RGM180 · QUICK START GUIDE

RGM180 Display Series quick start guide

Quick Start Guide RGM180 Display Series

Transcribed from the SATEC document RGM180 Display Series Quick Start Guide, BG0509 REV.A2, April 2012 (PDF, 24 pages, 1492 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the contact form.

LIMITED WARRANTY

The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts from date of dispatch from the distributor. In all cases, this warranty is valid for 36 months from the date of production. This warranty is on a return to factory basis.

The manufacturer does not accept liability for any damage caused by instrument malfunction. The manufacturer accepts no responsibility for the suitability of the instrument to the application for which it was purchased.

Failure to install, set up or operate the instrument according to the instructions herein will void the warranty.

Only a duly authorized representative of the manufacturer may open your instrument. The unit should only be opened in a fully anti-static environment. Failure to do so may damage the electronic components and will void the warranty.

The greatest care has been taken to manufacture and calibrate your instrument. However, these instructions do not cover all possible contingencies that may arise during installation, operation or maintenance, and all details and variations of this equipment are not covered by these instructions.

WARNING

WarningRead the instructions in this manual before performing installation, and take note of the following precautions:
WarningEnsure that all incoming AC power and other power sources are turned OFF before performing any work on the instrument. Failure to do so may result in serious or even fatal injury and/or equipment damage.
WarningBefore connecting the instrument to the power source, check the labels on the back of the instrument to ensure that your instrument is equipped with the appropriate power supply voltage, input voltages and currents.
WarningUnder no circumstances should the instrument be connected to a power source if it is damaged.
WarningTo prevent potential fire or shock hazard, do not expose the instrument to rain or moisture.
WarningThe secondary of an external current transformer must never be allowed to be open circuit when the primary is energized. An open circuit can cause high voltages, possibly resulting in equipment damage, fire and even serious or fatal injury. Ensure that the current transformer wiring is secured using an external strain relief to reduce mechanical strain on the screw terminals, if necessary.
WarningOnly qualified personnel familiar with the instrument and its associated electrical equipment must perform setup procedures.
WarningDo not open the instrument under any circumstances when it is connected to a power source.
WarningDo not use the instrument for primary protection functions where failure of the device can cause fire, injury or death. The instrument can only be used for secondary protection if needed.
WarningRead this manual thoroughly before connecting the device to the current carrying circuits.
WarningDuring operation of the device, hazardous voltages are present on input terminals. Failure to observe precautions can result in serious or even fatal injury or damage to equipment.

All trademarks are property of their respective owners.

April 2012

Copyright 2003-2007 © SATEC Ltd.

General

The RGM180 series provides a user-friendly interface to monitor and configure SATEC devices.

The RGM180 series includes two models:

Installation: 1. Interface Description

Front and rear views of the RGM180 with numbered callouts 1 to 6. Drawing not reproduced on this page. See page 3 of the PDF.

  1. LED: Red (Wh)/Green (Ethernet Link).
  2. IR Communication port (for PM180 only)
  3. USB Communication port
  4. RS485 Communication port and PM17x/PM180 display connector
  5. Ethernet Communication port (RGM180-G3 only)
  6. Display & Touchscreen.
Note: this document prepared for the following devices: RGM180-G1 & RGM180-G3.

2. Connection Configurations: 2.1 PM17x / RPM17x

Figure 1: PM17x connection. Drawing not reproduced on this page. See page 4 of the PDF.

Figure 2: RPM17x Connection. Drawing not reproduced on this page. See page 4 of the PDF.

2.2 ezPAC Connection

Figure 3: ezPac Connection. Drawing not reproduced on this page. See page 5 of the PDF.

2.3 EM720 Connection

Figure 4: EM720 Connection. Drawing not reproduced on this page. See page 5 of the PDF.

2.4 PM130 PLUS Connection

Figure 5: PM130 Plus Connection. Drawing not reproduced on this page. See page 6 of the PDF.

2.5 EM133 Connection

Figure 6: EM133 Connection. Drawing not reproduced on this page. See page 6 of the PDF.

2.6 Ethernet Connection

2.6.1. Regular Ethernet connection

Figure 7:Regular Ethernet Connection. Drawing not reproduced on this page. See page 7 of the PDF.

2.6.2. PoE Ethernet Connection

Figure 8: PoE Ethernet Connection. Drawing not reproduced on this page. See page 7 of the PDF.

2.7 Mechanical Installation

Figure 9: Instrument Dimensions. Drawing not reproduced on this page. See page 8 of the PDF.

