EM133-XM · DATASHEET

EM133-XM energy meter datasheet

Smart multifunction energy meter: 5A CT and direct input.

Transcribed from the SATEC Australia datasheet TBV1.1, 6 October 2026 (PDF, 9 pages, 715 KB). If this page and the PDF differ, the PDF is right; tell us through the contact form.

Overview

The EM133-XM is SATEC's advanced expertmeter™ smart multifunction, DIN rail mounted, tariff (TOU) energy meter for commercial, industrial, solar and residential applications. It is designed for revenue billing, energy management and NABERS/Green Star reporting. The XM is the enhancement of SATEC's discontinued AR model.

The EM133-XM provides 2 built-in digital pulse inputs for direct connection to pulse-output water, hot water, gas and steam meters, with expansion modules available to add 4, 8 or 12 further pulse inputs. It measures three-phase and per-phase active, reactive and apparent energy across four quadrants, with time-of-use registers spanning 8 tariffs, 4 seasons and 4 day types, alongside an embedded programmable logic controller, harmonic analyser and real-time waveform capture.

Current input options

Main features

Feature capabilities

Billing / TOU energy meter

  • Energy accuracy Class 0.5S
  • Four-quadrant active and reactive energy
  • Import/export per phase as single-phase configuration
  • Three-phase total and per-phase energy measurement — active, reactive and apparent energy counters
  • Time-of-Use: 8 totalisation and tariff energy/demand registers × 8 tariffs, 4 seasons × 4 types of days, 8 tariff changes per day
  • One-time easy programmable tariff calendar schedule
  • Automatic daily energy and maximum demand profile log for total and tariff registers
  • Cost calculation (upon application)
  • CO2 (upon application)

Water and gas measurement

  • Direct connection to pulse output water and gas meters
  • Setting of multiplication factors and units
  • Display of consumption in real values
  • Up to 14 digital pulse inputs

Harmonic analyser

  • Voltage and current THD, TDD and K-Factor, up to 40th order harmonic
  • Voltage and current harmonic spectrum and angles

Real-time waveform capture (via PC with PAS free licensed software)

  • Real-time "scope mode" waveform monitoring capability
  • Simultaneous 6-channel 8-cycle waveform capture at a rate of 64 samples per cycle
  • Vector analysis

Programmable logical controller

  • Embedded programmable controller
  • 16 control set points; programmable thresholds and delays
  • Relay output control
  • 1-cycle response time

Event and interval data recording

  • Non-volatile memory with interval data logging for load surveys and energy usage
  • *Interval data logging @ 30 minutes = 1365 days
  • *Interval data logging @ 15 minutes = 682 days
  • *Interval data logging @ 5 minutes = 227 days
  • *Interval/data logging time period user-definable 1–60 minutes
  • *Interval/data logging for up to 16 parameters/channels, user-definable
  • Event recorder for logging internal diagnostic events and setup changes
  • Two data recorders; programmable data logs on a periodic basis; automatic daily energy and maximum demand profile log

Display

  • Easy to read 2 × 16 characters LCD display, adjustable update time
  • Signal strength display reading for modem and WiFi module
  • Auto-scroll option with adjustable page exposition time; auto-return to a default page

Real-time clock

  • With backup battery
  • Low battery indication

Meter security

  • 3 levels password security protecting meter setups and accumulated data from unauthorised changes

Upgradeable firmware

  • Easy upgrading of device firmware through serial, Ethernet, WiFi or modem communications

Inputs / outputs

  • Built-in 2 digital inputs and 1 form-A solid state digital output
  • Optional module 4 digital inputs and 2 digital outputs (solid state or electro-mechanical)
  • Optional module 8 digital inputs
  • Optional module 12 digital inputs and 4 digital outputs (plus Ethernet or RS-485)
  • Optional module 4 analogue outputs

Communications

  • Standard 2-wire RS-485 communication
  • Built-in IR communication port (IEC)

Dual communications (add-on module)

  • Optional multipurpose RS-232/422/485 port
  • Optional 10/100Base T port
  • Optional external 4G modem (on application)

Communication protocols

  • Modbus RTU
  • Modbus TCP/IP
  • Modbus assignable registers
  • MV-90 xi Translation Interface Module (TIM) for EM133-XM

Software support and firmware

  • Power Analysis Software (PAS) — free licensed software for configuration, data acquisition and forensic analysis
  • Expertpower — SATEC's internet-based energy management software
  • eXpertConnect™ App — mobile connection to the meter for configuration, readings and diagnostics

eXpertConnect™ cloud-based software as a service (SaaS)

  • KWH (energy) billing, water billing, gas billing
  • Energy management and power monitoring
  • Power quality forensic analysis
  • Data pushed to cloud service via Ethernet, WiFi or modem communications

Capability depends on the exact model or part number, fitted modules, firmware version, licences and configuration.

