HACS · DATASHEET

HACS high accuracy current sensors datasheet

High accuracy current sensors for SATEC power meters and power quality analysers.

Transcribed from the SATEC Australia datasheet TBV1.1, 5 November 2026 (PDF, 12 pages, 1379 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The HACS range is SATEC’s family of high accuracy current sensors for use with SATEC’s EM132, EM133, PM130EH, PM135EH, BFM136, BFM II, PM180 and PRO Series family of metering and power quality devices, extending overall system accuracy to Class 1.0 or better. The range spans 17 models from 20A to 3,000A, in solid-core and split-core formats, so installers can match the sensor to the busbar or conductor without disturbing existing wiring.

A standard 2.5m lead is supplied with each unit and can be extended up to 200m from the meter using shielded 1.5mm² cable, making HACS well suited to retrofit installations where direct access to the load is restricted.

All 17 HACS models share the same technical specifications and installation requirements (see the following page) and differ only in current rating, window size, core type and accuracy, as summarised below.

Main features

Feature capabilities

Applications

  • Retrofit metering where direct load access is restricted
  • Revenue and sub-metering with SATEC EM132, EM133, PM130EH, PM135EH, BFM136 and BFM II
  • Power quality and energy monitoring with SATEC PM180 and the PRO Series family
  • Switchboard and busbar current sensing
  • Extending overall system accuracy to Class 1.0 or better

Installation recommendations

  • All HACS incorporate a built-in automatic shorting diode protection circuit for maximum safety; shorting CT links/bars are not required.
  • Future provision for testing circuits may require installation of shorting CT links/bars.*
  • Do not earth/ground the HACS output — doing so may cause damage to the HACS input meter.
  • All HACS are supplied with a 2.5m / 8.2ft cable.
  • Maximum cable length: can be wired up to 200m / 650ft from SATEC HACS input metering devices.
  • Recommended wire gauge: ≥1.5mm² diameter cable.
  • Use a shielded extension cable between the HACS and the SATEC meter, with the cable shield connected to the SATEC meter ground.
  • Locate HACS cable in a separate cable conduit, at least 1m (3ft) away from high-voltage circuits and/or other high-power magnetic fields.

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Shared specifications (all models)
Frequency50/60Hz
Lead insulation600V AC
Core insulation4,000V AC
Nominal current50% of maximum current
Lead length2.5m / 8.2ft (UL1015)
Operating temperature−40°C to +70°C (−40°F to 158°F)
Storage temperature−40°C to +85°C (−40°F to 185°F)
StandardIEC 60044-1
Burden0.2 VA
Thermal over current limit40×IMAX for 1 second
Short circuit over current80×IMAX for 10ms

The printed Material row is not shown (see the omissions list).

Standards compliance

Standard

  • IEC 60044-1

Ordering information

Model range
HX0140CS05S / RS5 — 20A, ∅16mm (∅0.62″), Split, 0.5%, 98.2g (0.22 lb)
EL0072CS1 — 100A, ∅12mm (∅0.47″), Solid, 0.1%, 156.4g (0.34 lb)
EL0115CS1L — 100A, ∅23mm (∅0.9″), Solid, 0.1%, 206.3g (0.45 lb)
HX0118CS1S — 100A, ∅16mm (∅0.63″), Split, 0.5%, 103.4g (0.23 lb)
HX0161CS1H — 100A, ∅13mm (∅0.5″), Split, 0.1/0.2%, 280g (0.6 lb)
EL0142CS2 — 200A, ∅23mm (∅0.9″), Solid, 0.1%, 206.3g (0.45 lb)
HX0145CS2S — 200A, 25×23mm (0.96×0.9″), Split, 0.5%, 160g (0.34 lb)
HX0156CS2SL — 200A, 43×33mm (1.69×1.3″), Split, 0.5%, 450g (1 lb)
HX0166CS250S — 250A, 24×25mm (0.94×0.98″), Split, 0.5%, 210g (0.46 lb)
EL0117CS4 — 400A, ∅26mm (∅1.02″), Solid, 0.1%, 214g (0.47 lb)
HX0157CS4S — 400A, 43×33mm (1.69×1.3″), Split, 0.5%, 450g (1 lb)
EL0153CS4L — 400A, ∅45mm (∅1.77″), Solid, 0.1%, 300g (0.66 lb)
EL0125CS8 — 800A, 100×32/62mm (4×1.28/2.44″), Solid, 0.1%, 525g (1.16 lb)
HX0158CS8S — 800A, 80×50mm (3.1×1.9″), Split, 0.5%, 900g (1.9 lb)
HX0153CS12S — 1,200A, 120×80mm (4.7×3.1″), Split, 0.5%, 1.25kg (2.75 lb)
HX0154CS20S — 2,000A, 160×80mm (6.3×3.15″), Split, 0.5%, 4.3kg (9.4 lb)
HX0155CS30S — 3,000A, 160×80mm (6.3×3.15″), Split, 0.5%, 4.3kg (9.4 lb)

Each HACS sensor is ordered directly by its catalog number, as listed in the Model Range table on page 2 — there is no order-code builder to assemble, since current rating, window size, core type and accuracy are all fixed per model. Model range table from page 2: catalogue number, then model — max current, window, core, accuracy, weight, in the order of the printed columns.

Downloads and related

Questions about this datasheet? Use the contact form.