PM180 · APPLICATION NOTE

PM180 Bay Control Unit (BCU) application note

expertmeter™ PM180 PM180 Series SUBSTATION AUTOMATION UNIT Bay Controller Unit BCU Application Note

Transcribed from the SATEC document PM180 Series Substation Automation Unit Bay Controller Unit BCU Application Note, BG0531 Rev. A2, Oct 2013 (PDF, 19 pages, 241 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.

1 General

This application note describes functions, operation and configuring of the bay control unit integrated in the expertmeter™ PM180. For detailed information on operating the expertmeter™ PM180 and communication settings refer to the expertmeter™ PM180 Operation Manual.

The bay control unit provides fully automated control of substation switching devices. After switches are configured in the device, no additional logic is normally required for controller operation, except of interlocking logic.

Bay control solutions can be customized via control logic using a variety of expertmeter™ PM180 digital I/O and analog measurement capabilities for the circuit switch/breaker position indication, interlocking and control.

General bay controller features:

2 Bay Controller Operation

The bay control unit provides control of up to two circuit breakers and 14 circuit switches depending on the selected configuration.

The switching devices can be operated either remotely via communication ports, or locally via setpoint control equations. Remote control permissions can be restricted by enabling control commands for specific control ports or clients depending on the device control mode.

See Section 4.1 for information on configuring switching devices via PAS.

See Sections 3.1 and 3.2 for information on monitoring and control of switching devices via IEC 61850 and via Modbus communications.

2.1 Switch Position Monitoring

Position Indication

The bay controller can monitor signals from three-phase switches with general two-contact or per-phase six-contact position indication. Phase A contact inputs should be used in case of general switch position indication using two contacts.

Positions of switch poles can be indicated via the device digital inputs, control logic equations, controllable event flags, or via remote indication from other substation controllers using inter-device IEC 61850 GOOSE communications.

The position of each pair of the N.O. and N.C. contacts is allowed to be signaled by one of the contacts. In this case its complementary status is taken for the opposite contact.

In case of three-pole position monitoring with six contacts, the general position of a switch is evaluated in the following way:

  1. In the event all poles have same position, it is taken as a general switch position.
  2. In the event one of the poles is in the bad position (both contacts are closed), the general position is indicated as bad.
  3. In other cases, the switch position is indicated as intermediate.

A position change is normally detected in a half cycle time.

Any switch position change is automatically logged to the device Event log with the time of change.

Position Substitution

A switch position can be manually substituted via communications in case that the actual position cannot be directly obtained by the controller, for example, when a switch is not accessible or not operational, while it blocks operation of controllable switches.

Switches with a substituted position are not allowed to be operated.

Indication of Breaker Trips

Uncontrollable breaker pole position changes from the closed to open state are indicated as breaker trips and are reported via the Modbus fault disconnect alarm registers and via the IEC 61850 switch controller data object AlmFlt.

The breaker trip indication is automatically reset in 5 seconds.

2.2 Interlocking Logic

Interlocking Control

Interlocking control logic blocks any switch control commands until predefined conditions are met. Interlocking logic is defined via setpoint control equations that must be evaluated to TRUE for the switch control commands to be executed.

If interlocking is not applicable to the switch, set the interlocking control setting to TRUE to allow unconditional command execution.

Interlocking Bypass Logic

The interlocking bypass option allows to temporary override interlocking logic. This is a one-shot action that is activated for a limited time and is controlled by an interlocking bypass timeout.

Interlocking bypass is enabled via a setpoint control equation, which normally monitors the status of an external “Interlocking OFF” switch, but can also track the status of a memorized event flag controlled via communications.

Interlocking bypass is active until the first control command is executed or until the bypass timeout expires.

The bypass control logic equation must be reset to FALSE in order to recharge this option before next use.

2.3 Controls

2.3.1 Control Parameters

See Section 4.1 for more information on configuring switching devices via PAS and for the full list of configurable options. The following gives explanations of control options and how they affect the switch operation.

