PM180 disturbance direction detection application note
High Performance Analyzer PM180 — Disturbance Direction Detection Application Note
Transcribed from the SATEC document Disturbance Direction Detection, BG0636 REV.A1, May 2021 (PDF, 6 pages, 130 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.
Revision history
| A1 | May 2021 | Initial release |
1 General
The disturbance direction detection function of the PM180 allows identifying and indicating the location of the voltage dip and swell source relative to the monitoring point where the device is installed. This function is available in devices with firmware V31.XX.43 and higher.
1.1 Measurement Techniques
Voltage dips and swells are commonly caused by short circuits, starting a large induction motor or energizing a power transformer.
The PM180 uses synchronous voltage and current waveforms recorded before and during an event to determine the location of the disturbance source. Depending on the characteristics of the fault, the device can apply different methods of analyzing the collected data to give the most reliable indication of the direction of the fault.
Symmetrical (three-phase) dips and swells are analyzed using the relative level of the fault or inrush current and the fundamental power angle. Asymmetric (single-phase and two-phase) dips and swells can be analyzed using the negative sequence power angle or, in the case of insufficient information, using the fundamental power angle.
1.2 Disturbance Direction Indication
When disturbance direction detection is enabled in the device (see instructions below), the analysis results are stored along with the dip and swell characteristics in the PQ event log and can be reported using the supplied PAS software tool or via customer application software. See the PM180 Modbus Reference Guide for the information on organizing and accessing the PQ event log data from a client application.
The disturbance direction indication gives the direction of the fault source (downstream or upstream) in relation to the monitoring point and the confidence level of the direction information (high, medium, or low). The picture below shows how the direction of the disturbance is indicated in the PAS PQ event report.
PAS PQ Log screen (PM180_221) showing voltage dip events with direction and confidence indicated in the Fault Category column, for example "Voltage dip (downstream, high confidence)". Drawing not reproduced on this page. See page 4 of the PDF.
2 Configuring Disturbance Direction Detection
The use of the disturbance direction function does not require special configuration of the device, except for the activation of the disturbance direction indication. Use the supplied PAS software tool to enable or disable this function in your device.
2.1 Enabling Direction Indication in PQ Event Reports
The disturbance direction setting is displayed under the Recording Options section on the Advanced PQ Setup tab for all power quality standards except IEEE 1159 (see the following section).
To configure the disturbance direction option, select Memory/Log in the Meter Setup menu and then click on the corresponding Advanced PQ Setup tab. The picture below shows an example of the disturbance direction detection setting in the EN 50160 advanced setup tab.
Set the Disturbance Direction Detection option to “Enabled” to allow disturbance direction indication and send your settings to the device.
PAS Log Setup screen (PM180_221), EN 50160:2010 Advanced Setup tab, with Disturbance Direction Detection set to Enabled under Recording Options. Drawing not reproduced on this page. See page 5 of the PDF.
2.2 Enabling Direction Indication in IEEE 1159 PQ Reports
To configure the disturbance direction option, select Memory/Log in the Meter Setup menu and then click on the IEEE 1159 Recorder tab. Check the Disturbance Direction checkbox to enable disturbance direction indication and send your settings to the device.
PAS Log Setup screen (PM180_217), IEEE 1159 PQ Recorder tab, with the Disturbance Direction checkbox ticked. Drawing not reproduced on this page. See page 6 of the PDF.
Downloads and related
- Download the PDF (BG0636 REV.A1, 130 KB)
- Read the PDF in the document library
- Product support: answers, documents and videos
- All application notes as web pages
- How do I replace the backup battery in a PM180?
- Which PM180 display and options are fitted or required?
- What information and records should I preserve before a PM180 service or change?
Questions about this document? Use the contact form.