Overview
SATEC VRM Module is designed for connecting SATEC meters to DC voltage systems above meter rating (800V DC for PM130 PLUS and 800V DC for PRO EM235/PM335) ranging up to 1500V DC.
- Dimensions: 127 x 75 x 52 mm
- Weight: 80 grams
- Installation: DIN-Rail only
Figure 1: VRM Module dimensions. Drawing not reproduced on this page. See page 2 of the PDF.
Figure 2: VRM Module. Drawing not reproduced on this page. See page 2 of the PDF.
Voltage Ratio Module Characteristics
- Accuracy = 0.1%
- 3 Independent voltage inputs
- Terminals: Wire size: 12 AWG (up to 3.5 mm2)
- DIN-rail installation
Electrical Installation
It is recommended that the distance between the SATEC VRM and SATEC meter should not exceed 2 meters, using cabling featuring minimum 600V insulation.
PAS screenshot: PRO - General Setup, Basic Setup tab, PT Ratio set to 3.5. Drawing not reproduced on this page. See page 3 of the PDF.
When using SATEC VRM, the correct ratio coefficient must be set with PAS software software (“Basic Setup” tab):
- Using the PRO Series meters, enter “ratio” = 3.5
- Using the PM130 PLUS, enter “ratio” = 11 Ratio coefficient = 11