Control Outputs

The bay controller provides control of up to 6 control outputs: one close command output, one or two open command outputs, one select-close output, and one or two select-open outputs.

Any of the 64 relay outputs available in the device or none of them can be selected as a switch control output.

Control outputs are not normally allowed to reuse same output relays. The only exception is made for the select-close and select-open outputs that may use the same relay for securing both closing and opening commands.

Control outputs are optional. When none of them is defined, the full switch functionality is still available, including position monitoring, interlocking and modeling control operations. Such a switch is seen as “virtual” that is not controllable, but which position indication may be used in interlocking equations of controllable switches.

When switch operation is enabled, the relay outputs are automatically put in unlatched mode with normal polarity, which will not be allowed to change. Relay outputs found under control of the bay controller are not available for direct control via communications or via control logic.

Command Duration

This parameter specifies the default duration of the output pulse for commands received via Modbus communications and from setpoint control equations.

In IEC 61850 Operate requests, the pulse duration can be set via the IEC 61850 CSWI switch controller node configuration by a non-zero CSWI$CF$pulsConfig$onDur data attribute. When it is zero, the default command pulse duration is used instead.

The pulse duration is supervised by the immobility and command termination timeouts. In case that either of them expires while the pulse continues, the relay outputs are deactivated and the operation is abnormally terminated. If the pulse is shorter than it will take for a switch to change its position, set the start moving timeout to more time than the expected duration of the pulse.

Pulse Duration Control Logic

A close/open command pulse is normally removed after the configured pulse duration expires. The bay controller allows a command pulse to be extended over the configured duration until a specific condition is met. The reason may be keeping the output pulse active until the new correct end position is reached, or until the line voltage is removed, or probably other binary or analog trigger reaches the expected value.

It is called an adaptive pulse and is handled by a setpoint logic equation that controls the pulse duration.

If a control equation is used, the output pulse will remain active until the logic equation is reset to FALSE. Operation of control logic is supervised by the immobility and command termination timeouts. In case that either of them expires while the pulse continues, the relay outputs are deactivated and the operation is abnormally terminated.

In all cases, the actual pulse duration is never less than the configured pulse duration. If you use the control logic, set the command pulse duration to a smallest reasonable value.

Start Moving Timeout

This parameter controls command execution supervision. It specifies the switch immobility timeout - the time that takes for a switch to start moving after command execution.

The parameter is optional. If you set it to zero, command execution is not supervised. In this case a control operation is immediately terminated after deactivating control outputs as the command pulse ends.

When the immobility timeout is used, command execution is supervised and a control operation is terminated and reported after the last of the two events happens: the command pulse ends and the switch position changes to either the intermediate, or a new end position. The immobility timer is reset and no more supervised as the switch position changes.

In case that the immobility timeout is used and the switch position does not change before the timeout expires, the active control outputs are deactivated and the operation is abnormally terminated by timeout.

Command Termination Timeout

This parameter defines the total operation supervision time since the command is taken for execution.

A control operation has to be terminated before the timeout expires. If the operation has not been completed before the command termination timer expires, the active control outputs are deactivated and the operation is abnormally terminated by timeout.

2.3.2 Control Command Execution

Control operations can be activated either via setpoint control equations, or via communications by commands sent via Modbus switch control registers or via the IEC 61850 CSWI switch controller nodes.

The IEC 61850 switch control interface supports direct control commands with enhanced security.

A control command is refused when one of the following conditions is encountered:

  1. The communication client is not permitted to issue control commands because of unacceptable switching authority: either a client control port is disabled or blocked, or the device is in local control mode (actual for IEC 61850 clients only).
  2. The switch is not controllable because of improper configuration.
  3. A control command is already in execution.
  4. The requested switch position has been reached.
  5. The switch is in an invalid position.
  6. Switch position is indicated by a substituted value.
  7. Control commands for the switch are blocked by interlocking logic.
  8. One of the control outputs is blocked by control logic.