2.8 RGM180 Panel Mount Installation

Figure 10: Panel Mount Installation. Drawing not reproduced on this page. See page 9 of the PDF.

Operation: 1. Connection

Connecting to a Meter

The RGM runs a self-test prior to connection.

The screen will display “Connecting….;” when connected, Voltage measurement data will be displayed.

Screen image: Voltage Line to Line screen. Drawing not reproduced on this page. See page 10 of the PDF.

The screen is touch activated.

To display the Main Menu, press MENU 3 times.

The Main Menu allows you to:

Screen image: Main Menu. Drawing not reproduced on this page. See page 10 of the PDF.

Connecting to the RGM

The device allows configuration through the USB or Ethernet at Modbus address 99.

2. Display Setup

Press on Display Setup from the Main Menu. The Display Setup menu will appear.

Screen image: RGM Setup Menu. Drawing not reproduced on this page. See page 10 of the PDF.

Display Definitions

Press Display to set Brightness, Standby Mode and Language:

After setting these options, press Save and then close the window by pressing on the X in the top right corner.

Screen image: Display Setup window. Drawing not reproduced on this page. See page 11 of the PDF.

Screen Calibration

Press Calibration to calibrate the display touch screen sensor:

Follow the instructions on the screen to calibrate the display. A message will appear indicating if input values are out of range.

Screen image: touch screen calibration. Drawing not reproduced on this page. See page 11 of the PDF.

Press OK to return to Display Setup menu.

Network Setup

Press Network to define the network connection:

Press on the IP Address number to define the address; input the correct IP address (or press Clear to input a new address) and press OK to save or Cancel to restore the previous address.

Define or change the Subnet Mask number and Default Gateway in the same manner.

DHCP – Press the setting (Off or On) to change, then press OK to save.

Press X to close the window and return to the Display setup menu.

Screen image: Network Setup window. Drawing not reproduced on this page. See page 11 of the PDF.

Serial Port Settings

Press Serial to define the serial port settings:

Set the Baud rate, Data format, Port direction and response time in the same manner as in the Network Setup.

Press X to close the window and return to the Display setup menu.

Screen image: Serial Port window. Drawing not reproduced on this page. See page 12 of the PDF.

Factory Settings

Press Factory to view the factory-set definition of the RGM.

WarningIt is not recommended to change these settings.

Screen image: Factory window. Drawing not reproduced on this page. See page 12 of the PDF.

Press MENU to return to the Main Menu.

Screen image: Main Menu. Drawing not reproduced on this page. See page 12 of the PDF.

3. Instrument Setup

The RGM connects to up to 32 devices. Each device has its own instrument setup definition.

Press Instrument Setup to define Wiring Setup and Demand Setup, to adjust the Time, to Reset measurement parameters and to define Communication parameters.

Screen image: Instrument Setups menu. Drawing not reproduced on this page. See page 13 of the PDF.

Wiring Setup

Press Wiring Setup to define the Wiring Mode, CT primary and Nominal Frequency.

Press on the value of the desired parameter and enter the correct value. Press Receive to complete the definition, then close the window using the X in the upper right corner.

Screen images: Wiring Setup window and Wiring Mode selection. Drawing not reproduced on this page. See page 13 of the PDF.

Demand Setup

Power demand parameters can be defined on this screen, used in the same fashion as the Wiring Setup.

Time Adjustment

Use this screen to set the date and time. Press OK when completed. Press OK on the ‘Operation successfully completed’ message.

Reset Setup

Use this screen to reset parameters or clear logs. You will be asked after each operation if you are sure you want to perform the reset.

Communications

Communications parameters can be set in the same fashion as the Wiring and Demand Setups.

Press MENU to return to the Main Menu.

Screen image: Main Menu. Drawing not reproduced on this page. See page 14 of the PDF.

4. Data Display

From the Main Menu, press RT Measure to display the Select Data Menu.

The Select Data Menu allows you to choose from the four data groups: Real Time Measurements, Harmonics, Energy, and the Logs (Event Log).

To display Real Time Measurements, press on Real Time.

Screen image: Select Data menu. Drawing not reproduced on this page. See page 15 of the PDF.

4.1 Real Time Measurements

Press on the desired data item to display the data. Continue to press NEXT to progress through the data in this group:

Screen image: Real Time Data menu. Drawing not reproduced on this page. See page 15 of the PDF.

This screen can be reached at any point from any of the real time measurement screens by pressing on MENU from those screens.

Note: From this screen, press MENU to display the Select Data menu; press NEXT to bring up the next data group: Harmonic Data (see 4.2).

Press Volts L-L RMS to display the screen at right.

