polyphase dips <90% and duration <=0.5 s
3N13 90%/1sNumber of polyphase dips <90% and duration <=1 s
4N14 90%/5sNumber of polyphase dips <90% and duration <=5 s
5N15 90%/60sNumber of polyphase dips <90% and duration <=60 s
6N21 80%/0,2sNumber of polyphase dips <80% and duration <=0.2 s
7N22 80%/0,5sNumber of polyphase dips <80% and duration <=0.5 s
8N23 80%/1sNumber of polyphase dips <80% and duration <=1 s
9N24 80%/5sNumber of polyphase dips <80% and duration <=5 s
10N25 80%/60sNumber of polyphase dips <80% and duration <=60 s
11N31 70%/0,2sNumber of polyphase dips <70% and duration <=0.2 s
12N32 70%/0,5sNumber of polyphase dips <70% and duration <=0.5 s
13N33 70%/1sNumber of polyphase dips <70% and duration <=1 s
14N34 70%/5sNumber of polyphase dips <70% and duration <=5 s
15N35 70%/60sNumber of polyphase dips <70% and duration <=60 s
16N41 40%/0,2sNumber of polyphase dips <40% and duration <=0.2 s
17N42 40%/0,5sNumber of polyphase dips <40% and duration <=0.5 s
18N43 40%/1sNumber of polyphase dips <40% and duration <=1 s
19N44 40%/5sNumber of polyphase dips <40% and duration <=5 s
20N45 40%/60sNumber of polyphase dips <40% and duration <=60 s
21N51 5%/0,2sNumber of polyphase dips <5% and duration <=0.2 s
22N52 5%/0,5sNumber of polyphase dips <5% and duration <=0.5 s
23N53 5%/1sNumber of polyphase dips <5% and duration <=1 s
24N54 5%/5sNumber of polyphase dips <5% and duration <=5 s
25N55 5%/60sNumber of polyphase dips <5% and duration <=60 s
26dt max 90%Maximum duration of a polyphase dip < 90%
27dt max 85%Maximum duration of a polyphase dip < 80%
28dt max 70%Maximum duration of a polyphase dip < 70%
29dt max 40%Maximum duration of a polyphase dip < 40%
30dt max 10%Maximum duration of a polyphase dip < 5%
31V min 0.2sMinimum residual voltage of dips with duration <=0.2 s, %Un
32V min 0.5sMinimum residual voltage of dips with duration <=0.5 s, %Un
33V min 1sMinimum residual voltage of dips with duration <=1 s, %Un
34V min 5sMinimum residual voltage of dips with duration <=5 s, %Un
35V min 60sMinimum residual voltage of dips with duration <=60 s, %Un
36dt totTotal duration of polyphase dips
Section 9 - Voltage Swells (indicative statistics)
1N11 120%/0,5sNumber of polyphase swells >=120% and duration <=0.5 s
2N12 120%/5sNumber of polyphase swells >=120% and duration <=5 s
3N13 120%/60sNumber of polyphase swells >=120% and duration <=60 s
4N21 110%/0,5sNumber of polyphase swells >110% and duration <=0.5 s
5N22 110%/5sNumber of polyphase swells >110% and duration <=5 s
6N23 110%/60sNumber of polyphase swells >110% and duration <=60 s
7dt max 120%Maximum duration of polyphase swells >=120%
8dt max 110%Maximum duration of polyphase swells >110%
9V max 0,5sMaximum polyphase swell voltage with duration <=0.5 s, %Un