When a remote control command is rejected, the cause is reported via a Modbus command termination status register, and via an IEC 61850 reporting service by the LastApplError variable in case of the IEC 61850 Operate request.

When a control command is accepted, the control operation is executed according to the following integrated logic:

  1. If the control relay outputs are configured, they are all activated together and the pulse duration timer is started.
  2. The command termination timer is started.
  3. If the start moving timeout is defined, the switch immobility timer is started.
  4. If the pulse duration timer expires while the pulse duration control logic is not used or is evaluated to FALSE, the control outputs are deactivated.
  5. If the pulse duration control logic is defined and is evaluated to FALSE, while the pulse duration timer has just expired, the control outputs are deactivated.
  6. If the control outputs are deactivated and the immobility timer is not running, the control operation is terminated.
  7. If the immobility timer is running and the switch position changes to an intermediate state, or reaches the target position, the immobility timer is reset and, if the control outputs are not active, the control operation is terminated.
  8. If the immobility timer expires, active control outputs are deactivated and the control operation is terminated by timeout.
  9. If the command termination timer expires, active control outputs are deactivated and the control operation is terminated by timeout.

The operation activation and termination events are automatically logged with the timestamp to the device Event log.

Termination of a remote command with the cause is reported via a Modbus command termination status register, and via an IEC 61850 Operate response service. In case of abnormal termination of an IEC 61850 Operate request, the cause is also reported via an IEC 61850 reporting service by a LastApplError variable.

2.4 Operation Counters

The expertmeter™ PM180 provides operation counters that count the total number of switch operations. When a close-to-open position change is detected, the switch operation counter is incremented.

Switch operation counters can be reset via Modbus communications and via PAS from the Monitor/Reset dialog.

2.5 Using Control Logic

Monitoring Switch Operations

The expertmeter™ PM180 provides internal variables related to switch operation for use in interlocking logic and in switch control equations. The following table lists parameters that can be used for monitoring of the switch position and command execution in setpoint control equations.

Input ParameterRangeDescription
XCBRn_Pos, XSWIn_PosIntermediate, OFF ON, BadSwitch position indication
XCBRn_OpCls, XSWIn_OpClsON=operation in execution, OFF=operation terminatedSwitch operation “Close” indication
XCBRn_OpOpn, XSWIn_OpOpnON=operation in execution, OFF=operation terminatedSwitch operation “Open” indication
XCBRn_OpCnt, XSWIn_OpCnt0-9999Switch operation counter
ExtInd1…ExtInd128OFF, ONSingle-point external indication
ExtInd1:2…ExtInd127:128Intermediate, OFF, ON, BadDouble-point external indication
ExtiVal1…ExtiVal32External integer measured values
ExtfVal1…ExtfVal32External floating-point measured values
REMOTE CONTROLOFF, ONInternal flag available for control via setpoint control logic. Defaulted to OFF.

All of the listed parameters are also available for monitoring via Modbus communications. See Section 3.2 for details.

Control Commands

The following table lists commands that are activated via setpoint control equations and may be used for local switch control and for control of the switching authority.

Control ActionTargetDescription
CLOSE SWITCHXCBR1-XCBR2, XSWI1-XSWI14Activates breaker/switch close operation when a control equation evaluates to TRUE
OPEN SWITCHXCBR1-XCBR2, XSWI1-XSWI14Activates breaker/switch open operation when a control equation evaluates to TRUE
REMOTE CONTROLPuts REMOTE CONTROL to ON while a control equation evaluates to TRUE. Tracks the output of control logic.
UNBLOCK CONTROL PORTALL, COM1, COM2, COM3, COM4, COM5, USB, EthernetEnables control operations via blocked control ports while a control equation evaluates to TRUE. Tracks the output of control logic.

