Compact Multi-function Power Meter with Modular I/O and Open Protocols.
Transcribed from the SATEC Australia datasheet TBV1.0, 28 September 2026 (PDF, 9 pages, 1385 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.
Overview
The PM135 is a compact multi-function power meter designed for metering three-phase AC current circuits. With versatile I/O options, communication ports and open protocols, it is suited to integration in utility substation and industrial SCADA systems as well as commercial energy management.
A built-in RS-485 port, optional Ethernet, Profibus or RS-232/422/485 modules and up to 16 digital and analogue I/O points let one meter grow with the site. A backlit LCD with an LED load bar-graph, 25–400 Hz frequency measurement options and dual 4″ round or 92×92 mm square mounting make it a flexible retrofit or new-build choice.
PM135P — Power version offering voltage, current, power and frequency measurements.
PM135E — All PM135P features plus energy measurements, Time-of-Use tariffs and data logging.
PM135EH — All PM135E features plus harmonic analysis to the 40th order.
Main features
Accuracy: Class 0.5S per AS/IEC 62053-22 and ANSI C12.20
Open protocols: Modbus RTU, DNP3.0, IEC 60870-5-101/104
Digital and analogue I/O modules: up to 16 I/O
Dual mounting: 4″ round and 92×92 mm square cutouts
Broad frequency range: 25–400 Hz measurement options
LED bar-graph: load shown as a percentage of nominal current
Embedded logic controller: 16 setpoints with 1-cycle response
Software: free PAS configuration software and Expertpower cloud platform
Feature capabilities
Multi-functional 3-phase power meter
True RMS volts, amps, power, power factor, neutral current, angles and unbalance for voltage and current, frequency, symmetrical components and more
Ampere and volt demand meter
25, 50, 60 and 400 Hz measurements with 3 decimal digit values
128 samples per cycle
Harmonic analyser (PM135EH only)
Individual voltage and current harmonic spectrum and harmonic angles up to the 40th order
Voltage and current THD, TDD and K-Factor
Real-time waveform capture
Real-time “scope mode” waveform monitoring via PAS software
Programmable logic controller
Embedded programmable controller
16 control setpoints with programmable thresholds and delays
Relay output control
1-cycle response time
Billing / TOU energy meter (PM135E and PM135EH only)
Accuracy Class 0.5S per AS/IEC 62053-22 and Class 0.2 per IEC 61557-12
Four-quadrant active and reactive energy polyphase static meter
Three-phase total and per-phase energy measurements; active, reactive and apparent energy counters
Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 types of days, 8 tariff changes per day
Easily programmable tariff calendar schedule
Automatic daily energy and maximum demand profile log for total energy and tariff registers
Event and data recording (PM135E and PM135EH only)
Non-volatile memory for timestamped event and data recording: 48 days for 2 daily TOU records, half-hourly writing of 4 parameters and more than 100 events over the whole period
Event recorder logging internal diagnostic events and setup changes
Two data recorders with programmable periodic data logs, automatic daily energy log and maximum demand profile
Current input options
1A or 5A inputs from CT secondary
40mA input designed for SATEC HACS current sensors (100–3000A options)
RS5: dedicated input for 5A rated split-core HACS
Voltage inputs
Direct measurement: 0–690V AC
I/O options
4DIOR: 4 digital inputs and 2 relay outputs with 1-cycle update time; unlatched, latched, pulse and KYZ operation; energy pulses; choice of solid state or electromechanical relays
12DIOR: 12 digital inputs and 4 relay outputs (with optional Ethernet or additional RS-485 port)
4AO: four optically isolated analogue outputs with internal power supply; 0–20mA, 4–20mA, 0–1mA, ±1mA, 0–5mA or ±5mA output; 1-cycle update time
8DI: eight digital inputs with 1 ms scan time
Communication: on-board interface
Standard 2-wire RS-485
Communication: optional interfaces
Ethernet (10/100BaseT)
Multipurpose RS-232/422/485
PROFIBUS DP
Communication: client functions
Modbus/TCP client over Ethernet
TCP notification client for sending events or periodic reports to a remote server
Expertpower client (subscription)
Communication: protocols
Modbus RTU and Modbus/TCP
SATEC ASCII
DNP3.0 (Level 2)
IEC 60870-5-101 and IEC 60870-5-104 (optional)
Applications
Energy management
Utility substation and industrial SCADA
Tariff and TOU energy monitoring
Renewable energy systems
Display
3×2″ / 76×49 mm backlit LCD
Adjustable display brightness and update rate
Auto-scroll with adjustable page and auto-return to a default page
LED bar-graph showing load as a percentage of nominal (user-definable) load current
Software support and firmware
SATEC Power Analysis Software (PAS) for full configuration and data acquisition, free to download
Expertpower web-based energy management platform (subscription)
eXpertConnect™ App for convenient mobile access to energy data
Any third-party software supporting the open protocols
Firmware easily upgraded through the serial or Ethernet port
Meter security
Password protection of meter setups and accumulated data against unauthorised changes
Real-time clock
Internal battery-backed clock with typical retention of 36 months
Unique design
Pass-through CT connection
Built-in auxiliary terminal for loose CT wires
Dual panel mounting: 92×92 mm square or 4″ round cutout
Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.
Specifications
Voltage inputs
Installation
Category III
Nominal voltage (L-N/L-L)
100/400V AC; 230/400V AC; 400/690V AC
Operating range (L-N/L-L)
Nominal voltage +25% tolerance
Burden for 120V
< 0.04 VA
Over-voltage withstand
1000V AC continuous, 2000V AC for 1 second
Input impedance
1 MΩ
Wire size
Up to 12 AWG (up to 3.5 mm²)
Current inputs (via CT)
Wire size
12 AWG (up to 3.5 mm²)
Galvanic isolation
2,500V
Current inputs: 5A secondary
Operating range
Continuous 10A RMS
Burden
< 0.2 VA @ In = 5A (12 AWG wire, 1 m long)
Overload withstand
15A RMS continuous, 300A RMS for 1 second (12 AWG wire)
Current inputs: 1A secondary
Operating range
Continuous 2A RMS
Burden
< 0.02 VA @ In = 1A (12 AWG wire, 1 m long)
Overload withstand
3A RMS continuous, 80A RMS for 1 second (12 AWG wire)
Current inputs: HACS / RS5 remote sensors
Depends on sensor rating. See the HACS datasheet.
Sampling
Sampling rate
Up to 256 samples per cycle
Waveforms
128 samples per cycle (via communications)
Power supply: 120/230V AC-DC option
Rated input
85–265V AC @ 50/60 Hz; 88–290V DC
Burden
9 VA
Isolation
1500V DC
Input to ground
2500V AC
Power supply: 12V DC option
Rated input
9.5–18V DC
Burden
4 VA
Isolation
1500V DC
Power supply: 24/48V DC option
Rated input
18.5–58V DC
Burden
4 VA
Isolation
1500V DC
Power supply
Wire size
Up to 12 AWG (up to 3.5 mm²)
Real-time clock
Type
Battery-backed clock
Accuracy
Typical error 7 seconds per month @ 25°C (±2.5 ppm)