Press on L-N at the bottom of the screen to view Line to Neutral voltage; press on Sec to display Line to Line Secondary voltage.

Press NEXT to proceed to the next data item.

Screen image: Voltage Line to Line screen. Drawing not reproduced on this page. See page 15 of the PDF.

To maneuver between the data items displayed, press PREV or NEXT.

At the display of voltage maximum demand, press NEXT to display Current data.

Current (Amps)

The next four screens display:

Screen image: Amps screen. Drawing not reproduced on this page. See page 16 of the PDF.

Press NEXT to display Power data.

Power

The next five screens display:

Screen image: Power Total screen. Drawing not reproduced on this page. See page 16 of the PDF.

Press NEXT to display Auxiliary power data.

Auxiliary Power

The next three screens display:

Screen image: Auxiliary screen. Drawing not reproduced on this page. See page 16 of the PDF.

Press NEXT to display the phasor graph.

Phasor

The phasor is a graphical display of phase angles for voltage and current per phase.

The phases are color coded for easy reading of the graph.

Screen image: phasor graph. Drawing not reproduced on this page. See page 17 of the PDF.

Press NEXT to display the Waveform graph.

Waveform

The waveform is a real time graphical display.

Use the sliding bar on the right to view different waveforms.

The icons at the top are (from left to right):

Screen image: RT Wave Form screen. Drawing not reproduced on this page. See page 17 of the PDF.

Press MENU to close this screen. “Closing” will appear, after which you will be back to the Real Time Measurement Data Menu (see 4.1).

From the Real Time Measurement Data screen, press MENU to display the Select Data menu; press NEXT to display the Harmonic Data Menu (see 4.2).

4.2 Harmonic Data Menu

This screen presents the Harmonic data group. This includes the following data:

Press on the desired data item to view that data.

Continue to press NEXT to progress through the data in this group.

Screen image: Harmonic Data menu. Drawing not reproduced on this page. See page 18 of the PDF.

Note: From this screen, press MENU to display the Select Data Menu menu; press NEXT to display the next data group: Energy Data (see 4.3). Press PREV to return to the Real Time Measurement Data Menu (see 4.1).

Individual Harmonics

These screens work differently from the Real Time Measurement Data screens – you will always need to press MENU to return to the screen shown above and then select the next item you want to view.

Each harmonic spectrum can be viewed in graph or tabular form, as shown below. The table expresses the harmonic distortion as a percentage. To view the full table, use the scroll bar on the right.

Press on V1 to display the Voltage Harmonic Spectrum (displayed per phase) graph:

Screen image: V1 Spectrum graph. Drawing not reproduced on this page. See page 18 of the PDF.

Press on the table icon at the bottom of the screen to view the Voltage Harmonic Spectrum table.

Screen image: V1 Spectrum table. Drawing not reproduced on this page. See page 18 of the PDF.

View Current Harmonic Spectrum (per phase) in the same way, by pressing on I1 on the Harmonic Data screen above.

Total Harmonic Distortion

These screens work the same as the Real Time Measurement Data screens – press NEXT to proceed to the next data item, or PREV to return to the previous data screen.

Voltage THD – per phase

Current THD – per phase

Screen image: Voltage THD screen. Drawing not reproduced on this page. See page 19 of the PDF.

Press MENU to return to the Harmonic Data group screen. Press NEXT to proceed to the Energy Data Menu (see 4.3).

4.3 Energy Data

This screen presents the Energy data group, consisting of the following data:

Screen image: Energy Data menu. Drawing not reproduced on this page. See page 19 of the PDF.

Press on the desired data item to view that data.

Screen image: Energy Import screen. Drawing not reproduced on this page. See page 19 of the PDF.

Press NEXT or PREV to see next or preceding data item. Press MENU to return to Energy Data Menu.

Press MENU to return to Select Data Menu; Press Logs to view Log Selection screen (only Event Log is available).

4.4 Log Selection

Press Event Log to define and view the log.

Screen image: Log Selection screen. Drawing not reproduced on this page. See page 20 of the PDF.

When you start the time, the Log will download to the display.

To order the data, first define the start time. Press on the gray area to insert the time definition. Press OK. Press OK again to commence log downloading.

Screen image: Event Log, Order the Data window. Drawing not reproduced on this page. See page 20 of the PDF.

The log will appear. Use the scroll bars at bottom and right to view the full log. To re-start the log, press READ to again define the start time.

Screen image: Event Log table. Drawing not reproduced on this page. See page 20 of the PDF.

Press MENU to return to Log Selection Menu.

Press MENU again to return to Select Data Menu.