2.6 Switching Permissions

Secure switching operations require that only one source is allowed to issue control commands at a time. Two mechanisms are provided in the device for restriction of the switching authority for users: a general permission based on the device local/remote control mode, and individual permissions based on the client connection ports and network addresses.

2.6.1 Local/Remote Control

The expertmeter™ PM180 has the internal REMOTE CONTROL flag (found within the STATIC EVENTS data group) that is handled via setpoint control logic. The control equation normally tracks the status of an external “Local/Remote” switch via a digital input and puts the device in remote mode with the REMOTE CONTROL action when the switch is in the “remote” position.

While the status of REMOTE CONTROL is OFF, control commands from IEC 61850 clients, commonly at station level, are denied. The Loc attribute in IEC 61850 logical nodes containing controls indicates the complementary status of the REMOTE CONTROL flag. Since REMOTE CONTROL is defaulted to FALSE, it must be set to ON via a control equation to allow control operations via IEC 61850.

Modbus communications is not directly affected by the status of the REMOTE CONTROL flag and may be used for local control via a local terminal station, which can be connected to the expertmeter™ PM180 via any available port, including serial ports, USB and Ethernet.

In cases when a local terminal station operates via IEC 61850, or remote Modbus communications is available for multiple users, or multiple clients may have access to the device via either protocol in REMOTE mode, per-client control permissions must be used.

2.6.2 Restricting Control Ports

Remote connection points via which direct control commands can be received are called direct control ports. For local ports, a connection point is identified by a physical port, while for Ethernet users a remote connection point is identified by the client IP address.

See Section 4.2 for more information on configuring direct control ports via PAS.

Control permissions may be permanently allowed or disabled, or be controllable via setpoint control logic for any of the ports.

To use controllable permissions, the control ports should be marked as “Blocked”. The control permissions are given to a blocked port via setpoint control equations that normally monitor the status of the REMOTE CONTROL flag and unblock the port to which the switching authority is currently granted.

3 Bay Controller Communications

3.1 IEC 61850 Communications

See the expertmeter™ PM180 IEC 61850 reference guide for more information on implementing IEC 61850 communications in the expertmeter™ PM180. The reference guide also provides instructions on configuring IED names and setting up inter-device GOOSE communications.

3.1.1 Bay Control Nodes and Objects

The expertmeter™ PM180 provides the dedicated CTRL logical device linked to the bay control unit. The table below shows mapping of data nodes and data objects associated with supervision, monitoring and control of switching devices.

The following designation are used:

The breaker and switch names are normally preceded with prefixes (not shown in the table) that designate the type and location of the switch and can be configured for each apparatus via the expertmeter™ PM180 Switching Device Setup (see Section 4.1).