10V max 5sMaximum polyphase swell voltage with duration <=5 s, %Un
11V max 60sMaximum polyphase swell voltage with duration <=60 s, %Un
12dt totTotal duration of polyphase swells
Section 10 - Transient Overvoltages (indicative statistics)
1N11 20%/0,1msNumber of polyphase impulses >20% and duration <=0.1 ms
2N12 20%/0,2msNumber of polyphase impulses >20% and duration <=0.2 ms
3N13 20%/0,5msNumber of polyphase impulses >20% and duration <=0.5 ms
4N14 20%/1msNumber of polyphase impulses >20% and duration <=1 ms
5N15 20%/5msNumber of polyphase impulses >20% and duration <=5 ms
6N16 20%/10msNumber of polyphase impulses >20% and duration <=10 ms
7N21 100%/0,1msNumber of polyphase impulses >100% and duration <=0.1 ms
8N22 100%/0,2msNumber of polyphase impulses >100% and duration <=0.2 ms
9N23 100%/0,5msNumber of polyphase impulses >100% and duration <=0.5 ms
10N24 100%/1msNumber of polyphase impulses >100% and duration <=1 ms
11N25 100%/5msNumber of polyphase impulses >100% and duration <=5 ms
12N26 100%/10msNumber of polyphase impulses >100% and duration <=10 ms
13N31 200%/0,1msNumber of polyphase impulses >200% and duration <=0.1 ms
14N32 200%/0,2msNumber of polyphase impulses >200% and duration <=0.2 ms
15N33 200%/0,5msNumber of polyphase impulses >200% and duration <=0.5 ms
16N34 200%/1msNumber of polyphase impulses >200% and duration <=1 ms
17N35 200%/5msNumber of polyphase impulses >200% and duration <=5 ms
18N36 200%/10msNumber of polyphase impulses >200% and duration <=10 ms
19N41 400%/0,1msNumber of polyphase impulses >400% and duration <=0.1 ms
20N42 400%/0,2msNumber of polyphase impulses >400% and duration <=0.2 ms
21N43 400%/0.5msNumber of polyphase impulses >400% and duration <=0.5 ms
22N44 400%/1msNumber of polyphase impulses >400% and duration <=1 ms
23N45 400%/5msNumber of polyphase impulses >400% and duration <=5 ms
24N46 400%/10msNumber of polyphase impulses >400% and duration <=10 ms
25N51 800%/0,1msNumber of polyphase impulses >800% and duration <=0.1 ms
26N52 800%/0,2msNumber of polyphase impulses >800% and duration <=0.2 ms
27N53 800%/0.5msNumber of polyphase impulses >800% and duration <=0.5 ms
28N54 800%/1msNumber of polyphase impulses >800% and duration <=1 ms
29N55 800%/5msNumber of polyphase impulses >800% and duration <=5 ms
30N56 800%/10msNumber of polyphase impulses >800% and duration <=10 ms
31V max 0,1msMaximum impulsive voltage with duration <=0.1 ms, %Un peak
32V max 0,2msMaximum impulsive voltage with duration <=0.2 ms, %Un peak
33V max 0,5msMaximum impulsive voltage with duration <=0.5 ms, %Un peak
34V max 1msMaximum impulsive voltage with duration <=1 ms, %Un peak
35V max 5msMaximum impulsive voltage with duration <=5 ms, %Un peak
36V max 10msMaximum impulsive voltage with duration <=10 ms, %Un peak

