PM135 · DATASHEET

PM135 power meter datasheet

Compact Multi-function Power Meter with Modular I/O and Open Protocols.

Transcribed from the SATEC Australia datasheet TBV1.0, 28 September 2026 (PDF, 9 pages, 1385 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The PM135 is a compact multi-function power meter designed for metering three-phase AC current circuits. With versatile I/O options, communication ports and open protocols, it is suited to integration in utility substation and industrial SCADA systems as well as commercial energy management.

A built-in RS-485 port, optional Ethernet, Profibus or RS-232/422/485 modules and up to 16 digital and analogue I/O points let one meter grow with the site. A backlit LCD with an LED load bar-graph, 25–400 Hz frequency measurement options and dual 4″ round or 92×92 mm square mounting make it a flexible retrofit or new-build choice.

PM135P — Power version offering voltage, current, power and frequency measurements.

PM135E — All PM135P features plus energy measurements, Time-of-Use tariffs and data logging.

PM135EH — All PM135E features plus harmonic analysis to the 40th order.

Main features

Feature capabilities

Multi-functional 3-phase power meter

  • True RMS volts, amps, power, power factor, neutral current, angles and unbalance for voltage and current, frequency, symmetrical components and more
  • Ampere and volt demand meter
  • 25, 50, 60 and 400 Hz measurements with 3 decimal digit values
  • 128 samples per cycle

Harmonic analyser (PM135EH only)

  • Individual voltage and current harmonic spectrum and harmonic angles up to the 40th order
  • Voltage and current THD, TDD and K-Factor

Real-time waveform capture

  • Real-time “scope mode” waveform monitoring via PAS software

Programmable logic controller

  • Embedded programmable controller
  • 16 control setpoints with programmable thresholds and delays
  • Relay output control
  • 1-cycle response time

Billing / TOU energy meter (PM135E and PM135EH only)

  • Accuracy Class 0.5S per AS/IEC 62053-22 and Class 0.2 per IEC 61557-12
  • Four-quadrant active and reactive energy polyphase static meter
  • Three-phase total and per-phase energy measurements; active, reactive and apparent energy counters
  • Time-of-Use: 4 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 types of days, 8 tariff changes per day
  • Easily programmable tariff calendar schedule
  • Automatic daily energy and maximum demand profile log for total energy and tariff registers

Event and data recording (PM135E and PM135EH only)

  • Non-volatile memory for timestamped event and data recording: 48 days for 2 daily TOU records, half-hourly writing of 4 parameters and more than 100 events over the whole period
  • Event recorder logging internal diagnostic events and setup changes
  • Two data recorders with programmable periodic data logs, automatic daily energy log and maximum demand profile

Current input options

  • 1A or 5A inputs from CT secondary
  • 40mA input designed for SATEC HACS current sensors (100–3000A options)
  • RS5: dedicated input for 5A rated split-core HACS

Voltage inputs

  • Direct measurement: 0–690V AC

I/O options

  • 4DIOR: 4 digital inputs and 2 relay outputs with 1-cycle update time; unlatched, latched, pulse and KYZ operation; energy pulses; choice of solid state or electromechanical relays
  • 12DIOR: 12 digital inputs and 4 relay outputs (with optional Ethernet or additional RS-485 port)
  • 4AO: four optically isolated analogue outputs with internal power supply; 0–20mA, 4–20mA, 0–1mA, ±1mA, 0–5mA or ±5mA output; 1-cycle update time
  • 8DI: eight digital inputs with 1 ms scan time

Communication: on-board interface

  • Standard 2-wire RS-485

Communication: optional interfaces

  • Ethernet (10/100BaseT)
  • Multipurpose RS-232/422/485
  • PROFIBUS DP

Communication: client functions

  • Modbus/TCP client over Ethernet
  • TCP notification client for sending events or periodic reports to a remote server
  • Expertpower client (subscription)

Communication: protocols

  • Modbus RTU and Modbus/TCP
  • SATEC ASCII
  • DNP3.0 (Level 2)
  • IEC 60870-5-101 and IEC 60870-5-104 (optional)

Applications

  • Energy management
  • Utility substation and industrial SCADA
  • Tariff and TOU energy monitoring
  • Renewable energy systems

Display

  • 3×2″ / 76×49 mm backlit LCD
  • Adjustable display brightness and update rate
  • Auto-scroll with adjustable page and auto-return to a default page
  • LED bar-graph showing load as a percentage of nominal (user-definable) load current

Software support and firmware

  • SATEC Power Analysis Software (PAS) for full configuration and data acquisition, free to download
  • Expertpower web-based energy management platform (subscription)
  • eXpertConnect™ App for convenient mobile access to energy data
  • Any third-party software supporting the open protocols
  • Firmware easily upgraded through the serial or Ethernet port

Meter security

  • Password protection of meter setups and accumulated data against unauthorised changes