Bay control nodes and objects (pages 11–12)
Data Object and AttributeRangeDescriptionMapping
Circuit breaker nodes
XCBRn$ST$Loc$stValOFF, ONLocal control behaviorComplement of REMOTE CONTROL
XCBRn$ST$Pos$stValIntermediate, OFF, ON, badGeneral position indicationXCBRn_Pos
XCBRn$ST$BlkOpn$stValOFF=enabled, ON=blockedBlock opening indicationComplement of the interlocking logic output
XCBRn$ST$BlkCls$stValOFF=enabled, ON=blockedBlock closing indicationComplement of the interlocking logic output
XCBRn$ST$OpCnt$stVal0-9999Operation counterXCBRn_OpCnt
XCBRn$ST$AlmFlt$stValOFF, ON=alarm indicationFault disconnect alarmFault disconnect alarm indication
Circuit switch nodes
XSWIn$ST$Loc$stValOFF, ONLocal control behaviorComplement of REMOTE CONTROL
XSWIn$ST$Pos$stValIntermediate, OFF, ON, badGeneral position indicationXSWIn_Pos
XSWIn$ST$BlkOpn$stValOFF=enabled, ON=blockedBlock opening indicationComplement of the interlocking logic output
XSWIn$ST$BlkCls$stValOFF=enabled, ON=blockedBlock closing indicationComplement of the interlocking logic output
XSWIn$ST$OpCnt$stVal0-9999Operation counterXSWIn_OpCnt
Switch interlocking indication nodes
CILOn$ST$EnaOpn$stValOFF=blocked, ON=enabledEnable Open indicationOpen interlocking logic output
CILOn$ST$EnaCls$stValOFF=blocked, ON=enabledEnable Close indicationClose interlocking logic output
CILOn$SV$EnaOpn$subEnaOFF=disabled, ON=enabledSubstitution enable for EnaOpnInterlocking bypass logic output
CILOn$SV$EnaOpn$subValOFF=blocked, ON=enabledSubstitution value for EnaOpnInterlocking bypass logic output
CILOn$SV$EnaCls$subEnaOFF=disabled, ON=enabledSubstitution enable for EnaClsInterlocking bypass logic output
CILOn$SV$EnaCls$subValOFF=blocked, ON=enabledSubstitution value for EnaClsInterlocking bypass logic output
Switch controller nodes
CSWIn$CO$Pos$ctlValOFF=operation Open, ON=operation CloseGeneral switch control commandXCBRn_OpOpn, XSWIn_OpOpn, XCBRn_OpCls, XSWIn_OpCls
CSWIn$ST$Loc$stValOFF, ONLocal control behaviorComplement of REMOTE CONTROL
CSWIn$ST$Pos$stValIntermediate, OFF, ON, badGeneral position indicationXCBRn_Pos/XSWIn_Pos
CSWIn$SV$Pos$subEnaOFF=disabled, ON=enabledSubstitution enable for PosWriteable
CSWIn$SV$Pos$subValIntermediate, OFF, ON, badSubstitution value for PosWriteable
CSWIn$CF$Pos$pulseConfigonDur=0-60000Command pulse configurationReplaces default pulse duration

3.1.2 Switch Control Model

The direct-with-enhanced-security control model is used for apparatus control operations. The command execution is supervised and is reported via the CommandTermination service as the operation completes. If the Start Moving Timeout is defined in the switching device setup, the switching operations are supervised for switch position change before reporting on operation termination.

In case of an unsuccessful command execution, the command termination report is extended by a LastApplError variable indicating the reason in the AddCause attribute. The supported AddCause values are listed in the following table.

Supported AddCause values
ValueDescription
1Not-supported
2Blocked-by-switching-hierarchy
4Invalid-position
5Position-reached
8Blocked-by-Mode
9Blocked-by-process
10Blocked-by-interlocking
12Command-already-in-execution
13Blocked-by-health
16Time-limit-over

3.2 Modbus Communications

See the expertmeter™ PM180 MODBUS reference guide for more information on operating the expertmeter™ PM180 via Modbus.

3.2.1 Bay Control Registers

The following table shows locations of Modbus registers associated with monitoring and control of switching devices and with inter-device GOOSE communications.

The following designations are used:

Bay control Modbus registers (pages 13–15)
AddressPoint IDDescriptionOptions/RangeTypeR/W
Switch Position Indication
29440-294710x8A00Switch position (Pos)00=intermediate, 01=OFF, 10=ON, 11=bad-stateUINT32R
+0,10x8A00XCBR1_Pos00/01/10/11TRG
+2,30x8A01XCBR2_Pos00/01/10/11TRG
+4,50x8A02XSWI1_Pos00/01/10/11TRG
……
+30,310x8A0FXSWI14_Pos00/01/10/11TRG
Operation-Open Indication
29568-295690x8B00Operation Open activation indication: Bit 0: XCBR1_OpOpn Bit 1: XCBR2_OpOpn Bit 2: XSWI1_OpOpn … Bit 15: XSWI14_OpOpn0x00000000 - 0x0000FFFF Bit value: 0=not active, 1=activatedUINT32R
0x8B00XCBR1_OpOpn0/1TRG
0x8B01XCBR2_OpOpn0/1TRG
0x8B02XSWI1_OpOpn0/1TRG
…
0x8B0FXSWI14_OpOpn0/1TRG
Operation-Close Indication
29632-296330x8B80Operation Close activation indication: Bit 0: XCBR1_OpCls Bit 1: XCBR2_OpCls Bit 2: XSWI1_OpCls … Bit 15: XSWI14_OpCls0x00000000 - 0x0000FFFF Bit value: 0=not active, 1=activatedUINT32R
0x8B80XCBR1_OpCls0/1TRG
0x8B81XCBR2_OpCls0/1TRG
0x8B82XSWI1_OpCls0/1TRG
…
0x8B8FXSWI14_OpCls0/1TRG
29696-29727Operation Counters (resettable)
+0,10x8C00XCBR1_OpCnt0-9999UINT32R/W
+2,30x8C01XCBR2_OpCnt0-9999UINT32R/W
+4,50x8C02XSWI1_OpCnt0-9999UINT32R/W
……
+30,310x8C0FXSWI14_OpCnt0-9999UINT32R/W
Switch Remote Control Registers
44458-44459Switch ON/Close command register: Bit 0: XCBR1 Bit 1: XCBR2 Bit 2: XSWI1 … Bit 15: XSWI140x00000000 - 0x0000FFFF Bit value: 0=no effect, 1=ONUINT32W
44460-44461Switch OFF/Open command register: Bit 0: XCBR1 Bit 1: XCBR2 Bit 2: XSWI1 … Bit 15: XSWI140x00000000 - 0x0000FFFF Bit value: 0=no effect, 1=OFFUINT32W
44462-44463Position substitution enable command register (subEna): Bit 0: XCBR1 Bit 1: XCBR2 Bit 2: XSWI1 … Bit 15: XSWI140x00000000 - 0x0000FFFF Bit value: 0=no effect, 1=enableUINT32W
44464-44465Position substitution disable command register (~subEna): Bit 0: XCBR1 Bit 1: XCBR2 Bit 2: XSWI1 … Bit 15: XSWI140x00000000 - 0x0000FFFF Bit value: 0=no effect, 1=disableUINT32W
44466-44481Position substitution value registers (subVal)00=intermediate, 01=OFF, 10=ON, 11=bad-state
+0XCBR1 position substitution valueUINT16W
+1XCBR2 position substitution valueUINT16W
+2XSWI1 position substitution valueUINT16W
……
+15XSWI14 position substitution valueUINT16W
Switch Status Registers