Annex C EN 50160:2010 Harmonics Compliance Statistics Log

Annex C EN 50160:2010 Harmonics Compliance Statistics Log
Field No.Field LabelDescription
Section 0 – V1 Harmonic Compliance
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3H02 N1Number of H02 values exceeded percentile limit on phase A/AB
4H03 N1Number of H03 values exceeded percentile limit on phase A/AB
…
51H50 N1Number of H50 values exceeded percentile limit on phase A/AB
52PercRankCompliance percentile rank, %
Section 1 – V2 Harmonic Compliance
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3H02 N1Number of H02 values exceeded percentile limit on phase B/BC
4H03 N1Number of H03 values exceeded percentile limit on phase B/BC
…
51H50 N1Number of H50 values exceeded percentile limit on phase B/BC
52PercRankCompliance percentile rank, %
Section 2 – V3 Harmonic Compliance
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3H02 N1Number of H02 values exceeded percentile limit on phase C/CA
4H03 N1Number of H03 values exceeded percentile limit on phase C/CA
…
51H50 N1Number of H50 values exceeded percentile limit on phase C/CA
52PercRankCompliance percentile rank, %
Section 3 – V1 Harmonic Voltages
1%H02 max1High percentile probability value of H02 on phase A/AB, %
2%H03 max1High percentile probability value of H03 on phase A/AB, %
…
49%H50 max1High percentile probability value of H50 on phase A/AB, %
50%H02 max2Maximum value of H02 on phase A/AB, %
51%H03 max2Maximum value of H03 on phase A/AB, %
…
98%H50 max2Maximum value of H50 on phase A/AB, %
Section 4 – V2 Harmonic Voltages
1%H02 max1High percentile probability value of H02 on phase B/BC, %
2%H03 max1High percentile probability value of H03 on phase B/BC, %
…
49%H50 max1High percentile probability value of H50 on phase B/BC, %
50%H02 max2Maximum value of H02 on phase B/BC, %
51%H03 max2Maximum value of H03 on phase B/BC, %
…
98%H50 max2Maximum value of H50 on phase B/BC, %
Section 5 – V3 Harmonic Voltages
1%H02 max1High percentile probability value of H02 on phase C/CA, %
2%H03 max1High percentile probability value of H03 on phase C/CA, %
…
49%H50 max1High percentile probability value of H50 on phase C/CA, %
50%H02 max2Maximum value of H02 on phase C/CA, %
51%H03 max2Maximum value of H03 on phase C/CA, %
…
98%H50 max2Maximum value of H50 on phase C/CA, %
Section 6 - V1 Interharmonic Compliance
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3H02 N1Number of H02 values exceeded percentile limit on phase A/AB
4H03 N1Number of H03 values exceeded percentile limit on phase A/AB
…
51H50 N1Number of H50 values exceeded percentile limit on phase A/AB
52PercRankCompliance percentile rank, %
Section 7 – V2 Interharmonic Compliance
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3H02 N1Number of H02 values exceeded percentile limit on phase B/BC
4H03 N1Number of H03 values exceeded percentile limit on phase B/BC
…
51H50 N1Number of H50 values exceeded percentile limit on phase B/BC
52PercRankCompliance percentile rank, %
Section 8 – V3 Interharmonic Compliance
1NnvNumber of non-valid 10-min intervals
2NNumber of valid 10-min intervals
3H02 N1Number of H02 values exceeded percentile limit on phase C/CA
4H03 N1Number of H03 values exceeded percentile limit on phase C/CA
…
51H50 N1Number of H50 values exceeded percentile limit on phase C/CA
52PercRankCompliance percentile rank, %
Section 9 – V1 Interharmonic Voltages
1%H02 max1High percentile probability value of H02 on phase A/AB, %
2%H03 max1High percentile probability value of H03 on phase A/AB, %
…
49%H50 max1High percentile probability value of H50 on phase A/AB, %
50%H02 max2Maximum value of H02 on phase A/AB, %
51%H03 max2Maximum value of H03 on phase A/AB, %
…
98%H50 max2Maximum value of H50 on phase A/AB, %
Section 10 - V2 Interharmonic Voltages
1%H02 max1High percentile probability value of H02 on phase B/BC, %
2%H03 max1High percentile probability value of H03 on phase B/BC, %
…
49%H50 max1High percentile probability value of H50 on phase B/BC, %
50%H02 max2Maximum value of H02 on phase B/BC, %
51%H03 max2Maximum value of H03 on phase B/BC, %
…
98%H50 max2Maximum value of H50 on phase B/BC, %
Section 11 - V3 Interharmonic Voltages
1%H02 max1High percentile probability value of H02 on phase C/CA, %
2%H03 max1High percentile probability value of H03 on phase C/CA, %
…
49%H50 max1High percentile probability value of H50 on phase C/CA, %
50%H02 max2Maximum value of H02 on phase C/CA, %
51%H03 max2Maximum value of H03 on phase C/CA, %
…
98%H50 max2Maximum value of H50 on phase C/CA, %