Specifications

Voltage inputs
Voltage connections3 phases, 1 neutral
Voltage ratingsDirect voltage connection: 220 to 400V (L-N); 380 to 690V (L-L); range 0–800VAC. Via PT (power transformer): 57.7 to 120V (L-N); 100 to 207V (L-L); range 0–250VAC
Starting voltage0.2% UN
Input impedance≥ 1MΩ
Overload withstand4000 VAC (L-G) for 1 min.
Impulse voltage12kV
Terminal blocks4 sealed, pitch 7–10mm, 2.5 to 4 mm²
Current inputs
Current connections4 galvanic isolated inputs
Current ratingsChoice of 3 options: ../5A CT connection; direct up to 100A; HACS input (refer HACS datasheet for inputs up to 3000A)
Starting current0.2% IN
Burden per phase<0.2 VA (../5A)
Overload (continuous)2×IN (1.2×IN for 100A model)
Over current50×IN (for 1 second)
Galvanic isolation4000 VAC (L-G) for 1 min.
Terminal blocks6 sealed, pitch 7–10mm, 4 to 16 mm²
Auxiliary power supply
Rated inputSelf powered
Insulation dielectric withstand4000 VAC for 1 min.
Terminal blocks2 sealed, pitch 7–10mm, 2.5 to 4 mm²
Built-in communication
Communication typeRS-485
Max. baud rate115.2 kb/s
Isolation4000 VAC (L-G) for 1 min.
Max. cable length1000 m
Terminal blocks3 sealed, pitch 7–10mm, 2.5 to 4 mm²
Infra-red communication
Baud rateTo be confirmed
ProtocolsModbus RTU
Add-on modules
Max. number of modules1
Available modulesRS485/RS-232; Ethernet; digital I/O; analogue output
Front panel
Display type2×16 characters transflective LCD with backlight
Character size3.2×1.85 mm
Viewing area46×11 mm
LEDsTotal 6 LEDs: 1 pulse calibration output; 3 voltage indication; 2 RX/TX activity
Keypad2 buttons
NameplateAccording to IEC 60688 and IEC 62052-11
Mechanical
EnclosureDIN rail mount, complies with EN50022
Dimensions [W×H×D]125 × 90 × 75mm
Enclosure materialReinforced polycarbonate
Temperature
Operational−25°C to 60°C
Storage−30°C to 85°C

Standards compliance

EMC immunity (per IEC 60688 and IEC 62052-11)

  • IEC 61000-4-2: electrostatic discharge — to be confirmed
  • IEC 61000-4-3: electromagnetic RF fields, 10V/m – 80MHz–1000MHz
  • IEC 61000-4-4: fast transients burst, 4KV on current and voltage circuits and 2KV for auxiliary circuits
  • IEC 61000-4-5: surge 4KV on current and voltage circuits and 1KV for auxiliary circuits
  • IEC 61000-4-6: conducted radio-frequency, 10V @ 0.15MHz–80MHz
  • IEC 61000-4-8: power frequency magnetic field

Emission (radiated / conducted)

  • EN55022: 2010 Class A (CISPR 22)
  • FCC p.15 Class A mandatory

Safety

  • UL/IEC 61010-1

Insulation

  • Impulse tested to SP-Method 1618, impulse voltage 12kV @ 1.2/50 µs
  • AS/IEC 62053-22: AC voltage tests related to ground, 4kV AC @ 1 min, for power and signal ports (above 40V)
  • 2.5KVAC r.m.s. @ 1 min, for other ports (below 40V)

Atmospheric environment

  • Operational ambient temperature range: −25°C to +60°C
  • Long-term damp heat withstand according to IEC 68-2-3, <95% (non-condensing), +40°C
  • Transport and storage temperature range: −30°C to +85°C
  • IEC 60068-2-6: vibration
  • Frequency range: 10Hz to 150Hz
  • Transition frequency: 60Hz
  • Constant movement amplitude 0.075mm, f<60Hz
  • Constant acceleration 9.8 m/s² (1g), f > 60Hz
  • Additional transport vibration and shocks — longitudinal acceleration 2.0g, vertical acceleration 1.2g, transversal acceleration 1.2g
  • Enclosure protection: IP50

Accuracy according to

  • AS/IEC 62053-22, class 0.5S — active energy
  • IEC 62053-21, class 0.5 — reactive energy
  • IEC 60688, class 0.5S — active energy
  • IEC 60688, class 1 — reactive energy

AER / AEMO / AEMC

  • NEM12/13 data, available via Expertpower or eXpertConnect™

Approvals in Australia

Ordering information

EM133-XM – CURR. – 50HZ – SE – CC

Current inputs (CURR.)
5 Ampere (CT operated)5
Direct current measurement up to 100A100
HACS (refer HACS datasheet) — CS1, CS1L, CS1S onlyHACS
Calibration at frequency
50Hz50HZ
400Hz400HZ
Power supply
Self energised / poweredSE
RS485/Modbus communications
RS485/Modbus (standard)—
Verification
NITP 14 verificationCC

Expansion module (max. 1 per instrument) is ordered separately — see Expansion modules below.

Expansion modules

Maximum 1 per instrument, ordered separately.

Analogue outputs
4 analogue output: ±1mAAO1
4 analogue output: 0–20mAAO2
4 analogue output: 0–1mAAO3
4 analogue output: 4–20mAAO4
4 analogue output: 0–3mAAO5
4 analogue output: ±3mAAO6
4 analogue output: 0–5mAAO7
4 analogue output: ±5mAAO8
Communication
Ethernet (TCP/IP)ETHD
RS232/422/485RS232D
Modem – 4G (optional external on application)*T4T-x

*Modem antennas: x = T – top, or F – front

Digital I/O and relay outputs
4 digital inputs (dry contact) / 2 relay output 250V/5A ACDIOR
4 digital inputs (dry contact) / 2 SSR output 250V/0.1A ACDIOS
8 digital inputs (dry contact) / 2 SSR output 250V/0.1A AC8DI
12 digital inputs (dry contact) / 4 relay outputs 250V/5A AC12DIOR-DRC
12 digital inputs (48VDC) / 4 relay outputs 250V/5A AC12DIOR-48V
12 digital inputs (125VDC) / 4 relay outputs 250V/5A AC12DIOR-125V
12 digital inputs (250VDC) / 4 relay outputs 250V/5A AC12DIOR-250V
As above, with RS485 — dry contact / 48V / 125V / 250V…-485
As above, with Ethernet — dry contact / 48V / 125V / 250V…-ETH