Reminder: In the data screens, pressing PREV or NEXT will move you to the previous/next data item within the data group you are currently displaying. You can move from one data group to another. For example, if you are on the Harmonic data display, press PREV to move to Real Time data display; or NEXT to move to Energy data display. To display the Logs, you must return to the Select Data Menu.

5. Meter Selection

Labels

The label name assigned to a device will appear in the lower left of the screen. The user may change these label names (the actual device being displayed will appear at the top of the screen in parentheses).

Meter Selection

To change the connection to a different device, press on the label name in the lower left of the screen (in this screen, it is PM172).

Screen image: Voltage Line to Line screen. Drawing not reproduced on this page. See page 21 of the PDF.

The Meter Selection screen will appear.

Press on the address of the desired meter. Press OK on the ‘Connection established’ box. Data display will begin.

Screen image: Meter Selection screen. Drawing not reproduced on this page. See page 21 of the PDF.

To change the label name or address of a device, press on Setup. The Connection Manager screen will appear. Press on the label name or address you wish to change.

Note: In most cases, excluding stand-alone or ethernet connections, there is no need to change the address or IP. Connecting to an external device requires the definition of MODBUS and/or IP addresses.

Screen image: Connection Manager screen. Drawing not reproduced on this page. See page 21 of the PDF.

To perform display setup from this menu, press RGM Setup. See Section 2 for Display Setup instructions.

6. Troubleshooting

Technical Specification

Communication ports
COM1IR Communication portPM180 device Only
OptionalOptical Communication port
OptionalMax. Baud rate19.200 kb/s
OptionalProtocolsModbus or DNP3.0
OptionalIsolation2500 VAC @ 1 mn
COM2Serial Communication portDevice COM port
basicRS-485 Max. Baud rate115.2 to 480 kb/s
basicIsolation4000 VAC @ 1 mn
basicRS-485 Maximum length cable1000m
basicProtocolsModbus RTU
basicConnectionDB-15
ETHERNETMultiple device Communication portRGM180-G3 only
10/100Base-T BasicBuilt-in network communication port with PoE ability
10/100Base-T BasicWired LAN communication port with auto-negotiationIEEE 802.3
10/100Base-T BasicEthernet port Baud rate10/100 Mb/s
10/100Base-T BasicProtocolsModbus/TCP
10/100Base-T BasicETH port Isolation1.5 KVAC @ 1mn
10/100Base-T BasicETH connectorStandard RJ-45
USBBuilt-in USB Communication portDISPLAY Panel
USBBasic - Device (default): USB communication portFull speed Device
USBBasic - Device (default): USB port Baud rate12 Mb/s
USBBasic - Device (default): ProtocolsModbus RTU/ASCII and DNP3.0
USBUSB device port Isolation (Remote display)1500 KVAC @ 1mn
USBUSB device port Isolation (Local display)4000 KVAC @ 1mn
USBUSB connector DISPLAY PanelUSB type A, vertical mount, straight
DISPLAY: Panel Display (Touch-Panel LCD graphic display, 1 Wh pulse led, IR port and USB Device/Host connector Type A)
size5.7″
resolution320 x 240 dots
TypeTFT – color with Touch Panel
Outline dimensions131mm (W) x 102mm (H) x 14.5mm (D)
Active area115.2mm (W) x 86.4mm (H)
Operating temperature-20°C - +70 °C
Storage temperature-30°C - +80 °C
Non-volatile memory
For energy and tariff registers logging, EV-PQ-DATA-WV logBasic 256MB

Power supply

Power supply: Low DC power supply
12VDC – Device PS standardRated Input10.8 – 13.2V DC
12VDC – Device PS standardDielectric withstand insulation4000 VDC @ 1mn
12VDC – Device PS standardPower Consumption2W
24VDC - Device PS option (PM180 Aux. PS)Rated Input9.5 – 24V DC
24VDC - Device PS option (PM180 Aux. PS)Dielectric withstand insulation3000 VDC @ 1mn
24VDC - Device PS option (PM180 Aux. PS)Power Consumption2W
48VDC – PoE optionRated Input37 – 58V DC
48VDC – PoE optionDielectric withstand insulation1500 VDC @ 1mn
48VDC – PoE optionPower Consumption2W
All modelsDetachable Terminals for wires size3 x 2.5 up to 6 mm²
All modelsHeader pitch7.5 mm
All modelsPoE connectionRJ45
Temperature limit range
Operational temperature-30 °C to 70 °C
LCD Operational temperature-20 °C to 70 °C
Storage temperature-30 °C to 80 °C