Annex D Online PQ Data

Annex D Online PQ Data
Field LabelDescription
Last recorded EN 50160:2010 voltage incidents data
V1 Var%V1 Voltage variation, +/-%Un
V2 Var%V2 Voltage variation, +/-%Un
V3 Var%V3 Voltage variation, +/-%Un
V1 dUssV1 Steady state voltage change, %Un
V1 dUmaxV1 Maximum voltage change, %Un
V2 dUssV2 Steady state voltage change, %Un
V2 dUmaxV2 Maximum voltage change, %Un
V3 dUssV3 Steady state voltage change, %Un
V4 dUmaxV3 Maximum voltage change, %Un
V1 PstV1 Voltage Pst
V2 PstV2 Voltage Pst
V3 PstV3 Voltage Pst
V1 PltV1 Voltage Plt
V2 PltV2 Voltage Plt
V3 PltV3 Voltage Plt
V1 THDV1 Voltage THD, %
V2 THDV2 Voltage THD, %
V3 THDV3 Voltage THD, %
NSeq Unb%Negative-sequence voltage unbalance, %
ZSeq Unb%Zero-sequence voltage unbalance, %
Freq Var%Frequency variation, +/-%Fn
V1 IntShort voltage interruption, V1 residual voltage, %Un
V2 IntShort voltage interruption, V2 residual voltage, %Un
V3 IntShort voltage interruption, V3 residual voltage, %Un
Int dtShort voltage interruption, duration, ms
V1 DipVoltage dip, V1 residual voltage, %Un
V2 DipVoltage dip, V2 residual voltage, %Un
V3 DipVoltage dip, V3 residual voltage, %Un
Dip dtVoltage dip, duration, ms
V1 SwlVoltage swell, V1 voltage, %Un
V2 SwlVoltage swell, V2 voltage, %Un
V3 SwlVoltage swell, V2 voltage, %Un
Swl dtVoltage swell, duration, ms
V1 ImpV1 Transient overvoltage, %Un peak
V1 Imp dtV1 Transient duration, µs
V2 ImpV2 Transient overvoltage, %Un peak
V2 Imp dtV2 Transient duration, µs
V3 ImpV3 Transient overvoltage, %Un peak
V3 Imp dtV3 Transient duration, µs
V1 Sig%V1 signaling voltage, %Un
V2 Sig%V2 signaling voltage, %Un
V3 Sig%V3 signaling voltage, %Un
Present IEC 61000-4-30 measurements and indication data
V1 rms(1/2)V1 rms(1/2) commencing at fundamental zero crossing
V2 rms(1/2)V2 rms(1/2) commencing at fundamental zero crossing
V3 rms(1/2)V3 rms(1/2) commencing at fundamental zero crossing
V1 rms(1/2) TmV1 rms(1/2) timestamp, seconds
V1 rms(1/2) TmmcsV1 rms(1/2) timestamp, fractional second, µs
V2 rms(1/2) TmV2 rms(1/2) timestamp, seconds
V2 rms(1/2) TmmcsV2 rms(1/2) timestamp, fractional second, µs
V3 rms(1/2) TmV3 rms(1/2) timestamp, seconds
V3 rms(1/2) TmmcsV3 rms(1/2) timestamp, fractional second, µs
I1 rms(1/2)I1 rms(1/2) coincident current
I2 rms(1/2)I2 rms(1/2) coincident current
I3 rms(1/2)I3 rms(1/2) coincident current
10/12c Tm10/12-cycle block timestamp, seconds
10/12c Tmmcs10/12-cycle block timestamp, fractional second
10/12c BlockNo10/12-cycle block number (1-3000)
150/180c BlockNo150/180-cycle block number (1-200)
10/12c Flag10/12-cycle interval flag (0=valid, 1=flagged)
150/180c Flag150/180-cycle interval flag (0=valid, 1=flagged)
10s Flag10-s interval flag (0=valid, 1=flagged)
10m Flag10-min interval flag (0=valid, 1=flagged)
2h Flag2-hour interval flag (0=valid, 1=flagged)