Real-time clock

  • Internal battery-backed clock with typical retention of 36 months

Unique design

  • Pass-through CT connection
  • Built-in auxiliary terminal for loose CT wires
  • Dual panel mounting: 92×92 mm square or 4″ round cutout

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Voltage inputs
InstallationCategory III
Nominal voltage (L-N/L-L)100/400V AC; 230/400V AC; 400/690V AC
Operating range (L-N/L-L)Nominal voltage +25% tolerance
Burden for 120V< 0.04 VA
Over-voltage withstand1000V AC continuous, 2000V AC for 1 second
Input impedance1 MΩ
Wire sizeUp to 12 AWG (up to 3.5 mm²)
Current inputs (via CT)
Wire size12 AWG (up to 3.5 mm²)
Galvanic isolation2,500V
Current inputs: 5A secondary
Operating rangeContinuous 10A RMS
Burden< 0.2 VA @ In = 5A (12 AWG wire, 1 m long)
Overload withstand15A RMS continuous, 300A RMS for 1 second (12 AWG wire)
Current inputs: 1A secondary
Operating rangeContinuous 2A RMS
Burden< 0.02 VA @ In = 1A (12 AWG wire, 1 m long)
Overload withstand3A RMS continuous, 80A RMS for 1 second (12 AWG wire)
Current inputs: HACS / RS5 remote sensors
Depends on sensor rating. See the HACS datasheet.
Sampling
Sampling rateUp to 256 samples per cycle
Waveforms128 samples per cycle (via communications)
Power supply: 120/230V AC-DC option
Rated input85–265V AC @ 50/60 Hz; 88–290V DC
Burden9 VA
Isolation1500V DC
Input to ground2500V AC
Power supply: 12V DC option
Rated input9.5–18V DC
Burden4 VA
Isolation1500V DC
Power supply: 24/48V DC option
Rated input18.5–58V DC
Burden4 VA
Isolation1500V DC
Power supply
Wire sizeUp to 12 AWG (up to 3.5 mm²)
Real-time clock
TypeBattery-backed clock
AccuracyTypical error 7 seconds per month @ 25°C (±2.5 ppm)
Retention timeTypically 36 months
Display
Screen3×2″ / 76×49 mm backlit LCD
Load bar-graph3-colour LED (40–110%)
Keypad6 push buttons
Electromechanical relay (optional)
ContactDry contact, 1 contact (SPST Form A)
Rating5A/250V AC; 5A/30V DC
Isolation, contacts to coil3000V AC @ 1 min
Isolation, open contacts750V AC
Operate time10 ms max
Release time5 ms max
Update time1 cycle
Wire size14 AWG (up to 1.5 mm²)
Solid state relay (optional)
ContactDry contact, 1 contact (SPST Form A)
Rating0.15A/250V AC/DC
Galvanic isolation3750V AC @ 1 min
Operate time1 ms max
Release time0.25 ms max
Update time1 cycle
Connector typeRemovable, 4 pins
Wire size14 AWG (up to 1.5 mm²)
Analogue outputs (optional)
Ranges (upon order)±1 mA, max. load 5 kΩ (100% overload); 0–20 mA, max. load 510 Ω; 4–20 mA, max. load 510 Ω; 0–1 mA, max. load 5 kΩ (100% overload)
Isolation2500V AC @ 1 min
Power supplyInternal
Accuracy0.5% FS
Update time1 cycle
Connector typeRemovable, 5 pins
Wire size14 AWG (up to 1.5 mm²)
Digital inputs (optional)
TypeDry contacts internally wetted @ 24V DC, or wet contact @ 250V DC (12DI/4DO only)
SensitivityOpen @ input resistance > 100 kΩ; closed @ input resistance < 100 Ω
Galvanic isolation3750V AC @ 1 min
Internal power supply24V DC (4DI/2DO or 12DI/4DO)
External power supply250V DC (12DI/4DO only)
Scan time1 ms
Connector typeRemovable, 5 pins
Wire size14 AWG (up to 1.5 mm²)
COM1: RS-485 (built in)
TypeRS-485 optically isolated port
Isolation3000V AC @ 1 min
Baud rateUp to 115.2 kbps
Supported protocolsModbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101
Connector typeRemovable, 3 pins
Wire sizeUp to 14 AWG (up to 1.5 mm²)
COM2: Ethernet (optional module)
TypeTransformer-isolated 10/100BaseT Ethernet port
Supported protocolsModbus/TCP (port 502), IEC 60870-5-104, DNP3/TCP (port 20000)
Simultaneous connections4 (2 Modbus/TCP + 2 DNP3/TCP)
Connector typeRJ45 modular
Isolation1,500V DC @ 1 min