44514-44515Operation Open activation indication (alias): Bit 0: XCBR1_OpOpn Bit 1: XCBR2_OpOpn Bit 2: XSWI1_OpOpn … Bit 15: XSWI14_OpOpn0x00000000 - 0x0000FFFF Bit value: 0=not active, 1=activatedUINT32R
44516-44517Operation Close activation indication (alias): Bit 0: XCBR1_OpCls Bit 1: XCBR2_OpCls Bit 2: XSWI1_OpCls … Bit 15: XSWI14_OpCls0x00000000 - 0x0000FFFF Bit value: 0=not active, 1=activatedUINT32R
44518-44519Enable Opening status (EnaOpn): Bit 0: XCBR1 Bit 1: XCBR2 Bit 2: XSWI1 … Bit 15: XSWI140x00000000 - 0x0000FFFF Bit value: 0= blocked, 1=enabledUINT32R
44520-44521Enable Closing status (EnaCls): Bit 0: XCBR1 Bit 1: XCBR2 Bit 2: XSWI1 … Bit 15: XSWI140x00000000 - 0x0000FFFF Bit value: 0= blocked, 1=enabledUINT32R
44522-44523Position substitution enable status (subEna): Bit 0: XCBR1 Bit 1: XCBR2 Bit 2: XSWI1 … Bit 15: XSWI140x00000000 - 0x0000FFFF Bit value: 0=actual position, 1=substituted positionUINT32R
44524-44525Fault disconnect alarm status (AlmFlt): Bit 0: XCBR1 Bit 1: XCBR2 Bit 2: XSWI1 … Bit 15: XSWI140x00000000 - 0x0000FFFF Bit value: 0=no alarm, 1=alarmUINT32R
44526-44541Command termination status0=Success, 1=Not-supported, 2=Blocked-by-switching-hierarchy, 4=Invalid-position, 5=Position-reached, 8=Blocked-by-Mode, 9=Blocked-by-process, 10=Blocked-by-interlocking, 12=Command-already-in-execution, 13=Blocked-by-health, 16=Time-limit-overUINT16R
+0XCBR1 command termination statusUINT16R
+1XCBR2 command termination statusUINT16R
+2XSWI1 command termination statusUINT16R
……
+15XSWI14 command termination statusUINT16R
28160-28223External Integer Measured Values
+0,10x8000ExtiVal1INT32R
+2,30x8001ExtiVal2INT32R
……INT32R
+62,630x801FExtiVal32INT32R
28288-28321External Float Measured Values
+0,10x8100ExtfVal1FLOAT32R
+2,30x8101ExtfVal2FLOAT32R
……FLOAT32R
+62,630x801FExtfVal32FLOAT32R
External Indication
28416-284170x8200ExtInd1:32 Bit 0: ExtInd1 … Bit 32: ExtInd320x00000000-0xFFFFFFFF Bit value: 0=OFF, 1=ONUINT32R
28480-284810x8220ExtInd33:64 Bit 0: ExtInd33 … Bit 32: ExtInd640x00000000-0xFFFFFFFF Bit value: 0=OFF, 1=ONUINT32R
28544-285450x8240ExtInd65:96 Bit 0: ExtInd65 … Bit 32: ExtInd960x00000000-0xFFFFFFFF Bit value: 0=OFF, 1=ONUINT32R
28608-286090x8260ExtInd97:128 Bit 0: ExtInd97 … Bit 32: ExtInd1280x00000000-0xFFFFFFFF Bit value: 0=OFF, 1=ONUINT32R
0x8200ExtInd10/1UINT32TRG
0x8201ExtInd20/1UINT32TRG
……
0x827FExtInd1280/1UINT32TRG

