PRO SERIES ยท ALARMS
What do EM235 and PM335 PRO setpoint alarms and TCP notifications tell the receiving system?

Quick answer
In the EM235 PRO and PM335 PRO, an alarm is a control setpoint. The meter has 64 of them. Each setpoint tests up to four conditions joined by OR or AND. When the expression becomes true, it can run up to four actions.
The manual describes these ways an operated setpoint can be seen from outside the meter:
| How it is seen | What the receiving system gets |
|---|---|
| Setpoint status register | The present status of each setpoint, readable over communications |
| Setpoint alarm latch register | The last operated alarm status, held until it is explicitly cleared |
| Relay action | A relay contact change |
| Event log action | A time-stamped record of the conditions that caused the event and the actions taken |
| Notification action | A message written to a Modbus/TCP server, with time stamps and the trigger value |
On the front display, Logs and Diagnostics, then Alarms/Event Log, lists the operated alarm setpoints with their trigger labels.
Applies to
The standard EM235 PRO and PM335 PRO. The manual and the Modbus guide cover both models together. We found no model difference in the sections this page cites, and those sections don't state a firmware version. FCAS variants aren't covered.
How a setpoint decides
- Analogue triggers have an operate limit and a release limit, which give hysteresis. Both are in primary units.
- An operate delay and a release delay (0โ10,000.000 seconds) mean "the logical controller changes the setpoints status only if all conditions are asserted for a period at least as long as the delay time". Delays don't work with pulsed events.
- "The scan time for all setpoints is 1/2 cycle time (8 ms at 60Hz and 10 ms at 50 Hz)."
- Setpoint 1 is factory preset to run Data logs 1 and 2 at 15-minute boundaries of an hour.
Getting a setpoint into the Event log
By default, the Event recorder stores configuration changes, resets and device diagnostics. It records a setpoint only when that setpoint has the "Event log" action in its action list. The manual recommends putting the Event log action first in the list, so other recorders can use the event's sequence number.
SATEC Australia's advice: if an alarm you expected isn't in the Event log, check whether that setpoint has the Event log action. For PAS basics, see PAS.
TCP notifications
The TCP notification client connects to a remote Modbus/TCP server and sends a message when an event occurs, or periodically.
The manual's setup has two parts:
- In PAS, Meter Setup, Communication Setup, TCP Notification Client Setup tab: Client Enabled (default NO), the server's IP address, the server port (default 502) and the Message Exchange Address (default 1000).
- A setpoint with the Notification action in its action list. The Modbus guide says to add it "to the end of the Setpoint actions list".
What a notification message contains
The Modbus reference guide, BG0613 section 2.10, describes the message structure:
- the device's serial number, MAC address, device address and IP address;
- the event type and an event sequence number;
- start and end time stamps, in local time as seconds since 1 January 1970 plus microseconds;
- the ID and value of the critical trigger.
The meter writes the message to the server's registers starting at the Message Exchange Address.
How often notifications are sent
- Ordinary setpoint triggers are reported twice. The first message, when the event starts, has the end time stamp set to zero and gives the trigger's entering value. The second, when it ends, gives both time stamps and the trigger's return value.
- Pulsed events and time triggers are reported once.
- Power quality and fault triggers, such as PQ EVENT, FAULT EVENT, EXTERNAL TRIGGER and FAULT DETECTED, report the recorded power quality or fault event instead. The message gives the fault event's start and end times, a critical phase and the maximum fault magnitude on that phase. The guide adds: "If regular triggers are added to the Setpoint triggers list, then the Setpoint operation events will also be reported."
Notification connection behaviour
After the server acknowledges the write, the meter keeps the connection open for 10 seconds so the server can read registers through it. If the server doesn't need that, the guide recommends it close the connection straight away. Otherwise the next notification waits 10 seconds. If a connection attempt fails, the client retries twice more before declaring a connection failure.
Where the documents disagree
The manual's setup table says the Message Exchange Address is the start of "a block of 16 MODBUS registers". The Modbus guide says messages are sent in "a block of 24 Modbus registers", and its layout uses 24 registers. SATEC Australia's advice: when you set up the receiving server, check its register block against the layout in BG0613 section 2.10, and contact technical support if the two don't match on your system.
When an alarm didn't arrive
First check the On-line button on the PAS toolbar and select the meter's site. The manual says that, on-line, "As the setup dialog box opens, PAS retrieves and displays the present meter setup data". Off-line, PAS shows the setup stored in the site database, not the meter's.
SATEC Australia's advice: these checks only read the meter. Don't change any values or click Send, which writes the setup to the meter. Don't press Clear or Reset either, because that clears counters or records you may need.
- Check the setpoint. In PAS, open Meter Setup, General Setup, Control/Alarm Setpoints. Check that the setpoint exists, and that its triggers, limits, delays and actions are what you expect.
- Check the notification client. On the TCP Notification Client Setup tab, check Client Enabled, the server IP address, the port and the Message Exchange Address.
- Check the connection statistics. With PAS on-line, open Monitor, Device Control, Communications tab. It shows connection statistics for the TCP clients.
- Check the Event log, if the setpoint has the Event log action.
What to send technical support
Contact SATEC Australia technical support through our contact form. SATEC Australia's advice is to include:
- the model (EM235 PRO or PM335 PRO), order code and firmware version;
- a saved copy of the meter's setup, made before any changes;
- the setpoint number and what you expected it to do;
- the time of the event, and the Event log records around it;
- what the receiving server logged, including the registers it received.
Manuals and source pages
- EM235/PM335 PRO Installation and Operation Manual, BG0612 Rev. A8, December 2024 (PDF on our site). Printed page numbers match the PDF pages:
- Logs and Diagnostics display, page 84.
- Setting Up TCP Notification Client, Table 7, page 103.
- Using Control Setpoints, Table 17, pages 120โ123.
- Configuring the Event Recorder, page 132.
- Viewing Communication Status and Statistics, page 164.
- Table 25 Setpoint Actions, page 211.
- EM235/PM335 PRO Modbus Reference Guide, BG0613 Rev. A8, section 2.10 TCP Notification Client, pages 14โ15. Our manuals page also links an older revision, A6.
- Evidence checked 22 November 2026.
Source review: 22 November 2026.