Annex E Generic Parameters Group

Annex E Generic Parameters Group
Field LabelDescription
V1V1 voltage
V2V2 voltage
V3V3 voltage
V4V4 voltage
V12V12 voltage
V23V23 voltage
V31V31 voltage
I1I1 current
I2I2 current
I3I3 current
I4I4 current
InIn current
I1xI1x current (extended range)
I2xI2x current (extended range)
I3xI3x current (extended range)
I4xI4x current (extended range)
InxInx current (extended range)
V ZERO-SEQZero-sequence voltage
I ZERO-SEQZero-sequence current
Ix ZERO-SEQIx Zero-sequence current (extended range)
V UNB%Voltage unbalance
I UNB%Current unbalance
Ix UNB%Ix current unbalance (extended range)
FREQFrequency
V1 THDV1 THD
V2 THDV2 THD
V3 THDV3 THD
V4 THDV4 THD
I1 THDI1 THD
I2 THDI2 THD
I3 THDI3 THD
I4 THDI4 THD
V1 THD/IV1 interharmonic THD
V2 THD/IV2 interharmonic THD
V3 THD/IV3 interharmonic THD
V4 THD/IV4 interharmonic THD
I1 THD/II1 interharmonic THD
I2 THD/II2 interharmonic THD
I3 THD/II3 interharmonic THD
I4 THD/II4 interharmonic THD
I1 TDDI1 TDD
I2 TDDI2 TDD
I3 TDDI3 TDD
I4 TDDI4 TDD
I1 KFI1 K-Factor
I2 KFI2 K-Factor
I3 KFI3 K-Factor
I4 KFI4 K-Factor
V1 CFV1 Crest Factor
V2 CFV2 Crest Factor
V3 CFV3 Crest Factor
V4 CFV4 Crest Factor
I1 CFI1 Crest Factor
I2 CFI2 Crest Factor
I3 CFI3 Crest Factor
I4 CFI4 Crest Factor
V1 rms(1/2)V1 rms(1/2), commencing at fundamental zero crossing
V2 rms(1/2)V2 rms(1/2), commencing at fundamental zero crossing
V3 rms(1/2)V3 rms(1/2), commencing at fundamental zero crossing
I1 rms(1/2)I1 rms(1/2) coincident current
I2 rms(1/2)I2 rms(1/2) coincident current
I3 rms(1/2)I3 rms(1/2) coincident current
V1 Sig%V1 signaling voltage magnitude, %Un
V2 Sig%V2 signaling voltage magnitude, %Un
V3 Sig%V3 signaling voltage magnitude, %Un

Annex F EN 50160:2010 PQ Event Log Report

Sample EN 50160:2010 PQ event log report (screenshot). Drawing not reproduced on this page. See page 33 of the PDF.

Annex G EN 50160:2010 Compliance Report

Sample EN 50160:2010 Compliance Report, report page 1: Tables 1-6 (screenshot). Drawing not reproduced on this page. See page 34 of the PDF.

Sample EN 50160:2010 Compliance Report, report page 2: Tables 7-8 (screenshot). Drawing not reproduced on this page. See page 35 of the PDF.

Sample EN 50160:2010 Compliance Report, report page 3: Tables 8 (continued)-11 (screenshot). Drawing not reproduced on this page. See page 36 of the PDF.

Sample EN 50160:2010 Compliance Report, report page 4: Tables 12-13 (screenshot). Drawing not reproduced on this page. See page 37 of the PDF.