3.2.2 Switch Control Model

The direct-with-enhanced-security control model is used for apparatus control operations as described in Section 3.1.2 above. The command execution is supervised and is reported via the command termination status registers 44526-44541 as the control operation is terminated. The Operation-Open and Operation-Close indication registers can be monitored to follow the termination of the activated operation.

4 Configuring the Bay Controller

4.1 Configuring Switching Devices

To configure the switching devices for monitoring and control via the expertmeter™ PM180 bay control unit:

  1. Select Bay Control Setup from the Meter Setup menu.

PAS screen: PM180 - Bay Control Setup, Switching Device Setup tab. Drawing not reproduced on this page. See page 16 of the PDF.

  1. Choose a switching device to configure in the Switch Name box and setup required switch attributes, position indication inputs and control outputs. See the table below for available options. See Section 2 for the explanations and configuration guidelines.
  2. Select Enabled in the Switch Enabled box to activate switch monitoring.
  3. Repeat the setup for other switches you wish to configure, and then send your setup to the device and save to the device database. Notice that switch name prefixes will not be available in PAS indications unless you saved the switch setup in the device database on your PC.
Switching device setup options (pages 16–18)
ParameterOptionsDefaultDescription
General
Switch NameXCBR1-XCBR2, XSWI1-XSWI14Identification name of a switching device
IEC 61850 Name Prefix1-5 ASCII charactersName prefix to be displayed as a part of a switch name in IEC 61850 and in PAS.
Switch TypeLoad break switch, Disconnector, Earthing switch, High speed earthing switch, BreakerIEC 61850 switch type. Not changeable for breakers.
Switch EnabledDisabled, EnabledDisabledEnables switch monitoring and control
Position Indication
Phase A N.O. Contact IndicationNone, DI1-DI48, SP1-SP64, FLAG1-FLAG64 ExtInd1-ExtInd128Normally open contact input of phase A and for general switch position indication in case of two-contact position monitoring
Phase A N.C. Contact IndicationNone, DI1-DI48, SP1-SP64, FLAG1-FLAG64 ExtInd1-ExtInd128Normally closed contact input of phase A and for general switch position indication in case of two-contact position monitoring
Phase B N.O. Contact IndicationNone, DI1-DI48, SP1-SP64, FLAG1-FLAG64 ExtInd1-ExtInd128Normally open contact input of phase B
Phase B N.C. contact IndicationNone, DI1-DI48, SP1-SP64, FLAG1-FLAG64 ExtInd1-ExtInd128Normally closed contact input of phase B
Phase C N.O. Contact IndicationNone, DI1-DI48, SP1-SP64, FLAG1-FLAG64 ExtInd1-ExtInd128Normally open contact input of phase C
Phase C N.C. contact indicationNone, DI1-DI48, SP1-SP64, FLAG1-FLAG64 ExtInd1-ExtInd128Normally closed contact input of phase C
Interlocking
Enable close logic equationNone, SP1-SP64, TRUESetpoint control equation enabling switch close commands. None = unconditionally blocked, TRUE = unconditionally enabled.
Enable open logic equationNone, SP1-SP64, TRUESetpoint control equation enabling switch open commands. None = unconditionally blocked, TRUE = unconditionally enabled.
Interlocking Bypass Logic EquationNone, SP1-SP64Setpoint control equation overriding interlocking logic. Active within the bypass timeout interval. None = not used.
Interlocking Bypass Timeout, s1-600 s30Interlocking bypass activity timeout
Control
Close control outputNone, RO1-RO24Command output for switch close commands
Open control outputNone, RO1-RO24Command output for switch open commands
Open-2 control outputNone, RO1-RO24Second command output for switch open commands for devices with two opening coils
Select-Close control outputNone, RO1-RO24Pre-select control output for switch close commands
Select-Open control outputNone, RO1-RO24Pre-select control output for switch open commands
Select-Open-2 control outputNone, RO1-RO24Second pre-select control output for switch open commands for devices with two opening coils
Close Duration Control Logic EquationNone, SP1-SP64Setpoint control equation controlling the close pulse duration for adaptive pulses
Open Duration Control Logic EquationNone, SP1-SP64Setpoint control equation controlling the open pulse duration for adaptive pulses
Close Command Duration, ms100-60000 ms2000Default close command pulse duration
Open Command Duration, ms100-60000 ms2000Default open command pulse duration
Close Start Moving Timeout, ms0-60000 ms5000Switch immobility timeout for close command execution supervision. 0=not supervised
Open Start Moving Timeout, ms0-60000 ms5000Switch immobility timeout for open command execution supervision. 0=not supervised
Close Command Termination Timeout, ms1-120000 ms10000Total close operation supervision timeout
Open Command Termination Timeout, ms1-120000 ms10000Total open operation supervision timeout

4.2 Configuring Control Ports

This setup allows configuring individual control permissions for user ports. To restrict control operations for users:

  1. Select Communication Setup from the Meter Setup menu and then click on the Direct Control Ports tab.

PAS screen: PM180 - Communication Setup, Direct Control Ports tab (Blocking Control Ports list). Drawing not reproduced on this page. See page 18 of the PDF.

  1. Configure control permissions for user ports. The following table lists available options:
Direct control status options
Direct Control StatusDescription
EnabledControl commands from the port are allowed
DisabledControl commands from the port are denied
BlockedControl commands from the port are denied until the port is unblocked via setpoint control logic

The following rules are applied:

  1. Send your setup to the device.

Downloads and related

Questions about this document? Use the contact form.