Independent module or add-on to the 12DIOR module

Environmental conditions
Operating range, unit stand-alone−30°C to 70°C (−22°F to 158°F)
Operating range, with add-on modules−30°C to 60°C (−22°F to 140°F)
Storage temperature−40°C to 85°C (−40°F to 185°F)
Humidity0 to 95% non-condensing
COM2: PROFIBUS DP, IEC 61158 (optional)
TypeRS-485 optically isolated Profibus interface
Connector typeRemovable, 5 pins
Baud rate9600 bit/s to 12 Mbit/s (auto detection)
Data32 bytes input, 32 bytes output
Supported protocolsPROFIBUS DP
COM2: RS-232/422/485 (optional)
TypeRS-232 or RS-422/485 optically isolated port
Isolation3000V AC @ 1 min
Baud rateUp to 115.2 kbps
Supported protocolsModbus RTU, DNP3, SATEC ASCII, IEC 60870-5-101
Connector typeRemovable 5 pins (RS-422/485); DB9 (RS-232)
Wire sizeUp to 14 AWG (up to 1.5 mm²)
Construction
Weight0.70 kg (1.54 lb)
Dimensions (H×W×D)114×114×109 mm (4.5×4.5×4.3″)
Panel cutout92×92 mm square or 4″ round
Construction: materials
Case enclosurePC/ABS plastic blend
Front panelPC plastic
PCBFR4 (UL94-V0)
TerminalsPBT (UL94-V0)
Plug-in connectorsPolyamide PA6.6 (UL94-V0)
LabelsPolyester film (UL94-V0)
PackagingCarton and Stratocell® (polyethylene foam) brackets

Standards compliance

Accuracy

  • Complies with AS/IEC 62053-22, Class 0.5S
  • Meets ANSI C12.20-1998, Class 10 0.5%

Accuracy: complies with IEC 61557-12 (PMD)

  • Total apparent power: 0.2%
  • Total active energy: 0.5/0.2%
  • Total reactive energy: 0.5%
  • Frequency: 0.05%
  • Current: 0.2%
  • Neutral current: 0.2%
  • Voltage: 0.2%
  • Power factor: 0.2%
  • THDV, THDI: 1%

Electromagnetic immunity: complies with IEC 61000-6-2

  • IEC 61000-4-2 level 3: Electrostatic Discharge
  • IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
  • IEC 61000-4-4 level 3: Electric Fast Transient
  • IEC 61000-4-5 level 3: Surge
  • IEC 61000-4-6 level 3: Conducted Radio Frequency
  • IEC 61000-4-8: Power Frequency Magnetic Field

Electromagnetic immunity

  • Meets ANSI/IEEE C37.90.1: Fast Transient SWC

Electromagnetic emission

  • Complies with IEC 61000-6-4: Radiated/Conducted Class A
  • Complies with IEC CISPR 22: Radiated/Conducted Class A

Safety

  • Meets IEC 61010-1:2006

AC and impulse insulation

  • Complies with IEC 62052-11: 2500V AC for 1 minute
  • 6 kV/500 Ω @ 1.2/50 µs impulse

Ordering information

MODEL – CURRENT – CAL. FREQ. – RESOLUTION – POWER – PROTOCOL – MOUNTING

Models
Power versionPM135P
Energy versionPM135E
Energy and harmonic versionPM135EH
Current inputs
5 Ampere5
1 Ampere1
5A split-core remote high accuracy current sensor (HACS), 50/60 Hz onlyRS5
High Accuracy Current Sensors (HACS), 50/60 Hz only; requires ordering of 3 HACSHACS
Calibration at frequency
25 Hz*25HZ
50 Hz50HZ
60 Hz60HZ
400 Hz*400HZ
Display resolution
Low resolution 1A, 1V–
High resolution 0.01A, 0.1VH
Power supply
85–265V AC and 85–290V DCACDC
9.5–18V DC1DC
18.5–58V DC (24V DC, 48V DC)23DC
Communication protocol
Modbus and DNP3.0–
Modbus and IEC 60870-5-101/104**870
Mounting
Panel mount (standard)–
DIN rail mountingDIN

* Supported by 1A and 5A models only. ** IEC 60870-5-104 requires Ethernet.

Expansion modules

Maximum of 1 expansion module per instrument. Modules can be ordered separately.

Expansion module: analogue outputs
4 analogue outputs: ±1mAAO1
4 analogue outputs: 0–20mAAO2
4 analogue outputs: 0–1mAAO3
4 analogue outputs: 4–20mAAO4
4 analogue outputs: 0–5mAAO7
4 analogue outputs: ±5mAAO8
Expansion module: communication ports
Ethernet (TCP/IP)ETH
PROFIBUSPRO
RS-232/422/485RS232
Expansion module: digital I/O
4 digital inputs (dry contact) / 2 relay outputs 250V/5A ACDIOR
4 digital inputs (dry contact) / 2 SSR outputs 250V/0.1A ACDIOS
8 digital inputs (dry contact)8DI
12 digital inputs / 4 relay outputs 250V/5A AC12DIOR
12DIOR: digital input rating
Dry contactDRC
48V48V
125V125V
250V250V
12DIOR: communication port
None–
RS-485485
EthernetETH

12DIOR order string example: 12DIOR-DRC-ETH.